<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Flame_spread_index</id>
	<title>Flame spread index - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Flame_spread_index"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;action=history"/>
	<updated>2026-11-21T22:00:48Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=9387&amp;oldid=prev</id>
		<title>Peter: Wiki review: corrected 3 errors: american-spelling (3) (Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=9387&amp;oldid=prev"/>
		<updated>2026-11-15T23:45:51Z</updated>

		<summary type="html">&lt;p&gt;Wiki review: corrected 3 errors: american-spelling (3) (Claude Opus 5.5)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 00:45, 16 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l57&quot;&gt;Line 57:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 57:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Treatment lowers the index markedly. Pressure impregnation with fire-retardant chemicals brings the lumber, plywood and particleboard in Shaw&amp;#039;s table down to 25 or less. Untreated, the same products range from 60 to 200.&amp;lt;ref name=&amp;quot;S6-134&amp;quot; /&amp;gt; Plywood with untreated face veneers on treated cores scores generally 20 to 75, depending on the density of the face veneer, and fully treated plywood generally less than 25.&amp;lt;ref name=&amp;quot;S6-135&amp;quot;&amp;gt;Shaw (2008), p. 6-135.&amp;lt;/ref&amp;gt; Wood-fibre acoustical tiles with fire retardants added during manufacture achieve less than 25.&amp;lt;ref name=&amp;quot;S6-132&amp;quot;&amp;gt;Shaw (2008), p. 6-132.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Treatment lowers the index markedly. Pressure impregnation with fire-retardant chemicals brings the lumber, plywood and particleboard in Shaw&amp;#039;s table down to 25 or less. Untreated, the same products range from 60 to 200.&amp;lt;ref name=&amp;quot;S6-134&amp;quot; /&amp;gt; Plywood with untreated face veneers on treated cores scores generally 20 to 75, depending on the density of the face veneer, and fully treated plywood generally less than 25.&amp;lt;ref name=&amp;quot;S6-135&amp;quot;&amp;gt;Shaw (2008), p. 6-135.&amp;lt;/ref&amp;gt; Wood-fibre acoustical tiles with fire retardants added during manufacture achieve less than 25.&amp;lt;ref name=&amp;quot;S6-132&amp;quot;&amp;gt;Shaw (2008), p. 6-132.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other building products give useful anchors. Madrzykowski and Fleming describe a fire test room for residential sprinklers. Its 6.4 mm Douglas fir plywood wall &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;paneling &lt;/del&gt;has a flame spread rating of 130 ± 30, and its ceiling tiles 25 or less.&amp;lt;ref name=&quot;MF16-97&quot;&amp;gt;Madrzykowski and Fleming (2008), p. 16-97.&amp;lt;/ref&amp;gt; The original ceiling tiles of the World Trade Center towers had a flame spread index under 25 according to their manufacturer (Fritz and Hough 2002, as cited in Gann, Hamins, et al., 2005).&amp;lt;ref name=&quot;NIST1-5-45&quot;&amp;gt;Gann, Hamins, et al. (2005), p. 45.&amp;lt;/ref&amp;gt; Plastic laminates for countertops and cabinets are commonly available with values of 25 to 75.&amp;lt;ref name=&quot;BC6-229&quot;&amp;gt;Benedetti and Colonna (2008), p. 6-229.&amp;lt;/ref&amp;gt; Cellular plastics cover a very wide range: in fires reviewed by Underwriters Laboratories, tunnel ratings of some materials ranged from 5 to 1375.&amp;lt;ref name=&quot;BC6-225&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Other building products give useful anchors. Madrzykowski and Fleming describe a fire test room for residential sprinklers. Its 6.4 mm Douglas fir plywood wall &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;panelling &lt;/ins&gt;has a flame spread rating of 130 ± 30, and its ceiling tiles 25 or less.&amp;lt;ref name=&quot;MF16-97&quot;&amp;gt;Madrzykowski and Fleming (2008), p. 16-97.&amp;lt;/ref&amp;gt; The original ceiling tiles of the World Trade Center towers had a flame spread index under 25 according to their manufacturer (Fritz and Hough 2002, as cited in Gann, Hamins, et al., 2005).&amp;lt;ref name=&quot;NIST1-5-45&quot;&amp;gt;Gann, Hamins, et al. (2005), p. 45.&amp;lt;/ref&amp;gt; Plastic laminates for countertops and cabinets are commonly available with values of 25 to 75.&amp;lt;ref name=&quot;BC6-229&quot;&amp;gt;Benedetti and Colonna (2008), p. 6-229.&amp;lt;/ref&amp;gt; Cellular plastics cover a very wide range: in fires reviewed by Underwriters Laboratories, tunnel ratings of some materials ranged from 5 to 1375.&amp;lt;ref name=&quot;BC6-225&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Classes and regulatory use ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Classes and regulatory use ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l78&quot;&gt;Line 78:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 78:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A new hotel is to receive wood wall &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;paneling&lt;/del&gt;. Under the &#039;&#039;Life Safety Code&#039;&#039; (2006), as tabulated by Hirschler (2008b), exits in new hotels require Class A, exit access corridors Class A or B, and other spaces Class A, B or C.&amp;lt;ref name=&quot;H18-28&quot; /&amp;gt; Three products are compared, using the upper end of each published range.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A new hotel is to receive wood wall &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;panelling&lt;/ins&gt;. Under the &#039;&#039;Life Safety Code&#039;&#039; (2006), as tabulated by Hirschler (2008b), exits in new hotels require Class A, exit access corridors Class A or B, and other spaces Class A, B or C.&amp;lt;ref name=&quot;H18-28&quot; /&amp;gt; Three products are compared, using the upper end of each published range.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Untreated southern yellow pine lumber, 130 to 195, is Class C.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; It is acceptable in other spaces. In a corridor it is acceptable only if the building is fully sprinklered, because Class C may then replace Class B. In an exit it is never acceptable, because sprinklers relax Class A only to Class B.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Untreated southern yellow pine lumber, 130 to 195, is Class C.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; It is acceptable in other spaces. In a corridor it is acceptable only if the building is fully sprinklered, because Class C may then replace Class B. In an exit it is never acceptable, because sprinklers relax Class A only to Class B.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l84&quot;&gt;Line 84:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 84:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Pressure-impregnated Douglas fir lumber, 25 or less, is Class A and acceptable in all three locations.&amp;lt;ref name=&amp;quot;S6-134&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Pressure-impregnated Douglas fir lumber, 25 or less, is Class A and acceptable in all three locations.&amp;lt;ref name=&amp;quot;S6-134&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The example shows how a single number, with a scatter of 10 to 20 points, decides where a product may be used. A test of the actual product, mounted as it will be installed, replaces the published ranges in practice.&amp;lt;ref name=&quot;H18-26&quot; /&amp;gt;&amp;lt;ref name=&quot;H18-27&quot; /&amp;gt; Alternatively, a pass in the NFPA 286 room-corner test makes the &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;paneling &lt;/del&gt;acceptable in every location.&amp;lt;ref name=&quot;H18-28&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The example shows how a single number, with a scatter of 10 to 20 points, decides where a product may be used. A test of the actual product, mounted as it will be installed, replaces the published ranges in practice.&amp;lt;ref name=&quot;H18-26&quot; /&amp;gt;&amp;lt;ref name=&quot;H18-27&quot; /&amp;gt; Alternatively, a pass in the NFPA 286 room-corner test makes the &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;panelling &lt;/ins&gt;acceptable in every location.&amp;lt;ref name=&quot;H18-28&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Other requirements based on the index ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Other requirements based on the index ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-4831:rev-9387:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=4831&amp;oldid=prev</id>
