<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Halon</id>
	<title>Halon - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Halon"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Halon&amp;action=history"/>
	<updated>2026-11-21T22:12:58Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Halon&amp;diff=9308&amp;oldid=prev</id>
		<title>Peter: Wiki review: corrected 5 errors: markup (3), citation (2) (Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Halon&amp;diff=9308&amp;oldid=prev"/>
		<updated>2026-11-15T23:41:38Z</updated>

		<summary type="html">&lt;p&gt;Wiki review: corrected 5 errors: markup (3), citation (2) (Claude Opus 5.5)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 00:41, 16 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v1.svg|thumb|upright=1.5|alt=&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Connect historical applications with replacement &lt;/del&gt;assessment&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;.&lt;/del&gt;|&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Connect historical &lt;/del&gt;applications &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;with &lt;/del&gt;replacement &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;assessment&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v1.svg|thumb|upright=1.5|alt=&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Halon branches into flame inhibition, used in streaming application and total flooding, and into agent-specific &lt;/ins&gt;assessment &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;of exposure and environmental effects&lt;/ins&gt;|&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Historical &lt;/ins&gt;applications &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;of halon and the separate questions in assessing a particular agent or &lt;/ins&gt;replacement.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l20&quot;&gt;Line 20:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 20:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.&amp;lt;ref name=&amp;quot;F-95a10b91d4&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.&amp;lt;ref name=&amp;quot;F-95a10b91d4&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.&amp;lt;ref name=&quot;G-48f9ac6e19&quot;&amp;gt;DiNenno (2002), &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 4-174.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;F-8cbcab761a&quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.&amp;lt;ref name=&quot;G-48f9ac6e19&quot;&amp;gt;DiNenno (2002), &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 4-174.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;F-8cbcab761a&quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l26&quot;&gt;Line 26:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 26:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Concentration, distribution and discharge ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Concentration, distribution and discharge ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v2.svg|thumb|upright=1.5|alt=&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Explain &lt;/del&gt;the &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;mechanism supporting halon.&lt;/del&gt;|&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Explain the mechanism supporting halon&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v2.svg|thumb|upright=1.5|alt=&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Stored agent is discharged through &lt;/ins&gt;the &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;distribution system into the protected volume, where the concentration after delivery must be retained over time&lt;/ins&gt;|&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Delivery and time-dependent retention of a gaseous agent in a protected volume&lt;/ins&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.&amp;lt;ref name=&quot;G-b3ce0218d6&quot;&amp;gt;DiNenno (2002), &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 4-175.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;F-4d17adc0ab&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.&amp;lt;ref name=&quot;G-b3ce0218d6&quot;&amp;gt;DiNenno (2002), &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 4-175.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;F-4d17adc0ab&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l54&quot;&gt;Line 54:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 54:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Laboratory evidence and system verification ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Laboratory evidence and system verification ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v3.svg|thumb|upright=1.5|alt=&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Distinguish complementary &lt;/del&gt;evidence &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;needed to assess halon.&lt;/del&gt;|&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Distinguish complementary &lt;/del&gt;evidence &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;needed to assess &lt;/del&gt;halon.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v3.svg|thumb|upright=1.5|alt=&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Four types of &lt;/ins&gt;evidence &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;(laboratory extinction, distribution evidence, enclosure leakage and retention prediction), each with what it shows and what it does not prove, combined into a complete assessment that is reassessed after change&lt;/ins&gt;|&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;Complementary &lt;/ins&gt;evidence &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;and its limits in assessing a &lt;/ins&gt;halon &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;system&lt;/ins&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-6660:rev-9308:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Halon&amp;diff=6660&amp;oldid=prev</id>
