<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Fire_water_storage_tank</id>
	<title>Fire water storage tank - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Fire_water_storage_tank"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;action=history"/>
	<updated>2026-11-21T22:43:53Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=9497&amp;oldid=prev</id>
		<title>Peter: Wiki review: corrected 13 errors: citation (13) (Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=9497&amp;oldid=prev"/>
		<updated>2026-11-16T00:32:24Z</updated>

		<summary type="html">&lt;p&gt;Wiki review: corrected 13 errors: citation (13) (Claude Opus 5.5)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;amp;diff=9497&amp;amp;oldid=6408&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=6408&amp;oldid=prev</id>
		<title>Mark: Add SVG figures fse-fire-water-storage-tank-v1.svg, fse-fire-water-storage-tank-v2.svg, fse-fire-water-storage-tank-v3.svg (list-5 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=6408&amp;oldid=prev"/>
		<updated>2026-11-12T18:51:45Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-fire-water-storage-tank-v1.svg, fse-fire-water-storage-tank-v2.svg, fse-fire-water-storage-tank-v3.svg (list-5 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 19:51, 12 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l5&quot;&gt;Line 5:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 5:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Usable reserve and tank arrangement ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Usable reserve and tank arrangement ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A tank can supply a [[Sprinkler system|sprinkler system]] where the public connection is insufficient or where a separate reserve is part of the [[Fire water supply|fire water supply]]; a gravity arrangement derives pressure from elevation. A suction tank relies on a [[Fire pump|fire pump]] for additional head. Each arrangement must be assessed at the water level that governs its useful delivery. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F_4-83&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-83.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A tank can supply a [[Sprinkler system|sprinkler system]] where the public connection is insufficient or where a separate reserve is part of the [[Fire water supply|fire water supply]]; a gravity arrangement derives pressure from elevation. A suction tank relies on a [[Fire pump|fire pump]] for additional head. Each arrangement must be assessed at the water level that governs its useful delivery. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F_4-83&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-83.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-fire-water-storage-tank-v1.svg|thumb|upright=1.5|alt=Fire water storage tank: functional relationships. Measurement and water paths are distinct.|Fire water storage tank: functional relationships. Schematic explanation; dimensions are not installation instructions.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Net positive suction head]] links the lowest usable tank level to pump operation; water remaining below a suitable intake level may be physically present but unavailable for the intended duty. Sediment and internal condition can further affect the outlet route. [[Microbiologically influenced corrosion]] is one possible contributor to deterioration in connected metallic water systems, requiring evidence rather than assumption. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5_15-18_15-19&amp;quot;&amp;gt;Cote (2008), ch. 15.1, pp. 15-3–15-5,15-18–15-19.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_5_15-79_15-81&amp;quot;&amp;gt;Cote (2008), ch. 15.5, pp. 15-79–15-81.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Net positive suction head]] links the lowest usable tank level to pump operation; water remaining below a suitable intake level may be physically present but unavailable for the intended duty. Sediment and internal condition can further affect the outlet route. [[Microbiologically influenced corrosion]] is one possible contributor to deterioration in connected metallic water systems, requiring evidence rather than assumption. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5_15-18_15-19&amp;quot;&amp;gt;Cote (2008), ch. 15.1, pp. 15-3–15-5,15-18–15-19.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_5_15-79_15-81&amp;quot;&amp;gt;Cote (2008), ch. 15.5, pp. 15-79–15-81.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l12&quot;&gt;Line 12:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 13:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Flow, pressure and duration ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Flow, pressure and duration ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A fire water supply has several necessary characteristics: adequate flow, sufficient pressure at that flow, an appropriate duration and availability when needed; these characteristics cannot replace one another. A large reservoir may have insufficient delivery capacity, while a high-pressure connection may offer too little sustained flow. The required combination depends on the fire protection demand being assessed. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-24.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-67&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-67.