		<title>Linda: Remove bibliographic source lines from image captions and descriptions</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=4831&amp;oldid=prev"/>
		<updated>2026-11-08T07:25:13Z</updated>

		<summary type="html">&lt;p&gt;Remove bibliographic source lines from image captions and descriptions&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:25, 8 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l14&quot;&gt;Line 14:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 14:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== How the index is determined ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== How the index is determined ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The specimen forms the ceiling of a 7.62 m (25 ft) tunnel and is exposed to a gas flame at one end, while air flows along the tunnel at 1.22 m/s (240 ft/min).&amp;lt;ref name=&amp;quot;H18-25&amp;quot;&amp;gt;Hirschler (2008b), p. 18-25.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Observers record the position of the flame front through side windows as a function of time over the 10-minute test.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The flame spread index is then calculated from the graph of flame spread against time, by comparison with the two reference materials.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The handbook describes the result as based on the area under this curve, but does not reproduce the formula of the standard.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The specimen forms the ceiling of a 7.62 m (25 ft) tunnel and is exposed to a gas flame at one end, while air flows along the tunnel at 1.22 m/s (240 ft/min).&amp;lt;ref name=&amp;quot;H18-25&amp;quot;&amp;gt;Hirschler (2008b), p. 18-25.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Observers record the position of the flame front through side windows as a function of time over the 10-minute test.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The flame spread index is then calculated from the graph of flame spread against time, by comparison with the two reference materials.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The handbook describes the result as based on the area under this curve, but does not reproduce the formula of the standard.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v1.svg|thumb|upright=1.5|alt=Schematic chart of flame front distance against time: red oak reaches 7.3 m at 5.5 minutes, a test material spreads less, cement board stays at zero.|Principle of the flame spread index: the flame front distance is recorded over the 10-minute test and the area under the curve is compared with that of red oak flooring (about 100) and cement board (0). Schematic, not measured data&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Hirschler (2008a), p. 6-43 and Hirschler (2008b), p. 18-26&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v1.svg|thumb|upright=1.5|alt=Schematic chart of flame front distance against time: red oak reaches 7.3 m at 5.5 minutes, a test material spreads less, cement board stays at zero.|Principle of the flame spread index: the flame front distance is recorded over the 10-minute test and the area under the curve is compared with that of red oak flooring (about 100) and cement board (0). Schematic, not measured data.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The reference values are arbitrary. Red oak flooring is assigned 100 and a cementitious board 0.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; According to the test standard, red oak spreads flame 7.3 m (24 ft) to the end of the specimen in 5½ minutes ± 15 seconds.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Cholin notes that red oak was originally used as the reference standard to establish the rating of 100. The test is now referenced to specific performance parameters on a noncombustible surface, but red oak still achieves about 100.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; This is consistent with the handbook giving red oak a flame spread index of approximately 100, whereas its smoke-developed index is exactly 100 by definition.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The reference values are arbitrary. Red oak flooring is assigned 100 and a cementitious board 0.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; According to the test standard, red oak spreads flame 7.3 m (24 ft) to the end of the specimen in 5½ minutes ± 15 seconds.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Cholin notes that red oak was originally used as the reference standard to establish the rating of 100. The test is now referenced to specific performance parameters on a noncombustible surface, but red oak still achieves about 100.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; This is consistent with the handbook giving red oak a flame spread index of approximately 100, whereas its smoke-developed index is exactly 100 by definition.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l24&quot;&gt;Line 24:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 24:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Typical values ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Typical values ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Wood is the natural point of comparison, because the scale is anchored to red oak. Cholin states that most wood species fall between 90 and 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; His table of 1 in. (25.4 mm) nominal lumber, compiled from tests by Underwriters Laboratories and others, actually spans 60 to 230. Only 11 of its 23 species lie entirely within 90 to 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Wood is the natural point of comparison, because the scale is anchored to red oak. Cholin states that most wood species fall between 90 and 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; His table of 1 in. (25.4 mm) nominal lumber, compiled from tests by Underwriters Laboratories and others, actually spans 60 to 230. Only 11 of its 23 species lie entirely within 90 to 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v2.svg|thumb|upright=1.5|alt=Range bars of flame spread index for twelve wood species between 60 and 230, over shaded bands for Class A, B and C.|Flame spread index ranges of untreated 25.4 mm nominal lumber of selected wood species, with the United States Class A, B and C bands&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cholin (2008c), p. 6-70 and Hirschler (2008b), p. 18-27&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v2.svg|thumb|upright=1.5|alt=Range bars of flame spread index for twelve wood species between 60 and 230, over shaded bands for Class A, B and C.|Flame spread index ranges of untreated 25.4 mm nominal lumber of selected wood species, with the United States Class A, B and C bands.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;{| class=&amp;quot;wikitable&amp;quot;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;{| class=&amp;quot;wikitable&amp;quot;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l75&quot;&gt;Line 75:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 75:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers relax the limits. A note to the 2006 table refers to the annex of NFPA 101 for buildings with a complete standard sprinkler system. There, Class C is permitted where Class B is required, and Class B where Class A is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; This does not apply to new detention and correctional occupancies. The trade-off is not written in code language and differs from the one in the International Building Code.