<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Flash_point</id>
	<title>Flash point - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Flash_point"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flash_point&amp;action=history"/>
	<updated>2026-11-04T13:13:25Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=2858&amp;oldid=prev</id>
		<title>Jan: Remove links to pages that do not exist; retain displayed text (wiki-wide link audit).</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=2858&amp;oldid=prev"/>
		<updated>2026-11-02T21:32:50Z</updated>

		<summary type="html">&lt;p&gt;Remove links to pages that do not exist; retain displayed text (wiki-wide link audit).&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 22:32, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l53&quot;&gt;Line 53:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 53:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Use in prevention and classification ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Use in prevention and classification ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[&lt;/del&gt;Hazardous area classification&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;]]&lt;/del&gt;, flash point supplies information about the liquid rather than the extent of a flammable atmosphere. The underlying ignition issue is whether released vapour mixes with air within its flammable range. This requires information about the release and mixing conditions as well as the liquid property.&amp;lt;ref name=&quot;IFEG-3.3-2&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For Hazardous area classification, flash point supplies information about the liquid rather than the extent of a flammable atmosphere. The underlying ignition issue is whether released vapour mixes with air within its flammable range. This requires information about the release and mixing conditions as well as the liquid property.&amp;lt;ref name=&quot;IFEG-3.3-2&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For storage and handling, a lower flash point signals that an ignitable vapour mixture can develop at a lower liquid temperature under comparable conditions. Control can therefore address liquid temperature, vapour accumulation and ignition sources together. The fire-triangle elements remain separate even though flash point combines their effects in one test observation.&amp;lt;ref name=&amp;quot;VR-4.2&amp;quot;&amp;gt;Van Rossum (2027), §4.2.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;For storage and handling, a lower flash point signals that an ignitable vapour mixture can develop at a lower liquid temperature under comparable conditions. Control can therefore address liquid temperature, vapour accumulation and ignition sources together. The fire-triangle elements remain separate even though flash point combines their effects in one test observation.&amp;lt;ref name=&amp;quot;VR-4.2&amp;quot;&amp;gt;Van Rossum (2027), §4.2.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;/table&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=2645&amp;oldid=prev</id>
		<title>Peter: Improve FSE wiki article: Flash point; source, clarity and calculation review (GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=2645&amp;oldid=prev"/>
		<updated>2026-11-02T17:29:08Z</updated>

		<summary type="html">&lt;p&gt;Improve FSE wiki article: Flash point; source, clarity and calculation review (GPT-6)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Flash_point&amp;amp;diff=2645&amp;amp;oldid=792&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=792&amp;oldid=prev</id>
		<title>Sanne: Add diagrams fse-flash-point-v1.svg, fse-flash-point-v2.svg, fse-flash-point-v3.svg (level-1 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=792&amp;oldid=prev"/>
		<updated>2026-11-02T06:25:26Z</updated>

		<summary type="html">&lt;p&gt;Add diagrams fse-flash-point-v1.svg, fse-flash-point-v2.svg, fse-flash-point-v3.svg (level-1 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 07:25, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l20&quot;&gt;Line 20:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 20:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the definition used by Kanury, the liquid is presumed to have a uniform temperature. A small gas-flame pilot makes a quick sweep near the vapourising surface. The observed result is a momentary flame propagation through the vapour-air layer. Sustained burning is not required for the flash-point observation.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the definition used by Kanury, the liquid is presumed to have a uniform temperature. A small gas-flame pilot makes a quick sweep near the vapourising surface. The observed result is a momentary flame propagation through the vapour-air layer. Sustained burning is not required for the flash-point observation.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flash-point-v1.svg|thumb|upright=1.5|alt=Open and closed cups with vapour above liquid and a pilot sweeping near the surface.|Flash-point tests use a pilot and a defined cup configuration. Based on Kanury (2002), pp. 2-190–2-191.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Closed-cup apparatus retains vapour more effectively and limits disturbance by room air currents. Open-cup apparatus exposes the sample more directly to its surroundings. Kanury reports that closed-cup methods, such as Pensky-Martens, generally produce flashing at a lower temperature than open-cup methods, such as Cleveland, in the cited comparisons.