<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Hazardous_area_classification</id>
	<title>Hazardous area classification - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Hazardous_area_classification"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Hazardous_area_classification&amp;action=history"/>
	<updated>2026-11-24T11:46:32Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Hazardous_area_classification&amp;diff=9648&amp;oldid=prev</id>
		<title>Lisa: Add New Zealand guidance on reviewing a classification after process changes</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Hazardous_area_classification&amp;diff=9648&amp;oldid=prev"/>
		<updated>2026-11-23T19:05:26Z</updated>

		<summary type="html">&lt;p&gt;Add New Zealand guidance on reviewing a classification after process changes&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 20:05, 23 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l30&quot;&gt;Line 30:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 30:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Intrinsic safety limits the energy available in a circuit under specified conditions. A flameproof enclosure permits ignition inside while preventing flame transmission to the surrounding atmosphere. A [[Purged and pressurised enclosure|pressurised enclosure]] uses a supply of protective gas to prevent the surrounding atmosphere from entering. These protective principles address ignition by the equipment. Process ventilation and control of combustible deposits address the formation of the atmosphere itself.&amp;lt;ref name=&amp;quot;protection&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;evaluation&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Intrinsic safety limits the energy available in a circuit under specified conditions. A flameproof enclosure permits ignition inside while preventing flame transmission to the surrounding atmosphere. A [[Purged and pressurised enclosure|pressurised enclosure]] uses a supply of protective gas to prevent the surrounding atmosphere from entering. These protective principles address ignition by the equipment. Process ventilation and control of combustible deposits address the formation of the atmosphere itself.&amp;lt;ref name=&amp;quot;protection&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;evaluation&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;== Recording and reviewing the boundary ==&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;A drawing can show the vapour space inside equipment, openings from which material escapes, and low points outside it. Recording which solvent is in use and which ventilation is operating gives the drawing a basis that operators can check when the process changes. For example, adding a second dipping line may introduce another release source next to a motor that stood outside the original boundary.&amp;lt;ref name=&quot;zoning&quot; /&amp;gt;&amp;lt;ref name=&quot;dipping&quot; /&amp;gt;&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;The New Zealand part of the 2005 &#039;&#039;International Fire Engineering Guidelines&#039;&#039; describes reviewing an existing fire engineering assessment when a change of use or design affects its assumptions. Applied to a classified area, that review asks whether the original release sources, paths and protective equipment still match the installation. The handbook&#039;s coating examples show why introducing a new solvent, adding equipment or increasing production can warrant that review.&amp;lt;ref name=&quot;change&quot;&amp;gt;Australian Building Codes Board et al. (2005), New Zealand part 0, §§0.3.2.8 and 0.3.3. Katunar (2008), chap. 9.3, p. 9-47.&amp;lt;/ref&amp;gt;&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== See also ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== See also ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l42&quot;&gt;Line 42:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 47:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== References ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== References ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;* Australian Building Codes Board, National Research Council of Canada, International Code Council, &amp;amp; Department of Building and Housing, New Zealand. (2005). &#039;&#039;International fire engineering guidelines&#039;&#039; (2005 ed.). Australian Building Codes Board.&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Beyler, C. (2002). Flammability limits of premixed and diffusion flames. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., chap. 2.7). National Fire Protection Association and Society of Fire Protection Engineers.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Beyler, C. (2002). Flammability limits of premixed and diffusion flames. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., chap. 2.7). National Fire Protection Association and Society of Fire Protection Engineers.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Cholin, J. M. (2008). Gas and vapor detection systems and monitors. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 14.8). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Cholin, J. M. (2008). Gas and vapor detection systems and monitors. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 14.8). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-9642:rev-9648:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Lisa</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Hazardous_area_classification&amp;diff=9642&amp;oldid=prev</id>