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A fire water supply has several necessary characteristics: adequate flow, sufficient pressure at that flow, an appropriate duration and availability when needed; these characteristics cannot replace one another. A large reservoir may have insufficient delivery capacity, while a high-pressure connection may offer too little sustained flow. The required combination depends on the fire protection demand being assessed. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-24.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-67&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-67.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-fire-water-storage-tank-v2.svg|thumb|upright=1.5|alt=Rate, duration and usable reserve. Measurement and water paths are distinct.|Rate, duration and usable reserve. Schematic explanation; dimensions are not installation instructions.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Demand must identify which outlets operate together; sprinkler calculations assemble the flows of individual operating sprinklers and include other applicable demands under the selected design basis. Municipal fire-flow planning addresses a different question and may include wider firefighting activity. Treating every quoted fire-flow value as a sprinkler demand obscures these differences. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-29&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-29.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-74_4-81&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-74–4-81.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Demand must identify which outlets operate together; sprinkler calculations assemble the flows of individual operating sprinklers and include other applicable demands under the selected design basis. Municipal fire-flow planning addresses a different question and may include wider firefighting activity. Treating every quoted fire-flow value as a sprinkler demand obscures these differences. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-29&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-29.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-74_4-81&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-74–4-81.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l37&quot;&gt;Line 37:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 39:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Suction conditions and cavitation ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Suction conditions and cavitation ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&amp;#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-68.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&amp;#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-68.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-fire-water-storage-tank-v3.svg|thumb|upright=1.5|alt=Available suction head. Measurement and water paths are distinct.|Available suction head. Schematic explanation; dimensions are not installation instructions.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Available net positive suction head describes the installation&amp;#039;s suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-92&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-92.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Available net positive suction head describes the installation&amp;#039;s suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-92&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-92.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-3775:rev-6408:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Mark</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=3775&amp;oldid=prev</id>
		<title>Daan: Refine sentence flow and printed-page reference locators (written by GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=3775&amp;oldid=prev"/>
		<updated>2026-11-07T21:37:02Z</updated>

		<summary type="html">&lt;p&gt;Refine sentence flow and printed-page reference locators (written by GPT-6)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;amp;diff=3775&amp;amp;oldid=3450&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Daan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=3450&amp;oldid=prev</id>
		<title>Daan: New FSE wiki article: Fire water storage tank (written by GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_water_storage_tank&amp;diff=3450&amp;oldid=prev"/>
		<updated>2026-11-07T21:26:17Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Fire water storage tank (written by GPT-6)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Fire water storage tank&amp;#039;&amp;#039;&amp;#039; is a vessel that holds a reserve of water for firefighting or fixed fire protection systems. &amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-83–4-84.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot;&amp;gt;Cote (2008), ch. 15.1, pp. 15-3–15-5.&amp;lt;/ref&amp;gt; The reserve may supply outlets by gravity or through a pump. Its useful capacity depends on the draw-off arrangement, operating water levels and any other uses of the stored water. Nominal capacity, available pressure and dependable duration are therefore separate characteristics of the installation. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Effective supply requires the right combination of flow, pressure, duration and availability. Each characteristic answers a different question about the protected demand. Source observations must be transferred through the actual connecting route before comparison with that demand. Storage, automatic operation and supplementary fire-service delivery can contribute in different ways, with their respective dependencies retained in the assessment. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-30&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-30.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-65.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-81_4-83&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-81–4-83.&amp;lt;/ref&amp;gt; The lowest relevant source level can govern delivery. &amp;lt;ref name=&amp;quot;H_15_4_15-63_15-64&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-64.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Usable reserve and tank arrangement ==&lt;br /&gt;