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Closed-cup apparatus retains vapour more effectively and limits disturbance by room air currents. Open-cup apparatus exposes the sample more directly to its surroundings. Kanury reports that closed-cup methods, such as Pensky-Martens, generally produce flashing at a lower temperature than open-cup methods, such as Cleveland, in the cited comparisons.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l30&quot;&gt;Line 30:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 31:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;At flash point, the applied pilot can produce a flame that flashes through the available mixture and then goes out. The vapour production rate is not yet sufficient for self-sustained burning under the test conditions. This is why the term should not be used as a synonym for the start of every liquid fire.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;At flash point, the applied pilot can produce a flame that flashes through the available mixture and then goes out. The vapour production rate is not yet sufficient for self-sustained burning under the test conditions. This is why the term should not be used as a synonym for the start of every liquid fire.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flash-point-v2.svg|thumb|upright=1.5|alt=Three panels: flash then out, sustained flame and self-ignition without pilot.|Flash point, fire point and autoignition describe different observations. Based on Kanury (2002), p. 2-190.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fire point is defined similarly except that the flame must continue and sustain burning of the liquid. Continued heat feedback and vapour production are now sufficient. In the datasets examined by Kanury, fire point consistently exceeded flash point by about 20 to 40 °C for the listed hydrocarbon liquids. That observed relationship belongs to those data and should not be treated as a universal conversion.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fire point is defined similarly except that the flame must continue and sustain burning of the liquid. Continued heat feedback and vapour production are now sufficient. In the datasets examined by Kanury, fire point consistently exceeded flash point by about 20 to 40 °C for the listed hydrocarbon liquids. That observed relationship belongs to those data and should not be treated as a universal conversion.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l64&quot;&gt;Line 64:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 66:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The table gives benzene a flash point of −11 °C, toluene 4 °C, styrene 31 °C and decane 46 °C. Under comparable test conditions, these values indicate different temperatures at which the respective vapour mixtures can support the specified flash. They do not rank the later heat release rates or total hazards of fires involving these liquids.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The table gives benzene a flash point of −11 °C, toluene 4 °C, styrene 31 °C and decane 46 °C. Under comparable test conditions, these values indicate different temperatures at which the respective vapour mixtures can support the specified flash. They do not rank the later heat release rates or total hazards of fires involving these liquids.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flash-point-v3.svg|thumb|upright=1.5|alt=Flash points: benzene minus 11, toluene 4, styrene 31 and decane 46 °C.|Selected flash points tabulated in the 2005 IFEG. Based on Australian Building Codes Board et al. (2005), pp. 3.3-2–3.3-3.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The same source lists lower and upper flammability limits alongside these temperatures. Benzene has listed limits of 1.3% and 7.9% by volume, while ethanol has 3.3% and 19%. Such data describe gas-mixture composition, whereas flash point describes liquid temperature in a particular apparatus. Keeping the quantities separate prevents a temperature from being mistaken for a vapour concentration.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The same source lists lower and upper flammability limits alongside these temperatures. Benzene has listed limits of 1.3% and 7.9% by volume, while ethanol has 3.3% and 19%. Such data describe gas-mixture composition, whereas flash point describes liquid temperature in a particular apparatus. Keeping the quantities separate prevents a temperature from being mistaken for a vapour concentration.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-35:rev-792:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Sanne</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=35&amp;oldid=prev</id>
		<title>Jan: Fix Cite error: Flash point (written by Kimi Code CLI)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=35&amp;oldid=prev"/>
		<updated>2026-11-01T22:00:41Z</updated>