		<title>Lisa: New FSE wiki article: Hazardous area classification (written by Codex)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Hazardous_area_classification&amp;diff=9642&amp;oldid=prev"/>
		<updated>2026-11-23T19:03:33Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Hazardous area classification (written by Codex)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Hazardous area classification&amp;#039;&amp;#039;&amp;#039; identifies places where a flammable gas, vapour or combustible dust can mix with air in quantities that present an [[Explosion|explosion]] hazard. The classification describes where such an atmosphere can occur and under what operating conditions. It informs the selection and location of equipment that could act as an [[Ignition source|ignition source]]. Predicting the pressure or damage from an explosion requires a separate assessment of the material, the mixture and its confinement.&amp;lt;ref name=&amp;quot;electrical&amp;quot;&amp;gt;Milatovich (2008), chap. 8.13, pp. 8-164 and 8-168–8-171.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;evaluation&amp;quot;&amp;gt;Zalosh (2002), chap. 3.16, p. 3-402.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The boundary can run through a room or even through a piece of equipment. In a dipping process, for example, vapour can come from the open liquid surface and from freshly coated work as it leaves the tank. Vapour denser than air may reach a floor recess some distance from the tank. A useful classification therefore describes the release sources, how ventilation moves the vapour, and the spaces where it can collect.&amp;lt;ref name=&amp;quot;dipping&amp;quot;&amp;gt;Katunar (2008), chap. 9.3, pp. 9-45–9-47.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== From a release to an explosive atmosphere ==&lt;br /&gt;
For a gas or vapour, flame can travel through a mixture only within a range of fuel concentrations in air. The [[Flammability limits|flammability limits]] apply at a specified temperature and pressure. A liquid&amp;#039;s [[Flash point|flash point]] gives information about its ability to produce ignitable vapour under a defined test. The distance that vapour travels after release depends on the size and location of the exposed surface, the ventilation and nearby pits.&amp;lt;ref name=&amp;quot;beyler&amp;quot;&amp;gt;Beyler (2002), chap. 2.7, p. 2-172.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;liquid&amp;quot;&amp;gt;Slye (2008), chap. 6.12, pp. 6-197–6-201.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;dipping&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[File:fse-hazardous-area-classification-v1.svg|thumb|right|upright=1.65|alt=Vapour rises from an open liquid and a freshly coated workpiece. A dashed path shows denser vapour reaching a nearby floor recess.|The exposed liquid and wetted workpiece both release vapour. A floor recess can collect dense vapour. Based on Katunar (2008), pp. 9-45–9-47.]]&lt;br /&gt;
&lt;br /&gt;
A fixed exhaust at the rim of a tank can capture vapour close to the source. The result depends on the supply of replacement air and on whether extraction is running while the process releases vapour. If a workpiece continues to give off solvent while it drains, the assessment follows the workpiece beyond the tank. A change of coating, an opening in an enclosure or a relocated exhaust inlet can alter the area concerned.&amp;lt;ref name=&amp;quot;dipping&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Zones and divisions ==&lt;br /&gt;
The zone approach used internationally distinguishes between circumstances in which an ignitable atmosphere can occur. An open solvent bath releases vapour during normal work. With a normally closed process, the assessment may instead examine a leak or loss of ventilation. The &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039; describes the zone system of the International Electrotechnical Commission (IEC) and its recognition for gases and vapours under the US National Electrical Code.&amp;lt;ref name=&amp;quot;electrical&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;frameworks&amp;quot;&amp;gt;Cholin (2008), chap. 14.8, p. 14-102.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An open-container example in the handbook distinguishes three gas zones. It shows Zone 0 in the vapour space of the container, Zone 1 near the opening and Zone 2 farther out near floor level. The geometry is specific to the illustrated liquid-handling process. Applying the same distances to a different solvent or installation would discard the assumptions about the release and its ventilation.&amp;lt;ref name=&amp;quot;zoning&amp;quot;&amp;gt;Katunar (2008), chap. 9.3, pp. 9-45–9-47, especially fig. 9.3.15.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In its account of the European Union framework for explosive atmospheres (ATEX), the handbook distinguishes classification of the workplace from assessment of the equipment used there. In the US class-and-division system it describes, Class I concerns gases and vapours, Class II combustible dusts, and Class III ignitable fibres or flyings. A division further describes the conditions under which the hazard can be present. Each system has its own designations and equipment approvals.&amp;lt;ref name=&amp;quot;electrical&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;frameworks&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Dust clouds and settled layers ==&lt;br /&gt;