&amp;lt;ref name=&amp;quot;H18-29&amp;quot;&amp;gt;Hirschler (2008b), p. 18-29.&amp;lt;/ref&amp;gt; A material that passes the NFPA 286 room-corner test may be used wherever a Class A, B or C finish is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers relax the limits. A note to the 2006 table refers to the annex of NFPA 101 for buildings with a complete standard sprinkler system. There, Class C is permitted where Class B is required, and Class B where Class A is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; This does not apply to new detention and correctional occupancies. The trade-off is not written in code language and differs from the one in the International Building Code.&amp;lt;ref name=&amp;quot;H18-29&amp;quot;&amp;gt;Hirschler (2008b), p. 18-29.&amp;lt;/ref&amp;gt; A material that passes the NFPA 286 room-corner test may be used wherever a Class A, B or C finish is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v3.svg|thumb|upright=1.5|alt=Index scale from 0 to 200 split into Class A, B and C, with arrows showing that sprinklers allow one class lower.|Classes of interior wall and ceiling finish by flame spread index in United States codes (2006 editions), with the common smoke-developed limit of 450 and the one-class relaxation for fully sprinklered buildings&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Hirschler (2008b), pp. 18-27–18-28&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v3.svg|thumb|upright=1.5|alt=Index scale from 0 to 200 split into Class A, B and C, with arrows showing that sprinklers allow one class lower.|Classes of interior wall and ceiling finish by flame spread index in United States codes (2006 editions), with the common smoke-developed limit of 450 and the one-class relaxation for fully sprinklered buildings.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l105&quot;&gt;Line 105:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 105:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The position of a finish also matters. In full-scale corridor experiments, wall coverings with an index of 90 could be used safely with ceilings of 25 or less, if they were limited to the lower 1.2 m (4 ft) of the wall.&amp;lt;ref name=&amp;quot;H18-39&amp;quot;&amp;gt;Hirschler (2008b), p. 18-39.&amp;lt;/ref&amp;gt; Full-height coverings of 90 led to rapid flame propagation. Some Class A ceiling materials increased flame spread over the walls, because they insulated better than materials with an index of zero.&amp;lt;ref name=&amp;quot;H18-39&amp;quot; /&amp;gt; O&amp;#039;Connor reports the same principle for health care: finishes on the lower half of a wall, below 1.2 m, contribute less to flame propagation than finishes higher up.&amp;lt;ref name=&amp;quot;OC20-145&amp;quot;&amp;gt;O&amp;#039;Connor (2008), p. 20-145.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The position of a finish also matters. In full-scale corridor experiments, wall coverings with an index of 90 could be used safely with ceilings of 25 or less, if they were limited to the lower 1.2 m (4 ft) of the wall.&amp;lt;ref name=&amp;quot;H18-39&amp;quot;&amp;gt;Hirschler (2008b), p. 18-39.&amp;lt;/ref&amp;gt; Full-height coverings of 90 led to rapid flame propagation. Some Class A ceiling materials increased flame spread over the walls, because they insulated better than materials with an index of zero.&amp;lt;ref name=&amp;quot;H18-39&amp;quot; /&amp;gt; O&amp;#039;Connor reports the same principle for health care: finishes on the lower half of a wall, below 1.2 m, contribute less to flame propagation than finishes higher up.&amp;lt;ref name=&amp;quot;OC20-145&amp;quot;&amp;gt;O&amp;#039;Connor (2008), p. 20-145.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v4.svg|thumb|upright=1.5|alt=Two corridor cross-sections: left, wall covering only on the lower 1.2 m; right, covering on the full wall height under the same ceiling.|Corridor experiments with a wall covering of flame spread index 90 under a ceiling of 25 or less: limited to the lower 1.2 m of the wall it could be used safely (left); over the full height it led to rapid flame propagation (right)&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Hirschler (2008b), p. 18-39&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-flame-spread-index-v4.svg|thumb|upright=1.5|alt=Two corridor cross-sections: left, wall covering only on the lower 1.2 m; right, covering on the full wall height under the same ceiling.|Corridor experiments with a wall covering of flame spread index 90 under a ceiling of 25 or less: limited to the lower 1.2 m of the wall it could be used safely (left); over the full height it led to rapid flame propagation (right).]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Engineering analyses sometimes still use the index. In Ramachandran&amp;#039;s stochastic model of corridor fire spread, the probability of spread before flashover is, to a first approximation, governed by the flame spread classification of the finishes.&amp;lt;ref name=&amp;quot;R3-393&amp;quot;&amp;gt;Ramachandran (2002c), p. 3-393.&amp;lt;/ref&amp;gt; Such uses rest on the ranking, not on a physical quantity.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Engineering analyses sometimes still use the index. In Ramachandran&amp;#039;s stochastic model of corridor fire spread, the probability of spread before flashover is, to a first approximation, governed by the flame spread classification of the finishes.&amp;lt;ref name=&amp;quot;R3-393&amp;quot;&amp;gt;Ramachandran (2002c), p. 3-393.&amp;lt;/ref&amp;gt; Such uses rest on the ranking, not on a physical quantity.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-4682:rev-4831:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Linda</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=4682&amp;oldid=prev</id>
		<title>Lisa: Add 4 watermarked NFPA SVG illustrations</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=4682&amp;oldid=prev"/>
		<updated>2026-11-08T07:13:39Z</updated>

		<summary type="html">&lt;p&gt;Add 4 watermarked NFPA SVG illustrations&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:13, 8 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l14&quot;&gt;Line 14:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 14:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== How the index is determined ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== How the index is determined ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The specimen forms the ceiling of a 7.62 m (25 ft) tunnel and is exposed to a gas flame at one end, while air flows along the tunnel at 1.22 m/s (240 ft/min).&amp;lt;ref name=&amp;quot;H18-25&amp;quot;&amp;gt;Hirschler (2008b), p. 18-25.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Observers record the position of the flame front through side windows as a function of time over the 10-minute test.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The flame spread index is then calculated from the graph of flame spread against time, by comparison with the two reference materials.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The handbook describes the result as based on the area under this curve, but does not reproduce the formula of the standard.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The specimen forms the ceiling of a 7.62 m (25 ft) tunnel and is exposed to a gas flame at one end, while air flows along the tunnel at 1.22 m/s (240 ft/min).&amp;lt;ref name=&amp;quot;H18-25&amp;quot;&amp;gt;Hirschler (2008b), p. 18-25.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Observers record the position of the flame front through side windows as a function of time over the 10-minute test.