		<summary type="html">&lt;p&gt;Fix Cite error: Flash point (written by Kimi Code CLI)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 23:00, 1 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l33&quot;&gt;Line 33:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 33:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fire point is defined similarly except that the flame must continue and sustain burning of the liquid. Continued heat feedback and vapour production are now sufficient. In the datasets examined by Kanury, fire point consistently exceeded flash point by about 20 to 40 °C for the listed hydrocarbon liquids. That observed relationship belongs to those data and should not be treated as a universal conversion.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Fire point is defined similarly except that the flame must continue and sustain burning of the liquid. Continued heat feedback and vapour production are now sufficient. In the datasets examined by Kanury, fire point consistently exceeded flash point by about 20 to 40 °C for the listed hydrocarbon liquids. That observed relationship belongs to those data and should not be treated as a universal conversion.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Autoignition temperature]] is the minimum temperature at which a vapour or gas mixture with air ignites without a local pilot. The test can involve a heated flask, furnace, bomb, compression device or hot surface. Autoignition also involves ignition delay, so the observed response depends on exposure and method.&amp;lt;ref name=&quot;Kanury-2-189&quot;&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;&amp;gt;Kanury (2002), p. 2-189.&amp;lt;&lt;/del&gt;/&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;ref&lt;/del&gt;&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Autoignition temperature]] is the minimum temperature at which a vapour or gas mixture with air ignites without a local pilot. The test can involve a heated flask, furnace, bomb, compression device or hot surface. Autoignition also involves ignition delay, so the observed response depends on exposure and method.&amp;lt;ref name=&quot;Kanury-2-189&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A liquid can have a low flash point and a much higher autoignition temperature because the two tests ask different questions. Flash point concerns the availability of an ignitable mixture for a pilot. Autoignition concerns whether the mixture can begin reacting without that pilot. Neither value alone describes all possible [[Ignition]] routes.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A liquid can have a low flash point and a much higher autoignition temperature because the two tests ask different questions. Flash point concerns the availability of an ignitable mixture for a pilot. Autoignition concerns whether the mixture can begin reacting without that pilot. Neither value alone describes all possible [[Ignition]] routes.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-25:rev-35:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=25&amp;oldid=prev</id>
		<title>Jan: New FSE wiki article: Flash point (written by Kimi Code CLI)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flash_point&amp;diff=25&amp;oldid=prev"/>
		<updated>2026-11-01T21:58:55Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Flash point (written by Kimi Code CLI)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Flash point&amp;#039;&amp;#039;&amp;#039; is the temperature of a liquid fuel at which the vapour-air mixture just above its surface can support a momentary propagating flash when a small pilot flame is applied under specified test conditions. It describes a response of the vapour mixture, not the temperature at which the entire liquid must burn continuously.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot;&amp;gt;Kanury (2002), p. 2-190.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The property is used as an indicator of how readily a liquid can produce an ignitable vapour mixture. A lower flash point generally corresponds to greater volatility under comparable conditions, but the measured value depends on the apparatus and procedure. Open-cup and closed-cup results are not automatically interchangeable. The reported method forms part of the result and must remain attached to the numerical value.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Flash point must be distinguished from fire point and autoignition temperature. At fire point, burning continues rather than flashing and ceasing. Autoignition occurs without a local pilot when the mixture is sufficiently hot. These distinctions make flash point useful for fire prevention while limiting its ability to describe a developed fire.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Vapour production and flammability ==&lt;br /&gt;
&lt;br /&gt;