		<title>Mark: Remove source references from image captions</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Halon&amp;diff=6660&amp;oldid=prev"/>
		<updated>2026-11-13T07:30:14Z</updated>

		<summary type="html">&lt;p&gt;Remove source references from image captions&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:30, 13 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v1.svg|thumb|upright=1.5|alt=Connect historical applications with replacement assessment.|Connect historical applications with replacement assessment&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99; Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103; Cote et al. (2008), chapter 17.6, pp. 17-93–17-94, 17-102–17-103, 17-120–17-121&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v1.svg|thumb|upright=1.5|alt=Connect historical applications with replacement assessment.|Connect historical applications with replacement assessment.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l26&quot;&gt;Line 26:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 26:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Concentration, distribution and discharge ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Concentration, distribution and discharge ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v2.svg|thumb|upright=1.5|alt=Explain the mechanism supporting halon.|Explain the mechanism supporting halon&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cote et al. (2008), chapter 17.1, pp. 17-5–17-8; Cote et al. (2008), chapter 17.6, pp. 17-110–17-112; DiNenno (2002), pp. 4-175&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v2.svg|thumb|upright=1.5|alt=Explain the mechanism supporting halon.|Explain the mechanism supporting halon.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l54&quot;&gt;Line 54:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 54:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Laboratory evidence and system verification ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Laboratory evidence and system verification ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v3.svg|thumb|upright=1.5|alt=Distinguish complementary evidence needed to assess halon.|Distinguish complementary evidence needed to assess halon&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on DiNenno (2002), pp. 4-175; Cote et al. (2008), chapter 17.6, pp. 17-110–17-112; Cote et al. (2008), chapter 17.6, pp. 17-119–17-121&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-halon-v3.svg|thumb|upright=1.5|alt=Distinguish complementary evidence needed to assess halon.|Distinguish complementary evidence needed to assess halon.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-6212:rev-6660:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Mark</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Halon&amp;diff=6212&amp;oldid=prev</id>
		<title>Peter: Add SVG figures fse-halon-v1.svg, fse-halon-v2.svg, fse-halon-v3.svg (list-4 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Halon&amp;diff=6212&amp;oldid=prev"/>
		<updated>2026-11-12T15:16:01Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-halon-v1.svg, fse-halon-v2.svg, fse-halon-v3.svg (list-4 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 16:16, 12 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-halon-v1.svg|thumb|upright=1.5|alt=Connect historical applications with replacement assessment.|Connect historical applications with replacement assessment. Based on Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99; Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103; Cote et al. (2008), chapter 17.6, pp. 17-93–17-94, 17-102–17-103, 17-120–17-121.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l25&quot;&gt;Line 25:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 26:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Concentration, distribution and discharge ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Concentration, distribution and discharge ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-halon-v2.svg|thumb|upright=1.5|alt=Explain the mechanism supporting halon.|Explain the mechanism supporting halon. Based on Cote et al. (2008), chapter 17.1, pp. 17-5–17-8; Cote et al. (2008), chapter 17.6, pp. 17-110–17-112; DiNenno (2002), pp. 4-175.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l52&quot;&gt;Line 52:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 54:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Laboratory evidence and system verification ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Laboratory evidence and system verification ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-halon-v3.svg|thumb|upright=1.5|alt=Distinguish complementary evidence needed to assess halon.|Distinguish complementary evidence needed to assess halon. Based on DiNenno (2002), pp. 4-175; Cote et al. (2008), chapter 17.6, pp. 17-110–17-112; Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-3836:rev-6212:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Halon&amp;diff=3836&amp;oldid=prev</id>