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The flame spread index is then calculated from the graph of flame spread against time, by comparison with the two reference materials.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The handbook describes the result as based on the area under this curve, but does not reproduce the formula of the standard.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flame-spread-index-v1.svg|thumb|upright=1.5|alt=Schematic chart of flame front distance against time: red oak reaches 7.3 m at 5.5 minutes, a test material spreads less, cement board stays at zero.|Principle of the flame spread index: the flame front distance is recorded over the 10-minute test and the area under the curve is compared with that of red oak flooring (about 100) and cement board (0). Schematic, not measured data. Based on Hirschler (2008a), p. 6-43 and Hirschler (2008b), p. 18-26.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The reference values are arbitrary. Red oak flooring is assigned 100 and a cementitious board 0.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; According to the test standard, red oak spreads flame 7.3 m (24 ft) to the end of the specimen in 5½ minutes ± 15 seconds.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Cholin notes that red oak was originally used as the reference standard to establish the rating of 100. The test is now referenced to specific performance parameters on a noncombustible surface, but red oak still achieves about 100.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; This is consistent with the handbook giving red oak a flame spread index of approximately 100, whereas its smoke-developed index is exactly 100 by definition.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The reference values are arbitrary. Red oak flooring is assigned 100 and a cementitious board 0.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; According to the test standard, red oak spreads flame 7.3 m (24 ft) to the end of the specimen in 5½ minutes ± 15 seconds.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Cholin notes that red oak was originally used as the reference standard to establish the rating of 100. The test is now referenced to specific performance parameters on a noncombustible surface, but red oak still achieves about 100.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; This is consistent with the handbook giving red oak a flame spread index of approximately 100, whereas its smoke-developed index is exactly 100 by definition.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l23&quot;&gt;Line 23:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 24:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Typical values ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Typical values ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Wood is the natural point of comparison, because the scale is anchored to red oak. Cholin states that most wood species fall between 90 and 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; His table of 1 in. (25.4 mm) nominal lumber, compiled from tests by Underwriters Laboratories and others, actually spans 60 to 230. Only 11 of its 23 species lie entirely within 90 to 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Wood is the natural point of comparison, because the scale is anchored to red oak. Cholin states that most wood species fall between 90 and 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; His table of 1 in. (25.4 mm) nominal lumber, compiled from tests by Underwriters Laboratories and others, actually spans 60 to 230. Only 11 of its 23 species lie entirely within 90 to 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flame-spread-index-v2.svg|thumb|upright=1.5|alt=Range bars of flame spread index for twelve wood species between 60 and 230, over shaded bands for Class A, B and C.|Flame spread index ranges of untreated 25.4 mm nominal lumber of selected wood species, with the United States Class A, B and C bands. Based on Cholin (2008c), p. 6-70 and Hirschler (2008b), p. 18-27.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;{| class=&amp;quot;wikitable&amp;quot;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;{| class=&amp;quot;wikitable&amp;quot;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l73&quot;&gt;Line 73:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 75:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers relax the limits. A note to the 2006 table refers to the annex of NFPA 101 for buildings with a complete standard sprinkler system. There, Class C is permitted where Class B is required, and Class B where Class A is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; This does not apply to new detention and correctional occupancies. The trade-off is not written in code language and differs from the one in the International Building Code.&amp;lt;ref name=&amp;quot;H18-29&amp;quot;&amp;gt;Hirschler (2008b), p. 18-29.&amp;lt;/ref&amp;gt; A material that passes the NFPA 286 room-corner test may be used wherever a Class A, B or C finish is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Automatic sprinklers relax the limits. A note to the 2006 table refers to the annex of NFPA 101 for buildings with a complete standard sprinkler system. There, Class C is permitted where Class B is required, and Class B where Class A is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; This does not apply to new detention and correctional occupancies. The trade-off is not written in code language and differs from the one in the International Building Code.&amp;lt;ref name=&amp;quot;H18-29&amp;quot;&amp;gt;Hirschler (2008b), p. 18-29.&amp;lt;/ref&amp;gt; A material that passes the NFPA 286 room-corner test may be used wherever a Class A, B or C finish is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flame-spread-index-v3.svg|thumb|upright=1.5|alt=Index scale from 0 to 200 split into Class A, B and C, with arrows showing that sprinklers allow one class lower.|Classes of interior wall and ceiling finish by flame spread index in United States codes (2006 editions), with the common smoke-developed limit of 450 and the one-class relaxation for fully sprinklered buildings. Based on Hirschler (2008b), pp. 18-27–18-28.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;=== Worked example ===&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l102&quot;&gt;Line 102:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 105:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The position of a finish also matters. In full-scale corridor experiments, wall coverings with an index of 90 could be used safely with ceilings of 25 or less, if they were limited to the lower 1.2 m (4 ft) of the wall.&amp;lt;ref name=&amp;quot;H18-39&amp;quot;&amp;gt;Hirschler (2008b), p. 18-39.&amp;lt;/ref&amp;gt; Full-height coverings of 90 led to rapid flame propagation. Some Class A ceiling materials increased flame spread over the walls, because they insulated better than materials with an index of zero.&amp;lt;ref name=&amp;quot;H18-39&amp;quot; /&amp;gt; O&amp;#039;Connor reports the same principle for health care: finishes on the lower half of a wall, below 1.2 m, contribute less to flame propagation than finishes higher up.&amp;lt;ref name=&amp;quot;OC20-145&amp;quot;&amp;gt;O&amp;#039;Connor (2008), p. 20-145.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The position of a finish also matters. In full-scale corridor experiments, wall coverings with an index of 90 could be used safely with ceilings of 25 or less, if they were limited to the lower 1.2 m (4 ft) of the wall.&amp;lt;ref name=&amp;quot;H18-39&amp;quot;&amp;gt;Hirschler (2008b), p. 18-39.&amp;lt;/ref&amp;gt; Full-height coverings of 90 led to rapid flame propagation. Some Class A ceiling materials increased flame spread over the walls, because they insulated better than materials with an index of zero.&amp;lt;ref name=&amp;quot;H18-39&amp;quot; /&amp;gt; O&amp;#039;Connor reports the same principle for health care: finishes on the lower half of a wall, below 1.2 m, contribute less to flame propagation than finishes higher up.