A liquid does not usually undergo flaming combustion throughout its bulk. Heat causes evaporation at the surface, and the vapour mixes with air above the liquid. Flaming occurs in this gas mixture when composition, temperature and ignition conditions are suitable. Sustained burning then depends on continued vapour production and heat feedback to the liquid.&amp;lt;ref name=&amp;quot;VR-4.1&amp;quot;&amp;gt;Van Rossum (2027), §4.1.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-189&amp;quot;&amp;gt;Kanury (2002), pp. 2-189–2-190.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[Flammability limits]] define the fuel concentrations between which a premixed flame can propagate under stated conditions. The lower limit is the lean side, with relatively little fuel vapour, and the upper limit is the rich side. Flash point is related to the temperature needed to establish an ignitable mixture near the liquid surface, but it is a test property rather than a direct concentration measurement.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Beyler-2-172&amp;quot;&amp;gt;Beyler (2002), p. 2-172.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Beyler illustrates flammability with methane in air, which propagates flame between 5% and 15% methane by volume at normal temperature and pressure. A local pilot can cause combustion outside such limits without producing a flame that travels through the wider mixture. This distinction between local ignition and propagation is central to the flash-point test.&amp;lt;ref name=&amp;quot;Beyler-2-172&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Vapour pressure links liquid temperature with the amount of vapour available, but the mixture above a real liquid is also affected by air movement and container geometry. Kanury notes that the vapour concentration above a vaporising surface depends on physical transport as well as fuel properties. Flash point therefore cannot be inferred from boiling point alone.&amp;lt;ref name=&amp;quot;Kanury-2-189&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The surrounding pressure and oxygen concentration also matter. Flammability limits are specified at particular temperature and pressure, and changes in inert gas concentration alter the mixture. A tabulated flash point consequently describes standardised test conditions rather than every storage or process environment.&amp;lt;ref name=&amp;quot;Beyler-2-172&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== How the test works ==&lt;br /&gt;
&lt;br /&gt;
In the definition used by Kanury, the liquid is presumed to have a uniform temperature. A small gas-flame pilot makes a quick sweep near the vapourising surface. The observed result is a momentary flame propagation through the vapour-air layer. Sustained burning is not required for the flash-point observation.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Closed-cup apparatus retains vapour more effectively and limits disturbance by room air currents. Open-cup apparatus exposes the sample more directly to its surroundings. Kanury reports that closed-cup methods, such as Pensky-Martens, generally produce flashing at a lower temperature than open-cup methods, such as Cleveland, in the cited comparisons.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The difference between methods is not always small or systematic. Table 2-8.1 in the SFPE Handbook lists naphtha with values from 34.4 °C to 50.0 °C across several tests, and kerosene from 52.8 °C to 60.0 °C. These examples demonstrate why a result needs its method, rather than serving as a universally interchangeable material constant.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot;&amp;gt;Kanury (2002), p. 2-191.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Cup walls, airflow, heat transfer and vapour leakage all influence the observed flash. Closed cups reduce alterations caused by drafts, while still allowing limited air leakage into the test region. Conductive cup walls and the location of the pilot also affect the mixture and its heating. The measurement is therefore an operational property tied to a defined procedure.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Flash point, fire point and autoignition ==&lt;br /&gt;
&lt;br /&gt;
At flash point, the applied pilot can produce a flame that flashes through the available mixture and then goes out. The vapour production rate is not yet sufficient for self-sustained burning under the test conditions. This is why the term should not be used as a synonym for the start of every liquid fire.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fire point is defined similarly except that the flame must continue and sustain burning of the liquid. Continued heat feedback and vapour production are now sufficient. In the datasets examined by Kanury, fire point consistently exceeded flash point by about 20 to 40 °C for the listed hydrocarbon liquids. That observed relationship belongs to those data and should not be treated as a universal conversion.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[Autoignition temperature]] is the minimum temperature at which a vapour or gas mixture with air ignites without a local pilot. The test can involve a heated flask, furnace, bomb, compression device or hot surface. Autoignition also involves ignition delay, so the observed response depends on exposure and method.&amp;lt;ref name=&amp;quot;Kanury-2-189&amp;quot;&amp;gt;Kanury (2002), p. 2-189.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A liquid can have a low flash point and a much higher autoignition temperature because the two tests ask different questions. Flash point concerns the availability of an ignitable mixture for a pilot. Autoignition concerns whether the mixture can begin reacting without that pilot. Neither value alone describes all possible [[Ignition]] routes.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The 2005 International Fire Engineering Guidelines list acetone with a flash point of −18 °C and an autoignition temperature of 465 °C, and ethanol with corresponding values of 13 °C and 365 °C. Methanol is listed at 11 °C and 470 °C. These older tabulated values illustrate the distinction, but their source and test basis must accompany any application.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot;&amp;gt;Australian Building Codes Board et al. (2005), pp. 3.3-2–3.3-3.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Flash point in liquid-fire development ==&lt;br /&gt;