A tank can supply a [[Sprinkler system|sprinkler system]] where the public connection is insufficient or where a separate reserve is part of the [[Fire water supply|fire water supply]]. A gravity arrangement derives pressure from elevation. A suction tank relies on a [[Fire pump|fire pump]] for additional head. Each arrangement must be assessed at the water level that governs its useful delivery. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F_4-83&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-83.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[Net positive suction head]] links the lowest usable tank level to pump operation. Water remaining below a suitable intake level may be physically present but unavailable for the intended duty. Sediment and internal condition can further affect the outlet route. [[Microbiologically influenced corrosion]] is one possible contributor to deterioration in connected metallic water systems, requiring evidence rather than assumption. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5_15-18_15-19&amp;quot;&amp;gt;Cote (2008), ch. 15.1, pp. 15-3–15-5,15-18–15-19.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_5_15-79_15-81&amp;quot;&amp;gt;Cote (2008), ch. 15.5, pp. 15-79–15-81.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The tank and its connections also interact with building movement. The handbook discusses earthquake effects on stored water, anchorage and connecting pipework. [[Seismic bracing]] of the distribution piping addresses only part of that arrangement. Tank support, differential movement and an available outlet must remain compatible for the reserve to serve its purpose after movement. &amp;lt;ref name=&amp;quot;H_15_1_15-4_15-5&amp;quot;&amp;gt;Cote (2008), ch. 15.1, pp. 15-4–15-5.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_4_16-65_16-67&amp;quot;&amp;gt;Cote (2008), ch. 16.4, pp. 16-65–16-67.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Flow, pressure and duration ==&lt;br /&gt;
A fire water supply has several necessary characteristics: adequate flow, sufficient pressure at that flow, an appropriate duration and availability when needed. These characteristics cannot replace one another. A large reservoir may have insufficient delivery capacity, while a high-pressure connection may offer too little sustained flow. The required combination depends on the fire protection demand being assessed. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-24.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-67&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-67.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Demand must identify which outlets operate together. Sprinkler calculations assemble the flows of individual operating sprinklers and include other applicable demands under the selected design basis. Municipal fire-flow planning addresses a different question and may include wider firefighting activity. Treating every quoted fire-flow value as a sprinkler demand obscures these differences. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-29&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-29.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-74_4-81&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-74–4-81.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The supply location also matters. A pressure measured in a street main is not automatically available at a building riser. Connecting pipework, backflow assemblies and changes in elevation affect the transfer. The assessment follows the supply through these elements to the same reference point used for the calculated demand. &amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F_4-81_4-83&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Storage introduces a time dimension that a pressure-flow curve alone does not show. Usable water is the quantity that the outlet or pump can actually draw while meeting its operating conditions. Water below the effective intake, or reserved for another purpose, cannot simply be counted as fire reserve. Replenishment contributes only through an identified source and a delivery arrangement that remains available. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A constant-flow volume calculation multiplies flow by duration. In the following form, flow is in litres per minute and usable volume is in cubic metres. The factor converts litres to cubic metres. &amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;V_u=\frac{Qt}{1000}&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;V_u&amp;lt;/math&amp;gt; || Usable water volume || m³&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;Q,t&amp;lt;/math&amp;gt; || Constant discharge and duration || L/min; min&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