		<title>Thomas: New FSE wiki article: Halon (written by GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Halon&amp;diff=3836&amp;oldid=prev"/>
		<updated>2026-11-07T21:38:47Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Halon (written by GPT-6)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Halon&amp;#039;&amp;#039;&amp;#039; is a name used for halogenated fire-extinguishing compounds, particularly the brominated agents historically employed in portable and fixed protection equipment. The Fire Protection Handbook describes Halon 1211 and Halon 1301 as examples with different principal applications. Their effectiveness includes chemical interference with the reactions sustaining a flame.&amp;lt;ref name=&amp;quot;F-6d7cde6281&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
These [[Extinguishing mechanisms|extinguishing mechanisms]] made halons useful where rapid [[Flame extinction|flame extinction]], electrical non-conductivity and low residue were valued. A [[Gaseous extinguishing system|gaseous extinguishing system]] using halon nevertheless required suitable distribution, concentration and exposure controls. Low residue did not establish absence of physiological or environmental effects.&amp;lt;ref name=&amp;quot;F-3b7451a2c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-98–17-99, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Concern about ozone depletion drove development of alternatives, including the [[Halocarbon clean agent|halocarbon clean agent]] family addressed alongside inert gases by [[NFPA 2001]]. The handbook also discusses environmental assessment involving the [[Environmental Protection Agency]] and decomposition products such as [[Hydrogen fluoride|hydrogen fluoride]]. Its regulatory and product-history discussion describes the period covered by the 2008 edition.&amp;lt;ref name=&amp;quot;F-d006ae6871&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-94, 17-102–17-103, 17-120–17-121.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Meaning and engineering application ==&lt;br /&gt;
Halogen substitution changes the properties of the original hydrocarbon molecule. The handbook describes compounds containing fluorine, chlorine, bromine or iodine, with different extinguishing and physiological characteristics. It therefore does not treat every halogenated compound as an interchangeable fire agent. The particular composition determines which mechanisms and limitations are relevant.&amp;lt;ref name=&amp;quot;F-cc548d64a7&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The brominated halons have a strong chemical effect on flame reactions. The handbook contrasts this with the predominantly thermal action of some replacement agents. This distinction explains why a replacement cannot be selected by assuming equal concentrations or identical equipment performance. The design follows the chosen agent and its test evidence.&amp;lt;ref name=&amp;quot;F-95a10b91d4&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-95–17-96, 17-98–17-99.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Historical applications also differed between agents. Halon 1211 was widely associated with streaming equipment, while Halon 1301 was extensively used for total flooding. The handbook describes the latter&amp;#039;s development in protection of electronics and other special hazards. These examples explain the terminology and design heritage; they do not establish the current availability or permitted use of any named agent.&amp;lt;ref name=&amp;quot;F-7f2ffbc83b&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-94.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Replacement involved more than finding another compound that extinguishes a small flame. Exposure, decomposition, ozone effects and system delivery all required assessment. The SFPE chapter on replacement agents consequently considers clean-agent properties and suppression mechanisms together. Performance equivalence needs evidence for the complete application rather than similarity of purpose or a shared description as residue-free.&amp;lt;ref name=&amp;quot;G-cbc28f5156&amp;quot;&amp;gt;DiNenno (2002), pp. 4-174–4-175.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-ed42b172a1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Thermal and chemical extinguishing mechanisms ==&lt;br /&gt;
A gaseous extinguishant changes the conditions supporting combustion around the flame. The SFPE treatment distinguishes thermal effects, dilution and chemical inhibition rather than assigning one identical mechanism to all agents. Adding a gas can increase the energy needed to maintain the reacting mixture at flame temperature. Some halogenated agents also interfere with the chemical reactions sustaining the flame.&amp;lt;ref name=&amp;quot;G-cbc28f5156&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Inert-gas agents mainly act through dilution and the resulting thermal balance. Halocarbon agents can combine heat absorption with chemical effects, depending on their composition. The handbook distinguishes the strong chemical contribution of brominated halons from the predominantly thermal action of some replacements. Similar equipment purposes therefore do not establish identical suppression mechanisms or identical required concentrations.