&lt;br /&gt;
A [[Pool fire]] requires continuing evaporation from the liquid surface and combustion of the resulting vapour. Heat from the flame returns to the liquid, supporting further vapour production. Flash point can indicate whether a piloted flash is possible at a lower liquid temperature, but it does not determine the later heat release rate or size of this developed fire.&amp;lt;ref name=&amp;quot;VR-4.1&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Before a sustained pool fire develops, vapour may accumulate or disperse according to ventilation and container geometry. A spill in still air and a spill exposed to strong airflow can produce different local concentrations at the same liquid temperature. The relevant question is therefore whether an ignitable mixture occurs where an ignition source is present.&amp;lt;ref name=&amp;quot;Kanury-2-189&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-3.3-1&amp;quot;&amp;gt;Australian Building Codes Board et al. (2005), p. 3.3-1.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The 2005 guidelines explain that liquid fuels present a safety issue similar to gases when enough vapour enters the flammable range. Very low-energy ignition sources can then be sufficient. Their preventive strategy for gases and vapours is to keep concentrations below the lower flammable limit, rather than relying on a rich mixture remaining above the upper limit after dilution.&amp;lt;ref name=&amp;quot;IFEG-3.3-1&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Flash point can support this assessment by showing how liquid temperature affects vapour availability under the test method. It does not measure vapour concentration at a particular distance from a spill, nor the ignition energy of that mixture. Those quantities require separate information about the scenario.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Beyler-2-172&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Use in prevention and classification ==&lt;br /&gt;
&lt;br /&gt;
[[Hazardous area classification]] considers where flammable gases or vapours may occur and how ignition risks are controlled. Flash-point information can contribute to the description of the liquid, but the classification also needs release conditions, ventilation and the possible extent of the flammable atmosphere. The test result alone does not draw the boundary of a hazardous area.&amp;lt;ref name=&amp;quot;IFEG-3.3-1&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For storage and handling, a lower flash point signals that an ignitable vapour mixture can develop at a lower liquid temperature under comparable conditions. Control can therefore address liquid temperature, vapour accumulation and ignition sources together. The fire-triangle elements remain separate even though flash point combines their effects in one test observation.&amp;lt;ref name=&amp;quot;VR-4.2&amp;quot;&amp;gt;Van Rossum (2027), §4.2.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The property is also useful when comparing liquids through consistent data. Comparisons should use the same method and edition of the source, with units and any pressure conditions retained. Mixing an open-cup value for one liquid with a closed-cup value for another can distort the comparison.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Flash point is not a measure of toxic hazard, soot production or total chemical energy. It does not state how much fuel is present or how fast it will burn after sustained ignition. Those aspects need combustion, toxicity and fire-scenario data rather than a single ignition-related temperature.&amp;lt;ref name=&amp;quot;Drysdale-1-95&amp;quot;&amp;gt;Drysdale (2002), p. 1-95.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;VR-4.5&amp;quot;&amp;gt;Van Rossum (2027), §4.5.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Comparing liquids and source data ==&lt;br /&gt;
&lt;br /&gt;
A meaningful comparison starts with values obtained on the same basis. The 2005 International Fire Engineering Guidelines place flash point beside flammability limits, autoignition temperature and boiling point for common gases and vapours. This arrangement helps distinguish the properties, but does not imply that one can be calculated reliably from another without a suitable model and conditions.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The table gives benzene a flash point of −11 °C, toluene 4 °C, styrene 31 °C and decane 46 °C. Under comparable test conditions, these values indicate different temperatures at which the respective vapour mixtures can support the specified flash. They do not rank the later heat release rates or total hazards of fires involving these liquids.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The same source lists lower and upper flammability limits alongside these temperatures. Benzene has listed limits of 1.3% and 7.9% by volume, while ethanol has 3.3% and 19%. Such data describe gas-mixture composition, whereas flash point describes liquid temperature in a particular apparatus. Keeping the quantities separate prevents a temperature from being mistaken for a vapour concentration.