A worked example separates usable water from gross capacity. Using Fleming&amp;#039;s example of 530 L/min for 30 minutes gives 15,900 L, or 15.9 m³, of usable water. This arithmetic does not select a design duration or establish the gross tank volume. The example is a historical worked calculation, with tank configuration and unavailable volume assessed separately. &amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Public supplies can change with domestic use, industrial demand, maintenance and seasonal conditions. Tank levels and pump operation can change during a fire as well. The design record therefore needs the conditions represented by the available supply, including relevant adverse conditions. A favourable isolated reading does not establish availability throughout the required incident duration. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-64&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Suction conditions and cavitation ==&lt;br /&gt;
Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation. Pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&amp;#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-68.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Available net positive suction head describes the installation&amp;#039;s suction energy above vapour-pressure head. Required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-92&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-92.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For a large open reservoir, the following form separates atmospheric pressure, water level and suction losses. The reservoir surface velocity is treated as negligible. A positive elevation difference means that the water surface is above the pump reference. A lower surface contributes a negative term. &amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;NPSH_a=\frac{p_a-p_v}{\rho g}+z_s-z_p-h_s&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;NPSH_a&amp;lt;/math&amp;gt; || Available net positive suction head || m&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;p_a,p_v&amp;lt;/math&amp;gt; || Absolute atmospheric and vapour pressures || Pa&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\rho,g&amp;lt;/math&amp;gt; || Water density and gravitational acceleration || kg/m³; m/s²&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;z_s,z_p,h_s&amp;lt;/math&amp;gt; || Surface elevation, pump elevation and suction loss || m&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The lowest usable tank level can be more demanding than the initial full condition. A greater flow increases suction-pipe loss and can also increase the pump&amp;#039;s required suction head. Warmer water increases vapour pressure, while atmospheric pressure varies with elevation. These effects explain why a universal maximum suction lift cannot represent every installation. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-95&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-95.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The handbook illustrates a pump requiring approximately 3.05 m of suction head at 7,570 L/min and 5.49 m at 11,400 L/min. These are converted values from one illustrative manufacturer&amp;#039;s-style curve, not general acceptance limits. Their significance is the changing requirement as flow rises. The appropriate comparison uses the actual pump data and the available head under the corresponding supply condition. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Availability and common dependencies ==&lt;br /&gt;
Two components do not necessarily provide two independent supplies. A pair of pumps may share the same tank, intake, electrical route or vulnerable connecting main. A looped network may still depend on one source connection. The relevant question is whether the required water path remains available after the particular failure being considered. &amp;lt;ref name=&amp;quot;H_15_2_15-27_15-30&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-27–15-30.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;N_xxxvii_xlii&amp;quot;&amp;gt;Hopkins et al. (2005), pp. xxxvii–xlii.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The NIST investigation of the World Trade Center&amp;#039;s 2001 fire suppression systems provides a specific illustration. Its review identified vulnerabilities associated with floor-feed arrangements and with the limits of some hydraulic calculation paths. It also considered the dependence of manually operated equipment on personnel access and action. These findings describe that complex and that investigation; they are not failure probabilities for all buildings. &amp;lt;ref name=&amp;quot;N_xxxvii_xlii&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The case also shows why upstream duplication alone is insufficient. Alternative water sources may converge on a single downstream segment. Damage or isolation at that segment can interrupt the route to the affected area despite apparently generous upstream equipment. Conversely, a reserve serving another pressure zone does not automatically become a usable alternative without an available connection. &amp;lt;ref name=&amp;quot;N_xxxvii_xlii&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Automatic and manual supply functions need separate treatment. A fire department connection depends on responding apparatus, water, personnel and access. A stored or pumped automatic supply can begin serving a demand without those same preliminary actions, provided its own operating chain remains intact. Calling both arrangements a water supply does not make their activation times or dependencies equivalent. &amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_16_10_16-200_16-201&amp;quot;&amp;gt;Cote (2008), ch. 16.10, pp. 16-200–16-201.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Duration introduces further common dependencies. Refill may rely on the same utility that a reserve is intended to supplement. Fuel and cooling water can constrain a driver even when the pump itself is mechanically sound. Seasonal source variation can affect both the initial reserve and its replenishment. Such dependencies belong in the description of the actual arrangement. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_6_15-98_15-99&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-98–15-99.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-44.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Availability also changes during maintenance. Sectional isolation can limit the area affected by work, while unclear valve identification can enlarge it. The handbook links planned shutdowns to preparation, notification and verified restoration. Records of the normal configuration make these operational controls meaningful rather than relying on an assumed open water path. &amp;lt;ref name=&amp;quot;H_16_11_16-208_16-209_16-221&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-208–16-209,16-221.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Earthquake movement and restraint ==&lt;br /&gt;
Earthquake protection of piping combines restraint with accommodation of movement. Braces limit displacement by transferring inertia forces to suitable structural members. Flexible connections and clearance address relative movement where rigid restraint would create damaging interaction. Treating every part as either completely rigid or completely free misses this combined function. &amp;lt;ref name=&amp;quot;H_16_4_16-55_16-65_16-67&amp;quot;&amp;gt;Cote (2008), ch. 16.4, pp. 16-55,16-65–16-67.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-84_4-85&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-84–4-85.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Lateral bracing resists movement across the pipe direction, while longitudinal bracing resists movement along it. A four-way arrangement addresses both horizontal directions. The supported piping assigned to a brace is described through its zone of influence. That allocation includes the relevant water-filled pipework and associated load allowances in the stated design method. &amp;lt;ref name=&amp;quot;H_16_4_16-65_16-67&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The handbook expresses the horizontal design force as a coefficient multiplied by the assigned weight. The coefficient represents the seismic design basis, rather than a property of the pipe material. Its value cannot be selected from pipe diameter alone. The resulting force then has to pass through the brace, its fittings, its fastener and the building structure. &amp;lt;ref name=&amp;quot;H_16_4_16-65_16-67&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;F_p=C_pW_p&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;F_p&amp;lt;/math&amp;gt; || Horizontal design force || N&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;C_p&amp;lt;/math&amp;gt; || Seismic coefficient for the stated method || dimensionless&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;W_p&amp;lt;/math&amp;gt; || Assigned piping weight including applicable allowances || N&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The United States NFPA 13 (2007) table reproduced in the handbook gives a coefficient of 0.52 for its stated mapped-acceleration input of 1.00. A normalised example with an assigned weight of 1.00 kN therefore produces 0.52 kN of horizontal force. This shows the arithmetic, not a site-specific seismic selection. The table&amp;#039;s assumptions and the actual building conditions remain separate design inputs. &amp;lt;ref name=&amp;quot;H_16_4_16-65_16-67&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The weakest component limits the brace assembly. Inclination changes the forces carried by the brace and its connections. Slender compression members can buckle, while tension-only cables need arrangements that resist movement in opposing directions. The capacity of the receiving structural member must also be established, so an adequate pipe clamp alone does not complete the load path. &amp;lt;ref name=&amp;quot;H_16_4_16-67&amp;quot;&amp;gt;Cote (2008), ch. 16.4, pp. 16-67.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-84_4-85&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Corrosion, deposits and diagnosis ==&lt;br /&gt;
Microbiologically influenced corrosion describes microbial participation in corrosion processes. Organisms and their biofilms can change local chemistry and establish conditions that promote metal loss. The presence of bacteria does not by itself prove that they caused a particular failure. The handbook explicitly distinguishes evidence of organisms from a defensible diagnosis of their role. &amp;lt;ref name=&amp;quot;H_15_5_15-75_15-78_15-81&amp;quot;&amp;gt;Cote (2008), ch. 15.5, pp. 15-75,15-78–15-81.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Biofilms can create local differences in oxygen concentration and other chemical conditions. Deposits may maintain an aggressive local environment even after a treatment reduces viable organisms. A high microbial count is therefore not a direct measurement of corrosion rate. A low count at one sampling time likewise does not reconstruct the previous history of an affected pipe. &amp;lt;ref name=&amp;quot;H_15_5_15-79_15-81&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Both wet and dry sprinkler arrangements can be affected by internal deterioration. A dry system can retain water in low points and expose that water to oxygen in the gas supply. Water chemistry and deposits also matter in wet systems. Plastic components can experience biological fouling even though the same metallic corrosion mechanism does not apply to the plastic itself. &amp;lt;ref name=&amp;quot;H_15_5_15-79_15-81&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-211_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-211–16-212.