&amp;lt;ref name=&amp;quot;OC20-145&amp;quot;&amp;gt;O&amp;#039;Connor (2008), p. 20-145.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-flame-spread-index-v4.svg|thumb|upright=1.5|alt=Two corridor cross-sections: left, wall covering only on the lower 1.2 m; right, covering on the full wall height under the same ceiling.|Corridor experiments with a wall covering of flame spread index 90 under a ceiling of 25 or less: limited to the lower 1.2 m of the wall it could be used safely (left); over the full height it led to rapid flame propagation (right). Based on Hirschler (2008b), p. 18-39.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Engineering analyses sometimes still use the index. In Ramachandran&amp;#039;s stochastic model of corridor fire spread, the probability of spread before flashover is, to a first approximation, governed by the flame spread classification of the finishes.&amp;lt;ref name=&amp;quot;R3-393&amp;quot;&amp;gt;Ramachandran (2002c), p. 3-393.&amp;lt;/ref&amp;gt; Such uses rest on the ranking, not on a physical quantity.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Engineering analyses sometimes still use the index. In Ramachandran&amp;#039;s stochastic model of corridor fire spread, the probability of spread before flashover is, to a first approximation, governed by the flame spread classification of the finishes.&amp;lt;ref name=&amp;quot;R3-393&amp;quot;&amp;gt;Ramachandran (2002c), p. 3-393.&amp;lt;/ref&amp;gt; Such uses rest on the ranking, not on a physical quantity.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-3233:rev-4682:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Lisa</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=3233&amp;oldid=prev</id>
		<title>Peter: New FSE wiki article: Flame spread index (written by Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Flame_spread_index&amp;diff=3233&amp;oldid=prev"/>
		<updated>2026-11-07T21:15:55Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Flame spread index (written by Claude Opus 5.5)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;The &amp;#039;&amp;#039;&amp;#039;flame spread index&amp;#039;&amp;#039;&amp;#039; (&amp;#039;&amp;#039;&amp;#039;FSI&amp;#039;&amp;#039;&amp;#039;) is a relative number that expresses how readily flame spreads over the surface of a building material in the [[Steiner tunnel test]] (NFPA 255, ASTM E84).&amp;lt;ref name=&amp;quot;HA6-43&amp;quot;&amp;gt;Hirschler (2008a), p. 6-43.&amp;lt;/ref&amp;gt; It is calculated from the record of flame spread distance against time during the 10-minute test.&amp;lt;ref name=&amp;quot;H18-26&amp;quot;&amp;gt;Hirschler (2008b), p. 18-26.&amp;lt;/ref&amp;gt; The scale is set by two reference materials: a cement board scores 0 and red oak flooring about 100.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt; The lower the index, the better the presumed performance of the material.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Typical untreated wood species score between about 60 and 230, while fire-retardant-treated wood reaches 25 or less.&amp;lt;ref name=&amp;quot;C6-70&amp;quot;&amp;gt;Cholin (2008c), p. 6-70.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;S6-134&amp;quot;&amp;gt;Shaw (2008), p. 6-134.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the United States, NFPA 101 and NFPA 5000 (2006 editions) group wall and ceiling finishes into Class A (0 to 25), Class B (26 to 75) and Class C (76 to 200).&amp;lt;ref name=&amp;quot;H18-27&amp;quot;&amp;gt;Hirschler (2008b), p. 18-27.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-28&amp;quot;&amp;gt;Hirschler (2008b), p. 18-28.&amp;lt;/ref&amp;gt; The index is also used for ducts, elevator cars, treated wood and the definition of limited-combustible materials.&amp;lt;ref name=&amp;quot;W10-72&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;D10-63&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;S6-133&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;GW19-5&amp;quot; /&amp;gt; It has no engineering units, so it cannot be used directly in fire safety engineering calculations.&amp;lt;ref name=&amp;quot;HA6-42&amp;quot;&amp;gt;Hirschler (2008a), p. 6-42.&amp;lt;/ref&amp;gt; Nor does a low value guarantee good behaviour in a real fire, especially for thin, melting or foamed products.&amp;lt;ref name=&amp;quot;H18-31&amp;quot;&amp;gt;Hirschler (2008b), p. 18-31.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Definition and terminology ==&lt;br /&gt;
Hirschler defines the flame spread index as the normal output of the NFPA 255 and ASTM E84 test. It is a relative number based on the area under the curve of flame spread distance against time, with cement board at 0 and red oak flooring at approximately 100.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt; Nolan describes it as a relative performance of fire travel over the surface of a material tested to NFPA 255.&amp;lt;ref name=&amp;quot;Nolan-F31&amp;quot;&amp;gt;Nolan (2000), as cited in Iqbal and Salley (2004), p. F-31.&amp;lt;/ref&amp;gt; The index is non-dimensional and does not produce results in proper engineering units.&amp;lt;ref name=&amp;quot;HA6-42&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Several names are in use for the same number. The handbook uses flame spread index and its abbreviation FSI, but also flame spread rating and flame spread classification.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;BC6-226&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-226.&amp;lt;/ref&amp;gt; Shaw explains that flame spread rating refers to indices or classifications obtained to NFPA 255 (ASTM E84) or other flame spread tests.&amp;lt;ref name=&amp;quot;S6-129&amp;quot;&amp;gt;Shaw (2008), p. 6-129.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A glossary quoted in NUREG-1805 defines the flame spread rating as a numerical classification determined by ASTM E84. It indexes the relative burning behaviour of a material by quantifying the spread of flame over a test specimen.&amp;lt;ref name=&amp;quot;IS-F31&amp;quot;&amp;gt;Iqbal and Salley (2004), p. F-31.&amp;lt;/ref&amp;gt; The same glossary adds that this surface burning characteristic is not a measure of resistance to fire exposure.&amp;lt;ref name=&amp;quot;IS-F31&amp;quot; /&amp;gt; The index is thus distinct from fire resistance.&lt;br /&gt;
&lt;br /&gt;
The index is meant to describe [[flame spread]] across the surface of a material. Hirschler explains that the main hazard of flame spread is heat transfer, which affects mainly a person close to the fire.&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt; The smoke produced in the same test is reported separately as the [[smoke-developed index]], and the two numbers are not directly related.&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== How the index is determined ==&lt;br /&gt;