&amp;lt;ref name=&amp;quot;F-95a10b91d4&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Carbon dioxide requires separate treatment. It can provide an electrically non-conductive, residue-free extinguishing medium, but it is not interchangeable with the inert-gas blends discussed as clean agents. Its physiological effects are significant at extinguishing concentrations. The SFPE chapter explicitly distinguishes carbon dioxide from those replacement clean agents when discussing suitability for occupied spaces.&amp;lt;ref name=&amp;quot;G-48f9ac6e19&amp;quot;&amp;gt;DiNenno (2002), pp. 4-174.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-8cbcab761a&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-3–17-5.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Flame extinguishment does not necessarily remove stored heat. A solid material can remain hot, a concealed fire can continue, or an ignition source can persist after a visible flame disappears. The handbook therefore separates surface fires from deep-seated hazards and discusses retention and energy isolation. The chosen mechanism must operate for the relevant fuel arrangement, with sufficient duration to achieve the intended protection outcome.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Concentration, distribution and discharge ==&lt;br /&gt;
Total flooding establishes an extinguishing concentration within an enclosure surrounding the hazard. Local application instead directs agent at a specified object or surface. These arrangements require different design evidence because an enclosure can retain agent while an exposed hazard allows it to disperse. The handbook treats them separately in its carbon dioxide chapter and connects each with the geometry of the protected fire.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Stored quantity is only one part of total-flooding performance. The agent must leave its storage arrangement, pass through the distribution system and reach the protected volume in the intended time. Nozzle characteristics and distribution determine whether the concentration is adequate where the fire can occur. The handbook accordingly relates clean-agent performance to tested equipment arrangements and to the geometry used in demonstrating distribution.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The concentration needed to extinguish a laboratory flame is different from the concentration adopted for a complete system. Small-scale tests provide information about a particular agent, fuel and procedure. The system assessment also includes distribution, the hazard and the applicable design allowances. Treating a minimum extinguishing concentration as an installation prescription omits these additional conditions and the evidence supporting them.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot;&amp;gt;DiNenno (2002), pp. 4-175.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Ventilation and openings affect the concentration after discharge. Continued air movement can remove agent, while an open connection can spread it into an adjoining space. The operating sequence can therefore include ventilation shutdown, closure of openings and isolation of continuing energy sources. The assessment follows the whole protected volume and its connected spaces, rather than considering the discharge container in isolation.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Enclosure leakage and retention ==&lt;br /&gt;
An enclosure is part of a total-flooding system because it influences where the agent travels and how long it remains. Doors, service penetrations, ducts and construction joints can provide leakage paths. The importance of a path depends on its size, position and the pressure conditions across it. A room that appears closed can therefore differ substantially from the enclosure assumed in the design.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Retention is the maintenance of an adequate concentration for the required period. Its purpose depends on the fire, including the possibility of re-ignition from hot material or continuing electrical energy. The handbook discusses different retention needs for different hazards and system arrangements. A single observation immediately after discharge cannot establish that the protective atmosphere persists for the intended duration.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A fan-based integrity assessment uses pressure and airflow measurements to estimate enclosure leakage. A model then relates that leakage to the expected loss of agent under stated assumptions. Leakage distribution and the behaviour of the gas mixture influence the result. The test therefore evaluates an enclosure characteristic and supports a retention prediction; it is not a direct demonstration that the extinguishing nozzles discharge correctly.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Pressure relief and retention must also be considered together. The discharge can change enclosure pressure, while an opening that relieves pressure can allow agent to escape. The design has to account for both functions and their operating states. Later changes to doors, ventilation or penetrations can alter that balance, which connects enclosure assessment with the IFEG requirement to review the assumptions affected by building alterations.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;I-68e160c6fb&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.8; p. 0.3-7.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Exposure endpoints and occupied spaces ==&lt;br /&gt;