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The consequences need separate description. Wall loss can lead to leakage or loss of integrity, while deposits increase resistance or reduce the effective bore. Detached material can migrate and obstruct a smaller downstream opening. No single roughness coefficient represents every combination of these effects. The hydraulic model and the assessment of physical condition therefore answer complementary questions. &amp;lt;ref name=&amp;quot;H_15_5_15-80_15-81&amp;quot;&amp;gt;Cote (2008), ch. 15.5, pp. 15-80–15-81.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-50_4-53&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-50–4-53.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-212.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A useful investigation combines observations of the metal, deposits, water chemistry and microbiology. The handbook cautions against assigning cause from a single test result. Cleaning and treatment also require separate evaluation because removing organisms does not restore lost wall thickness. The remaining installation must still meet its structural and hydraulic functions. &amp;lt;ref name=&amp;quot;H_15_5_15-80_15-81&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The maintenance implication is broader than finding a chemical treatment. Source-water condition, retained water, internal debris and future inspection all affect continued performance. Treatment concentrations can be difficult to control in intermittently flowing sprinkler networks. The available handbook discussion explains these limitations without providing a current product-specific treatment specification. &amp;lt;ref name=&amp;quot;H_15_5_15-81&amp;quot;&amp;gt;Cote (2008), ch. 15.5, pp. 15-81.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;I_1_7-8&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), pp. 1.7-8.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Inspection and evidence of readiness ==&lt;br /&gt;
Inspection, testing and maintenance provide different forms of evidence. Visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation&amp;#039;s intended state. &amp;lt;ref name=&amp;quot;H_16_11_16-205_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-205–16-212.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance. A system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. &amp;lt;ref name=&amp;quot;H_16_11_16-205&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-205.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position. Neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. &amp;lt;ref name=&amp;quot;H_16_3_16-42_16-43&amp;quot;&amp;gt;Cote (2008), ch. 16.3, pp. 16-42–16-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-209_16-210&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-209–16-210.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Deposits on a sprinkler can interfere with heating or mechanical release. Corrosion can affect both the operating mechanism and water passage. Inside pipes, scale or foreign material can migrate to smaller fittings and outlets. These mechanisms explain why an apparently pressurised system may still have reduced effective protection. &amp;lt;ref name=&amp;quot;H_16_11_16-207_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-207–16-212.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The purpose of a test determines its interpretation. An alarm test can establish signalling without demonstrating the full water demand. A main-drain comparison can reveal a changed supply condition without reproducing every operating sprinkler. A pump start test exercises starting functions, while a flow test examines delivery capability over selected operating points. &amp;lt;ref name=&amp;quot;H_14_4_14-42_14-43&amp;quot;&amp;gt;Cote (2008), ch. 14.4, pp. 14-42–14-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-210_16-211_16-220&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-210–16-211,16-220.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The International Fire Engineering Guidelines (IFEG) links commissioning to the performance assumed in a fire engineering evaluation. It also links subsequent management and maintenance to keeping those assumptions valid. This provides a useful framework for reading test records: the observation must answer the performance question being claimed. Successful operation of one component is evidence about that component and the functions actually exercised. &amp;lt;ref name=&amp;quot;I_1_7-8&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Water distribution system]]&lt;br /&gt;
* [[Private fire service main]]&lt;br /&gt;
* [[Needed fire flow]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Cote, A. E. (Ed.). (2008). &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed.). National Fire Protection Association.&lt;br /&gt;
* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 4-72–4-87). National Fire Protection Association.&lt;br /&gt;
* Hopkins, M., Schoenrock, J., &amp;amp; Budnick, E. (2005). &amp;#039;&amp;#039;Fire suppression systems&amp;#039;&amp;#039; (NIST NCSTAR 1-4B). National Institute of Standards and Technology.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International fire engineering guidelines&amp;#039;&amp;#039;. Australian Building Codes Board.&lt;br /&gt;
* Titus, J. J. (2002). Hydraulics. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 4-44–4-71). National Fire Protection Association.&lt;br /&gt;
&lt;br /&gt;
[[Category:Water Supply &amp;amp; Hydraulics]]&lt;/div&gt;</summary>
		<author><name>Daan</name></author>
	</entry>
</feed>