The specimen forms the ceiling of a 7.62 m (25 ft) tunnel and is exposed to a gas flame at one end, while air flows along the tunnel at 1.22 m/s (240 ft/min).&amp;lt;ref name=&amp;quot;H18-25&amp;quot;&amp;gt;Hirschler (2008b), p. 18-25.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Observers record the position of the flame front through side windows as a function of time over the 10-minute test.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The flame spread index is then calculated from the graph of flame spread against time, by comparison with the two reference materials.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The handbook describes the result as based on the area under this curve, but does not reproduce the formula of the standard.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The reference values are arbitrary. Red oak flooring is assigned 100 and a cementitious board 0.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; According to the test standard, red oak spreads flame 7.3 m (24 ft) to the end of the specimen in 5½ minutes ± 15 seconds.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; Cholin notes that red oak was originally used as the reference standard to establish the rating of 100. The test is now referenced to specific performance parameters on a noncombustible surface, but red oak still achieves about 100.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; This is consistent with the handbook giving red oak a flame spread index of approximately 100, whereas its smoke-developed index is exactly 100 by definition.&amp;lt;ref name=&amp;quot;HA6-43&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The index is a comparative number with a known scatter. Tunnel data vary considerably, and replicate tests are not likely to give precise values. Differences of 10 to 20 points are not likely to be discernible in actual fire behaviour.&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt; For that reason, flame spread indices are usually rounded to the nearest whole number divisible by 5.&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt; The scale is open at the top: values above 200 occur, such as 340 for one thin sample tested without poultry netting and up to 1375 for cellular plastics involved in fires.&amp;lt;ref name=&amp;quot;HA6-44&amp;quot;&amp;gt;Hirschler (2008a), p. 6-44.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;BC6-225&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-225.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Mounting changes the number. Products must be tested as they will be installed, because substrates, adhesives and air spaces behind the product all affect the result.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt; Thin membranes supported on poultry netting in the tunnel can score much lower than the same materials tested without it, for example 20 instead of 340.&amp;lt;ref name=&amp;quot;HA6-44&amp;quot; /&amp;gt; An index is therefore valid only for the tested combination of product, thickness and mounting.&lt;br /&gt;
&lt;br /&gt;
== Typical values ==&lt;br /&gt;
Wood is the natural point of comparison, because the scale is anchored to red oak. Cholin states that most wood species fall between 90 and 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; His table of 1 in. (25.4 mm) nominal lumber, compiled from tests by Underwriters Laboratories and others, actually spans 60 to 230. Only 11 of its 23 species lie entirely within 90 to 160.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
|+ Flame spread index of selected untreated wood species, 25.4 mm (1 in.) nominal lumber, tested to ASTM E84, UL 723 or NFPA 255&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt;&lt;br /&gt;
! Species !! Flame spread index&lt;br /&gt;
|-&lt;br /&gt;
| Western hemlock || 60–75&lt;br /&gt;
|-&lt;br /&gt;
| Redwood || 70&lt;br /&gt;
|-&lt;br /&gt;
| Western red cedar || 70&lt;br /&gt;
|-&lt;br /&gt;
| Douglas fir || 70–100&lt;br /&gt;
|-&lt;br /&gt;
| Red oak || 100&lt;br /&gt;
|-&lt;br /&gt;
| White oak || 100&lt;br /&gt;
|-&lt;br /&gt;
| Sitka spruce || 100&lt;br /&gt;
|-&lt;br /&gt;
| Lodgepole pine || 65–110&lt;br /&gt;
|-&lt;br /&gt;
| Walnut || 130–140&lt;br /&gt;
|-&lt;br /&gt;
| Southern yellow pine || 130–195&lt;br /&gt;
|-&lt;br /&gt;
| Yellow poplar || 170–185&lt;br /&gt;
|-&lt;br /&gt;
| Ponderosa pine || 105–230&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
Treatment lowers the index markedly. Pressure impregnation with fire-retardant chemicals brings the lumber, plywood and particleboard in Shaw&amp;#039;s table down to 25 or less. Untreated, the same products range from 60 to 200.&amp;lt;ref name=&amp;quot;S6-134&amp;quot; /&amp;gt; Plywood with untreated face veneers on treated cores scores generally 20 to 75, depending on the density of the face veneer, and fully treated plywood generally less than 25.&amp;lt;ref name=&amp;quot;S6-135&amp;quot;&amp;gt;Shaw (2008), p. 6-135.&amp;lt;/ref&amp;gt; Wood-fibre acoustical tiles with fire retardants added during manufacture achieve less than 25.&amp;lt;ref name=&amp;quot;S6-132&amp;quot;&amp;gt;Shaw (2008), p. 6-132.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Other building products give useful anchors. Madrzykowski and Fleming describe a fire test room for residential sprinklers. Its 6.4 mm Douglas fir plywood wall paneling has a flame spread rating of 130 ± 30, and its ceiling tiles 25 or less.&amp;lt;ref name=&amp;quot;MF16-97&amp;quot;&amp;gt;Madrzykowski and Fleming (2008), p. 16-97.&amp;lt;/ref&amp;gt; The original ceiling tiles of the World Trade Center towers had a flame spread index under 25 according to their manufacturer (Fritz and Hough 2002, as cited in Gann, Hamins, et al., 2005).&amp;lt;ref name=&amp;quot;NIST1-5-45&amp;quot;&amp;gt;Gann, Hamins, et al. (2005), p. 45.&amp;lt;/ref&amp;gt; Plastic laminates for countertops and cabinets are commonly available with values of 25 to 75.&amp;lt;ref name=&amp;quot;BC6-229&amp;quot;&amp;gt;Benedetti and Colonna (2008), p. 6-229.&amp;lt;/ref&amp;gt; Cellular plastics cover a very wide range: in fires reviewed by Underwriters Laboratories, tunnel ratings of some materials ranged from 5 to 1375.&amp;lt;ref name=&amp;quot;BC6-225&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Classes and regulatory use ==&lt;br /&gt;
In the United States, the building, fire and life safety codes use the index in classes, as summarised by Hirschler (2008a). Each class covers a range of the flame spread index. All three share one smoke limit, so the flame spread index alone decides between Classes A, B and C:&amp;lt;ref name=&amp;quot;HA6-44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;\text{Class A: } 0 \le \mathrm{FSI} \le 25, \qquad \text{Class B: } 26 \le \mathrm{FSI} \le 75, \qquad \text{Class C: } 76 \le \mathrm{FSI} \le 200, \qquad \mathrm{SDI} \le 450&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\mathrm{FSI}&amp;lt;/math&amp;gt; || flame spread index from NFPA 255 / ASTM E84 || – (non-dimensional)&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\mathrm{SDI}&amp;lt;/math&amp;gt; || smoke-developed index from the same test || – (non-dimensional)&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
NFPA 101, &amp;#039;&amp;#039;Life Safety Code&amp;#039;&amp;#039;, and NFPA 5000 (2006 editions), as described by Hirschler (2008b), assign a class to each location and occupancy.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; Exits have the strictest limits, because occupants there have restricted travel paths and may not be able to avoid the heat from a flame.&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt; General office areas are treated less strictly than exit stairs and exit access corridors. Occupancies with less capable occupants, such as health care, are stricter than those with mobile and alert occupants.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; In general, NFPA 101 limits wall and ceiling finishes to a maximum of 200.&amp;lt;ref name=&amp;quot;L4-75&amp;quot;&amp;gt;Lathrop (2008a), p. 4-75.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Automatic sprinklers relax the limits. A note to the 2006 table refers to the annex of NFPA 101 for buildings with a complete standard sprinkler system. There, Class C is permitted where Class B is required, and Class B where Class A is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; This does not apply to new detention and correctional occupancies. The trade-off is not written in code language and differs from the one in the International Building Code.&amp;lt;ref name=&amp;quot;H18-29&amp;quot;&amp;gt;Hirschler (2008b), p. 18-29.&amp;lt;/ref&amp;gt; A material that passes the NFPA 286 room-corner test may be used wherever a Class A, B or C finish is required.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
=== Worked example ===&lt;br /&gt;
A new hotel is to receive wood wall paneling. Under the &amp;#039;&amp;#039;Life Safety Code&amp;#039;&amp;#039; (2006), as tabulated by Hirschler (2008b), exits in new hotels require Class A, exit access corridors Class A or B, and other spaces Class A, B or C.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt; Three products are compared, using the upper end of each published range.&lt;br /&gt;