A combustible powder can settle between operations. A moving belt, a transfer point or a disturbance of a deposit can put dust back into the air. In a [[Grain elevator|grain handling facility]], an overheating bearing or a slipping belt can introduce heat near dust-handling equipment. The enclosure, its openings and deposits on nearby surfaces therefore matter even when the room air looks clear during an inspection.&amp;lt;ref name=&amp;quot;grain&amp;quot;&amp;gt;Maness and Sargent (2008), chap. 9.7, pp. 9-97–9-99.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;dust&amp;quot;&amp;gt;Zalosh (2008), chap. 2.8, pp. 2-99–2-101.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[File:fse-hazardous-area-classification-v2.svg|thumb|right|upright=1.65|alt=Dust settles on a ledge in the first panel. In the second, a disturbance has lifted particles into the surrounding air.|A layer on a ledge can supply a dust cloud when disturbed. Based on Zalosh (2008), pp. 2-100–2-101.]]&lt;br /&gt;
&lt;br /&gt;
A [[Dust explosion|dust explosion]] inside equipment can disturb deposits on beams or floors. Dust dispersed by the pressure wave can then fuel a second event outside the original enclosure. Deposits can also affect electrical equipment by insulating a hot surface or interfering with heat loss. The likelihood of a suspended cloud and the presence of a settled layer are therefore separate observations in the assessment.&amp;lt;ref name=&amp;quot;dust&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;electrical&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== What the classification tells an equipment designer ==&lt;br /&gt;
The designer needs the area designation, the substance involved and the equipment&amp;#039;s maximum surface temperature. A motor can present a hot surface, while a switch or instrument circuit can produce a spark. The [[Minimum ignition energy|minimum ignition energy]] describes how readily a specified mixture ignites from an electrical discharge under test conditions. Gas grouping, ignition energy and ignition temperature describe different properties. Equipment selection therefore needs information about the substance as well as the area designation.&amp;lt;ref name=&amp;quot;protection&amp;quot;&amp;gt;Beyler (2002), chap. 2.7, pp. 2-181–2-182. Milatovich (2008), chap. 8.13, pp. 8-168–8-171.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[File:fse-hazardous-area-classification-v3.svg|thumb|right|upright=1.65|alt=Three symbols show energy limitation in a circuit, flame containment inside an enclosure and positive pressure from protective gas.|Intrinsic safety, flameproof containment and pressurisation control different routes to ignition. Based on Beyler (2002), pp. 2-181–2-182, and Milatovich (2008), pp. 8-169–8-171.]]&lt;br /&gt;
&lt;br /&gt;
Intrinsic safety limits the energy available in a circuit under specified conditions. A flameproof enclosure permits ignition inside while preventing flame transmission to the surrounding atmosphere. A [[Purged and pressurised enclosure|pressurised enclosure]] uses a supply of protective gas to prevent the surrounding atmosphere from entering. These protective principles address ignition by the equipment. Process ventilation and control of combustible deposits address the formation of the atmosphere itself.&amp;lt;ref name=&amp;quot;protection&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;evaluation&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Autoignition temperature]]&lt;br /&gt;
* [[Hydrogen safety]]&lt;br /&gt;
* [[Flame detector]]&lt;br /&gt;
* [[Spray booth]]&lt;br /&gt;
* [[Explosionproof equipment]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Beyler, C. (2002). Flammability limits of premixed and diffusion flames. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., chap. 2.7). National Fire Protection Association and Society of Fire Protection Engineers.&lt;br /&gt;
* Cholin, J. M. (2008). Gas and vapor detection systems and monitors. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 14.8). National Fire Protection Association.&lt;br /&gt;
* Katunar, J., III. (2008). Dipping and coating processes. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 9.3). National Fire Protection Association.&lt;br /&gt;
* Maness, J. E., &amp;amp; Sargent, L. M. (2008). Storage and handling of grain mill products. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 9.7). National Fire Protection Association.&lt;br /&gt;
* Milatovich, R. M. (2008). Electrical systems and appliances. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 8.13). National Fire Protection Association.&lt;br /&gt;
* Slye, O. M., Jr. (2008). Flammable and combustible liquids. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 6.12). National Fire Protection Association.&lt;br /&gt;
* Zalosh, R. (2002). Explosion protection. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., chap. 3.16). National Fire Protection Association and Society of Fire Protection Engineers.&lt;br /&gt;
* Zalosh, R. (2008). Explosions. In A. E. Cote (Ed.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., chap. 2.8). National Fire Protection Association.&lt;br /&gt;
&lt;br /&gt;
[[Category:Explosions &amp;amp; Industrial Fires]]&lt;/div&gt;</summary>
		<author><name>Lisa</name></author>
	</entry>
</feed>