Extinguishing effectiveness and human exposure are separate assessment questions. The concentration that removes a flame does not by itself establish acceptable conditions for people. Relevant effects depend on the agent, concentration, duration and the circumstances of exposure. The handbook therefore treats toxicological information alongside extinguishing performance, rather than using one measurement as a substitute for the other.&amp;lt;ref name=&amp;quot;F-ed42b172a1&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-1115be49e3&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.7, pp. 17-129–17-130.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The no-observed-adverse-effect level, or NOAEL, identifies the highest tested exposure level without the specified adverse effect. The lowest-observed-adverse-effect level, or LOAEL, identifies the lowest tested level at which that effect was observed. These are experimental endpoints with defined test conditions. They do not describe a universal boundary between harmless and harmful exposure for every person and duration.&amp;lt;ref name=&amp;quot;F-ed42b172a1&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For halocarbon agents, the handbook discusses cardiac sensitisation testing and the relationship between concentration, uptake and exposure duration. Inert-gas protection raises the separate issue of reduced oxygen concentration. Carbon dioxide adds direct physiological effects and cannot be assessed solely as an oxygen-displacing gas. These differences prevent a common exposure rule from being inferred merely because all three media can extinguish a fire.&amp;lt;ref name=&amp;quot;F-ed42b172a1&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-e5df5e33c1&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-4–17-5.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The fire itself also changes the atmosphere. Combustion products remain relevant, and some agents can form decomposition products when exposed to flame or hot surfaces. Warning, evacuation and the discharge sequence consequently belong within the system assessment. The handbook&amp;#039;s historical concentration tables support understanding of the assessment method; they do not establish a current permitted exposure for an unspecified installation or population.&amp;lt;ref name=&amp;quot;F-b43c0dfd83&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-101–17-103, 17-120–17-121.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Laboratory evidence and system verification ==&lt;br /&gt;
The cup burner provides a controlled method of studying flame extinction. Liquid fuel burns at a small cup while an air stream surrounds the flame. Agent is introduced into that stream until extinction occurs under the defined procedure. The result describes a particular combination of agent, fuel and experimental conditions, rather than the behaviour of every possible fire in a building.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
System-level tests answer additional questions. Distribution tests can examine whether the chosen nozzles establish adequate conditions in the protected volume. Tests using representative solid materials address hazards that differ from the small liquid flame. The handbook consequently discusses more than one test arrangement when describing clean-agent approval and design. Evidence at one scale contributes to the assessment but does not automatically replace evidence at another.&amp;lt;ref name=&amp;quot;F-4d17adc0ab&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The installed enclosure presents a further set of questions. Leakage testing supports assessment of retention, while inspection examines openings and the conditions assumed by the calculation. Neither test demonstrates every part of the release circuit or distribution piping. Commissioning therefore needs to connect the separate evidence for controls, agent delivery and enclosure behaviour with the intended operating sequence.&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;I-d6b6a6d1a7&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.4; p. 0.3-6.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Uncertainty enters through both measurement and representation of the hazard. A laboratory flame has controlled geometry and ventilation, whereas equipment can contain obstructed or concealed burning surfaces. The design concentration and retention requirement must relate to the relevant fire evidence and system conditions. The defensible result is a stated protection claim with identifiable assumptions, rather than a general assertion that any fire will be extinguished.&amp;lt;ref name=&amp;quot;G-b3ce0218d6&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-30d0907eb9&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-110–17-112, 17-119–17-121.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Residue, decomposition and environmental effects ==&lt;br /&gt;