&lt;br /&gt;
* Untreated southern yellow pine lumber, 130 to 195, is Class C.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; It is acceptable in other spaces. In a corridor it is acceptable only if the building is fully sprinklered, because Class C may then replace Class B. In an exit it is never acceptable, because sprinklers relax Class A only to Class B.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;br /&gt;
* Untreated Douglas fir lumber, 70 to 100, falls in Class B at its lower end and in Class C at its upper end.&amp;lt;ref name=&amp;quot;C6-70&amp;quot; /&amp;gt; On the safe side, the upper value is used, and the result is then the same as for southern yellow pine.&lt;br /&gt;
* Pressure-impregnated Douglas fir lumber, 25 or less, is Class A and acceptable in all three locations.&amp;lt;ref name=&amp;quot;S6-134&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The example shows how a single number, with a scatter of 10 to 20 points, decides where a product may be used. A test of the actual product, mounted as it will be installed, replaces the published ranges in practice.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H18-27&amp;quot; /&amp;gt; Alternatively, a pass in the NFPA 286 room-corner test makes the paneling acceptable in every location.&amp;lt;ref name=&amp;quot;H18-28&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Other requirements based on the index ==&lt;br /&gt;
Many United States documents reuse the index outside the room-finish tables. NFPA 101 and NFPA 5000 (2006 editions), as described by Hirschler (2008b), require Class C for interior trim covering at most 10 percent of the wall or ceiling area. Typical wood products reach that class.&amp;lt;ref name=&amp;quot;H18-36&amp;quot;&amp;gt;Hirschler (2008b), p. 18-36.&amp;lt;/ref&amp;gt; Foam plastic trim must also have a density of at least 320 kg/m³ (20 lb/ft³) and reach Class B. Nonmetallic electrical raceways must reach 25 or less where the authority having jurisdiction judges them a hazard.&amp;lt;ref name=&amp;quot;H18-36&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Very thin materials, less than 0.9 mm (1/28 in.) thick, need no further testing as interior finish if they reach Class A on a fibre cement board.&amp;lt;ref name=&amp;quot;H18-35&amp;quot;&amp;gt;Hirschler (2008b), p. 18-35.&amp;lt;/ref&amp;gt; The exception rests on the understanding that thin coverings secured to a substrate, such as paint on steel or paper on gypsum, tend to behave like the substrate.&amp;lt;ref name=&amp;quot;H18-35&amp;quot; /&amp;gt; Finishes over an air space in noncombustible assemblies must be Class A on both faces, under the building codes described by Hirschler (2008b).&amp;lt;ref name=&amp;quot;H18-38&amp;quot;&amp;gt;Hirschler (2008b), p. 18-38.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the United States, air distribution and building services use the lowest values. The UL standards for air ducts and connectors, as described by Webb (2008), define Class 1 ducts. These have a flame spread rating of at most 25 without progressive combustion and a smoke developed rating of at most 50.&amp;lt;ref name=&amp;quot;W10-72&amp;quot;&amp;gt;Webb (2008), p. 10-72.&amp;lt;/ref&amp;gt; Plastic ducts for corrosive vapours need a flame spread rating of at most 25 and a smoke-developed rating of at most 50 to NFPA 255, as described by Lataille (2008).&amp;lt;ref name=&amp;quot;La8-7&amp;quot;&amp;gt;Lataille (2008), p. 8-7.&amp;lt;/ref&amp;gt; Combustible linings of laboratory exhaust ducts need 25 or less, as described by Anderson (2008a).&amp;lt;ref name=&amp;quot;A9-162&amp;quot;&amp;gt;Anderson (2008a), p. 9-162.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
ASME A17.1/CSA B44, as described by Donoghue (2008), allows 0 to 75 for materials exposed in elevator cars. Canadian fire fighter elevators under the National Building Code of Canada need 0 to 25 for walls and ceilings.&amp;lt;ref name=&amp;quot;D10-63&amp;quot;&amp;gt;Donoghue (2008), p. 10-63.&amp;lt;/ref&amp;gt; Under ASME A17.1/CSA B44, the materials must be tested in their end-use configuration.&amp;lt;ref name=&amp;quot;D10-63&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The index also enters material definitions. In a United States definition of limited-combustible material, quoted by Gore Willse (2008b), the potential heat must not exceed 8141 kJ/kg (3500 Btu/lb).&amp;lt;ref name=&amp;quot;GW19-5&amp;quot;&amp;gt;Gore Willse (2008b), p. 19-5.&amp;lt;/ref&amp;gt; In addition, one of two conditions applies. Either a noncombustible base carries a surfacing of at most 3.2 mm (1/8 in.) with an index of at most 50. Or the material reaches 25 or less, also on cut faces, without progressive combustion.&amp;lt;ref name=&amp;quot;GW19-5&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fire-retardant-treated wood is defined by an index of 25 or less in a tunnel test extended to 30 minutes.&amp;lt;ref name=&amp;quot;S6-133&amp;quot;&amp;gt;Shaw (2008), p. 6-133.&amp;lt;/ref&amp;gt; Underwriters Laboratories requires listed fire-retardant coatings to reach 50 or less, or half the value of the untreated surface, whichever is lower.&amp;lt;ref name=&amp;quot;S6-136&amp;quot;&amp;gt;Shaw (2008), p. 6-136.&amp;lt;/ref&amp;gt; A definition by Nolan instead uses a 50 percent reduction or a value of 75, whichever is lesser, together with a smoke developed rating of at most 200.&amp;lt;ref name=&amp;quot;Nolan-F28&amp;quot;&amp;gt;Nolan (2000), as cited in Iqbal and Salley (2004), p. F-28.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Relation to real fire behaviour ==&lt;br /&gt;
The index ranks materials under one standard exposure; it does not predict fire growth. Hirschler states that there is not necessarily a correlation between the measured index and product behaviour in actual fires.&amp;lt;ref name=&amp;quot;H18-26&amp;quot; /&amp;gt; The tunnel very likely gives falsely favourable results for materials that melt and drip and for thin films. It rarely gives falsely unfavourable ones, so a high index almost always indicates mediocre or poor performance.&amp;lt;ref name=&amp;quot;H18-31&amp;quot; /&amp;gt; In a survey of 25 materials, five with an index of 200 or less caused flashover in the room-corner test.&amp;lt;ref name=&amp;quot;H18-31&amp;quot; /&amp;gt; Some textile wall coverings reach less than 25 and still spread flame to flashover within minutes in room-corner tests.&amp;lt;ref name=&amp;quot;H18-35&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Quintiere reports a correlation that helps to explain this behaviour. Tunnel ratings were found to be low and insensitive to the energy release rate per unit area below about 70 kW/m², and highly sensitive above that value.&amp;lt;ref name=&amp;quot;Q2-253&amp;quot;&amp;gt;Quintiere (2002b), p. 2-253.&amp;lt;/ref&amp;gt; Some critical rate of energy release thus appears to be needed before flame spread in the tunnel becomes self-sustaining.&amp;lt;ref name=&amp;quot;Q2-253&amp;quot; /&amp;gt; Benedetti and Colonna warn that a low classification, such as 25 or less, does not ensure limited combustibility for exposed foam on ceilings, in plenums or in shafts.&amp;lt;ref name=&amp;quot;BC6-229&amp;quot; /&amp;gt; Four materials in one test series all scored 18, yet affected between 24 and 85 percent of the wall and ceiling area in a full-size corner test.&amp;lt;ref name=&amp;quot;BC6-226&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The position of a finish also matters. In full-scale corridor experiments, wall coverings with an index of 90 could be used safely with ceilings of 25 or less, if they were limited to the lower 1.2 m (4 ft) of the wall.&amp;lt;ref name=&amp;quot;H18-39&amp;quot;&amp;gt;Hirschler (2008b), p. 18-39.&amp;lt;/ref&amp;gt; Full-height coverings of 90 led to rapid flame propagation. Some Class A ceiling materials increased flame spread over the walls, because they insulated better than materials with an index of zero.&amp;lt;ref name=&amp;quot;H18-39&amp;quot; /&amp;gt; O&amp;#039;Connor reports the same principle for health care: finishes on the lower half of a wall, below 1.2 m, contribute less to flame propagation than finishes higher up.&amp;lt;ref name=&amp;quot;OC20-145&amp;quot;&amp;gt;O&amp;#039;Connor (2008), p. 20-145.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Engineering analyses sometimes still use the index. In Ramachandran&amp;#039;s stochastic model of corridor fire spread, the probability of spread before flashover is, to a first approximation, governed by the flame spread classification of the finishes.&amp;lt;ref name=&amp;quot;R3-393&amp;quot;&amp;gt;Ramachandran (2002c), p. 3-393.&amp;lt;/ref&amp;gt; Such uses rest on the ranking, not on a physical quantity.&lt;br /&gt;