&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Kanury&amp;#039;s multi-method table provides a second kind of comparison. Gas oil is listed with flash points of 90.6 °C, 93.3 °C and 92.2 °C in three apparatus types, while the listed heavy-oil values extend from 265.5 °C to 293.3 °C. The pattern across methods is not sufficiently consistent to support one universal correction between all tests.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Heavier fuels tending to have higher flash points in these data is an observed trend, not a substitute for measurement. Kanury also notes that several trends across fuel families are weak or conceptually uncertain. A liquid&amp;#039;s name or broad family therefore does not justify inventing a value when a tested result is unavailable.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Source age and scope also matter. The SFPE Handbook chapter dates from 2002 and the guidelines from 2005. Their values remain evidence of the reported tests, but an engineering application still needs the appropriate method, current product information where applicable and the actual storage or release conditions. This article does not turn those tabulated results into jurisdiction-specific classification rules.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-3.3-3&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Limits and common misunderstandings ==&lt;br /&gt;
&lt;br /&gt;
Flash point is not the boiling point. Boiling concerns a phase-change condition of the liquid, while flash point concerns piloted flame propagation in the vapour-air mixture. Volatility affects both properties, but they answer different questions and can differ substantially.&amp;lt;ref name=&amp;quot;Kanury-2-189&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
It is also not a minimum room temperature for every fire. The test concerns liquid temperature and the vapour layer near the surface. Ambient temperature can influence evaporation and heat loss, but a warm liquid in a cooler room can still produce an ignitable mixture. Local conditions remain decisive.&amp;lt;ref name=&amp;quot;Kanury-2-190&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-3.3-1&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A liquid below its reported flash point is not guaranteed to present no ignition hazard in every configuration. The result depends on apparatus and procedure, and real releases can involve sprays, heated surfaces or other conditions not represented by the cup test. The property should therefore be applied only within the scenario it is able to inform.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;IFEG-3.3-1&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Finally, flash point does not indicate whether an established fire can be extinguished easily. Sustained combustion depends on heat feedback, fuel supply and oxygen, while extinction adds heat-loss and reaction-chemistry considerations. The initial flashing threshold and the later fire state must remain separate.&amp;lt;ref name=&amp;quot;VR-4.3&amp;quot;&amp;gt;Van Rossum (2027), §4.3.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Drysdale-1-97&amp;quot;&amp;gt;Drysdale (2002), p. 1-97.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A careful report identifies the liquid, the numerical result, the unit and the test method together. Reporting only a temperature loses information needed to reproduce or compare the measurement. Where several methods are present in a source table, each value must remain attached to its own column and apparatus.&amp;lt;ref name=&amp;quot;Kanury-2-191&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The result should then be connected with the scenario being assessed. Liquid inventory, release area, ventilation and possible ignition locations determine how the property affects risk. Flash point supplies one piece of evidence within that wider description, rather than replacing the scenario itself.&amp;lt;ref name=&amp;quot;IFEG-3.3-1&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Kanury-2-189&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
&lt;br /&gt;
* [[Autoignition temperature]]&lt;br /&gt;
* [[Flammability limits]]&lt;br /&gt;
* [[Ignition]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
&lt;br /&gt;
* Australian Building Codes Board, National Research Council of Canada, International Code Council, &amp;amp; Department of Building and Housing New Zealand. (2005). &amp;#039;&amp;#039;International fire engineering guidelines&amp;#039;&amp;#039; (2005 ed.). Australian Building Codes Board.&lt;br /&gt;
* Beyler, C. L. (2002). Flammability limits of premixed and diffusion flames. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Drysdale, D. D. (2002). Thermochemistry. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Kanury, A. M. (2002). Ignition of liquid fuels. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Van Rossum, E. (2027). &amp;#039;&amp;#039;Introduction to Fire Safety Engineering&amp;#039;&amp;#039;. Fire Safety Academy.&lt;br /&gt;
&lt;br /&gt;
[[Category:Combustion]]&lt;/div&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
</feed>