The term clean agent concerns properties relevant to the protected equipment, particularly electrical conductivity and residue after discharge. It does not mean that the agent has no physiological or environmental effects. The SFPE treatment separates these matters when comparing alternatives to halon. An assessment can therefore favour an agent for sensitive equipment while still requiring separate evaluation of exposure and environmental consequences.&amp;lt;ref name=&amp;quot;G-cbc28f5156&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Halon replacement followed concern about stratospheric ozone depletion. The handbook describes the development of alternatives and the recovery of halon for particular continuing applications. This is a historical account of the situation discussed in the 2008 edition. The chemistry explaining ozone effects is different from the criteria used to describe persistence or climate effects, so one environmental property cannot stand for all others.&amp;lt;ref name=&amp;quot;F-9a3029ccdc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-94, 17-102–17-103.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Thermal decomposition is another distinct issue. A halogenated agent exposed to fire can form products with different properties from the original extinguishant. The quantity formed depends on the fire and the conditions during discharge. Early detection and effective suppression can affect the duration of contact between agent and flame. The handbook therefore connects decomposition with system performance, rather than treating it only as a stored-product characteristic.&amp;lt;ref name=&amp;quot;F-a007a9bec0&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-102–17-103, 17-120–17-121.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Comparisons must retain the conditions supporting each claim. A statement about residue, ozone depletion or extinguishing concentration answers a different question from a statement about occupancy or allowable use. The historical handbook provides a technical framework for these comparisons, but not a current inventory of permitted products. Product selection requires the relevant agent identity, performance evidence and governing edition to remain explicit within the assessment.&amp;lt;ref name=&amp;quot;F-175594eb1b&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-93–17-96, 17-101–17-103.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Protection objectives and limits of performance ==&lt;br /&gt;
Suppression describes an intended change in a fire, but the required outcome needs further definition. Control can limit growth or reduce the rate of heat release without extinguishing every burning item. Extinguishment removes the continuing combustion under the conditions considered. Prevention of renewed burning may require cooling, continued agent retention or removal of an ignition source. These outcomes impose different demands on the protection arrangement.&amp;lt;ref name=&amp;quot;F-a7e389f0f3&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.3, pp. 17-32–17-33.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Agent selection follows the fuel and the objective. Water can cool a solid surface, foam can maintain a barrier over a liquid, and a gaseous agent can change the atmosphere surrounding a fire. None of these descriptions establishes universal effectiveness. The protected material, fire geometry, ventilation and available delivery arrangement determine whether the relevant mechanism can operate where it is needed.&amp;lt;ref name=&amp;quot;F-4ad60f14bc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.3, pp. 17-32–17-33, 17-36–17-38.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-36233581a2&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.4, pp. 17-45–17-49.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The assessment also distinguishes successful operation from unsuccessful or delayed operation. An explicit example appears in Australia&amp;#039;s Fire Safety Verification Method Standard, 2022 edition. Its structural-stability scenario considers failures of suppression, delayed fire brigade intervention and combinations of failures. That requirement belongs to the Australian method and its stated scenario. It illustrates why the mere presence of equipment is insufficient evidence of the building&amp;#039;s performance.&amp;lt;ref name=&amp;quot;B-2b63577d33&amp;quot;&amp;gt;Australian Building Codes Board (2022), §2.12.2; p. 19.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The protection claim consequently includes its conditions of use. These include the hazard, the quantity and distribution of agent, the expected activation sequence and the time for which protection is maintained. Changes to storage, ventilation or operating procedures can alter those conditions. The International Fire Engineering Guidelines connect continued building use and alterations with review of the original engineering assumptions.&amp;lt;ref name=&amp;quot;I-7b0907c015&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.6–0.3.2.8; pp. 0.3-6–0.3-7.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Fire extinguisher maintenance]]&lt;br /&gt;
* [[NOAEL and LOAEL]]&lt;br /&gt;
* [[Inert gas agent]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Australian Building Codes Board. (2022). &amp;#039;&amp;#039;Fire Safety Verification Method Standard 2022&amp;#039;&amp;#039;.&lt;br /&gt;
* Cote, A. E., Grant, C. C., Hall, J. R., Jr., &amp;amp; Solomon, R. E. (Eds.). (2008). &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039; (20th ed.). National Fire Protection Association.&lt;br /&gt;
* DiNenno, P. J. (2002). Halon replacement clean agent total flooding systems. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall, Jr., &amp;amp; J. M. Watts, Jr. (Eds.), &amp;#039;&amp;#039;SFPE Handbook of Fire Protection Engineering&amp;#039;&amp;#039; (3rd ed., chapter 4-7, pp. 4-173–4-200). National Fire Protection Association.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International Fire Engineering Guidelines&amp;#039;&amp;#039; (2005 ed.). Australian Building Codes Board.&lt;br /&gt;
&lt;br /&gt;
[[Category:Fire Suppression]]&lt;/div&gt;</summary>
		<author><name>Thomas</name></author>
	</entry>
</feed>