&lt;br /&gt;
== Comparison with other flame spread measures ==&lt;br /&gt;
Other tests produce indices that are not interchangeable with the FSI. The radiant panel test, ASTM E162, exposes a 150 mm by 460 mm specimen, inclined at an angle of 30 degrees, to a radiant panel of about 45 kW/m².&amp;lt;ref name=&amp;quot;HA6-44&amp;quot; /&amp;gt; Its radiant panel index is the product of a flame spread factor and a heat evolution factor, and differs from the tunnel index.&amp;lt;ref name=&amp;quot;HA6-44&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the United States it is not used in building, fire or life safety codes as a substitute for the tunnel test. The Federal Railroad Administration and NFPA 130, however, require radiant panel indices of 25 to 100 for rail lining materials. NFPA 1192 (recreational vehicles) and NFPA 501 (manufactured housing) require an index of 200 for certain finishes.&amp;lt;ref name=&amp;quot;H18-32&amp;quot;&amp;gt;Hirschler (2008b), p. 18-32.&amp;lt;/ref&amp;gt; The lateral ignition and flame spread test (LIFT) produces data in engineering units that can be used to predict full-scale flame spread.&amp;lt;ref name=&amp;quot;HA6-45&amp;quot;&amp;gt;Hirschler (2008a), p. 6-45.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Outside North America, [[reaction to fire]] is classified differently. The tunnel test is widely accepted only in North America.&amp;lt;ref name=&amp;quot;HA6-42&amp;quot; /&amp;gt; The European Community uses the ISO 9705 room-corner test as its reference scenario and other tests as surrogates.&amp;lt;ref name=&amp;quot;HA6-53&amp;quot;&amp;gt;Hirschler (2008a), p. 6-53.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the [[Euroclass system]], construction products other than floorings, pipe insulation and cables are placed in classes A1 to F. For classes B, C and D the single burning item test (EN 13823) limits the fire growth rate to 120, 250 and 750 W/s respectively.&amp;lt;ref name=&amp;quot;HA6-52&amp;quot;&amp;gt;Hirschler (2008a), p. 6-52.&amp;lt;/ref&amp;gt; A small-flame test, EN ISO 11925-2, limits flame spread to 150 mm, and separate additional classes cover smoke and flaming droplets.&amp;lt;ref name=&amp;quot;HA6-52&amp;quot; /&amp;gt; The European criteria are thus expressed as fire growth rate, total heat release, flame spread distance and smoke production, not as a tunnel index.&amp;lt;ref name=&amp;quot;HA6-52&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the United States, [[interior finish]] can already be approved by heat release instead of the index. The codes accept NFPA 286 because materials that do not cause flashover in that room-corner test are known to have an index below 200 and a smoke-developed index below 450.&amp;lt;ref name=&amp;quot;H18-31&amp;quot; /&amp;gt; The International Building Code, as quoted in the International Fire Engineering Guidelines (2005), similarly allows NFPA 286 where Class A to ASTM E 84 is required, except for textiles.&amp;lt;ref name=&amp;quot;IFEG0.2-10&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), p. 0.2-10 (Part 0, United States).&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Fire-retardant-treated wood]]&lt;br /&gt;
* [[Wood-based panel products]]&lt;br /&gt;
* [[Room corner test]]&lt;br /&gt;
* [[Cone calorimeter]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Anderson, R. R. (2008a). Fire protection of laboratories using chemicals. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 9-157–9-166). National Fire Protection Association.&lt;br /&gt;
* Benedetti, R. P., &amp;amp; Colonna, G. R. (2008). Polymeric materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-209–6-231). National Fire Protection Association.&lt;br /&gt;
* Cholin, J. M. (2008c). Wood and wood-based products. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-61–6-74). National Fire Protection Association.&lt;br /&gt;
* Donoghue, E. A. (2008). Building transportation systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 10-57–10-68). National Fire Protection Association.&lt;br /&gt;
* Gann, R. G., Hamins, A., McGrattan, K. B., Mulholland, G. W., Nelson, H. E., Ohlemiller, T. J., Pitts, W. M., &amp;amp; Prasad, K. R. (2005). &amp;#039;&amp;#039;Reconstruction of the fires in the World Trade Center towers&amp;#039;&amp;#039; (NIST NCSTAR 1-5). National Institute of Standards and Technology.&lt;br /&gt;
* Gore Willse, P. J. (2008b). Types of building construction. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 19-3–19-27). National Fire Protection Association.&lt;br /&gt;
* Hirschler, M. M. (2008a). Concepts and protocols of fire testing. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-35–6-60). National Fire Protection Association.&lt;br /&gt;
* Hirschler, M. M. (2008b). Interior finish. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 18-23–18-42). National Fire Protection Association.&lt;br /&gt;
* Iqbal, N., &amp;amp; Salley, M. H. (2004). &amp;#039;&amp;#039;Fire Dynamics Tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission Fire Protection Inspection Program&amp;#039;&amp;#039; (NUREG-1805). U.S. Nuclear Regulatory Commission, Office of Nuclear Reactor Regulation.&lt;br /&gt;
* Lataille, J. I. (2008). Air-Moving equipment. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 8-3–8-15). National Fire Protection Association.&lt;br /&gt;
* Lathrop, J. K. (2008a). Concepts of egress design. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 4-69–4-91). National Fire Protection Association.&lt;br /&gt;
* Madrzykowski, D., &amp;amp; Fleming, R. P. (2008). Residential sprinkler systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 16-91–16-107). National Fire Protection Association.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International fire engineering guidelines&amp;#039;&amp;#039; (2005 ed.). Australian Building Codes Board.&lt;br /&gt;
* O&amp;#039;Connor, D. J. (2008). Health care occupancies. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 20-139–20-155). National Fire Protection Association.&lt;br /&gt;
* Quintiere, J. G. (2002b). Surface flame spread. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 2-246–2-257). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* Ramachandran, G. (2002c). Stochastic models of fire growth. In P. J. DiNenno, D. Drysdale, C. L. Beyler, W. D. Walton, R. L. P. Custer, J. R. Hall Jr., &amp;amp; J. M. Watts Jr. (Eds.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 3-381–3-401). National Fire Protection Association; Society of Fire Protection Engineers.&lt;br /&gt;
* Shaw, J. R. (2008). Fire-Retardant and flame-resistant treatment of cellulosic materials. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 6-129–6-139). National Fire Protection Association.&lt;br /&gt;
* Webb, W. A. (2008). Air-Conditioning and ventilating systems. In A. E. Cote, C. C. Grant, J. R. Hall Jr., &amp;amp; R. E. Solomon (Eds.), &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed., pp. 10-69–10-76). National Fire Protection Association.&lt;br /&gt;
&lt;br /&gt;
[[Category:Materials &amp;amp; Fire Testing]]&lt;/div&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
</feed>