<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Fire_extinguisher_rating</id>
	<title>Fire extinguisher rating - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Fire_extinguisher_rating"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;action=history"/>
	<updated>2026-11-21T22:44:38Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=9297&amp;oldid=prev</id>
		<title>Peter: Wiki review: corrected 1 error: citation (Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=9297&amp;oldid=prev"/>
		<updated>2026-11-15T23:41:03Z</updated>

		<summary type="html">&lt;p&gt;Wiki review: corrected 1 error: citation (Claude Opus 5.5)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 00:41, 16 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l74&quot;&gt;Line 74:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 74:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An installed system needs evidence that its components perform the intended sequence together. Commissioning examines the arrangement as built, including supplies, controls and the interfaces with the protected process. A component test establishes only the behaviour observed under that test. The Australian part of the International Fire Engineering Guidelines treats commissioning as a distinct stage connecting design and subsequent occupation or use.&amp;lt;ref name=&amp;quot;I-f73f312240&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.6; pp. 0.3-6–0.3-7.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An installed system needs evidence that its components perform the intended sequence together. Commissioning examines the arrangement as built, including supplies, controls and the interfaces with the protected process. A component test establishes only the behaviour observed under that test. The Australian part of the International Fire Engineering Guidelines treats commissioning as a distinct stage connecting design and subsequent occupation or use.&amp;lt;ref name=&amp;quot;I-f73f312240&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.6; pp. 0.3-6–0.3-7.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Inspection and functional testing provide complementary information. Physical examination can reveal corrosion, obstruction, leakage or changes around the hazard. Functional tests can demonstrate flow, proportioning, signalling or mechanical movement under specified conditions. The Fire Protection Handbook&#039;s foam-system discussion separates these checks from the more extensive task of demonstrating complete extinguishing performance. It also recognises test arrangements that avoid unnecessarily discharging agent over the protected equipment.&amp;lt;ref name=&quot;F-2ef4d8b6a4&quot;&amp;gt;Cote et al. (2008), chapter 17.4, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 17-68.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Inspection and functional testing provide complementary information. Physical examination can reveal corrosion, obstruction, leakage or changes around the hazard. Functional tests can demonstrate flow, proportioning, signalling or mechanical movement under specified conditions. The Fire Protection Handbook&#039;s foam-system discussion separates these checks from the more extensive task of demonstrating complete extinguishing performance. It also recognises test arrangements that avoid unnecessarily discharging agent over the protected equipment.&amp;lt;ref name=&quot;F-2ef4d8b6a4&quot;&amp;gt;Cote et al. (2008), chapter 17.4, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 17-68.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Records connect observations with the installation&amp;#039;s intended performance. An indicated pressure, for example, establishes a different fact from a measured agent quantity or a demonstrated discharge pattern. The handbook makes this distinction particularly clear for portable extinguishers. A satisfactory observation must therefore be interpreted in relation to what was measured, rather than treated as proof that every possible failure has been excluded.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Records connect observations with the installation&amp;#039;s intended performance. An indicated pressure, for example, establishes a different fact from a measured agent quantity or a demonstrated discharge pattern. The handbook makes this distinction particularly clear for portable extinguishers. A satisfactory observation must therefore be interpreted in relation to what was measured, rather than treated as proof that every possible failure has been excluded.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-6587:rev-9297:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=6587&amp;oldid=prev</id>
		<title>Mark: Remove source references from image captions</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=6587&amp;oldid=prev"/>
		<updated>2026-11-13T07:27:12Z</updated>

		<summary type="html">&lt;p&gt;Remove source references from image captions&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:27, 13 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;[[Fire extinguisher|fire extinguisher]] rating&amp;#039;&amp;#039;&amp;#039; is a classification of an extinguisher&amp;#039;s fire performance under a specified test system. It differs from the amount of agent contained in the equipment. The Fire Protection Handbook presents agent capacity and rated capability as separate characteristics because the complete discharge arrangement contributes to performance.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-73–17-74.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;[[Fire extinguisher|fire extinguisher]] rating&amp;#039;&amp;#039;&amp;#039; is a classification of an extinguisher&amp;#039;s fire performance under a specified test system. It differs from the amount of agent contained in the equipment. The Fire Protection Handbook presents agent capacity and rated capability as separate characteristics because the complete discharge arrangement contributes to performance.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-73–17-74.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-fire-extinguisher-rating-v1.svg|thumb|upright=1.5|alt=Separate agent capacity from tested performance.|Separate agent capacity from tested performance&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cote et al. (2008), chapter 17.5, pp. 17-73–17-74; Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84; Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-81–17-82&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-fire-extinguisher-rating-v1.svg|thumb|upright=1.5|alt=Separate agent capacity from tested performance.|Separate agent capacity from tested performance.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the NFPA framework discussed by the handbook, [[Fire classes|fire classes]] identify the type of hazard, with numerical ratings used for particular classes. [[NFPA 10]] relates the resulting classifications to selection and distribution. The meaning of a letter or number consequently depends on the classification and edition in which it is used.&amp;lt;ref name=&amp;quot;F-fec2bf6e94&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the NFPA framework discussed by the handbook, [[Fire classes|fire classes]] identify the type of hazard, with numerical ratings used for particular classes. [[NFPA 10]] relates the resulting classifications to selection and distribution. The meaning of a letter or number consequently depends on the classification and edition in which it is used.&amp;lt;ref name=&amp;quot;F-fec2bf6e94&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l17&quot;&gt;Line 17:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 17:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Fire classification and agent suitability ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Fire classification and agent suitability ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The NFPA classification described in the 2008 handbook groups fires by the material or condition involved. Class A concerns ordinary combustible solids, while Class B concerns flammable and combustible liquids and related fuel hazards. Class C identifies the involvement of energised electrical equipment. Classes D and K concern combustible metals and cooking media respectively. These letters belong to the NFPA classification discussed in that source.&amp;lt;ref name=&amp;quot;F-644b6cf371&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-72.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The NFPA classification described in the 2008 handbook groups fires by the material or condition involved. Class A concerns ordinary combustible solids, while Class B concerns flammable and combustible liquids and related fuel hazards. Class C identifies the involvement of energised electrical equipment. Classes D and K concern combustible metals and cooking media respectively. These letters belong to the NFPA classification discussed in that source.&amp;lt;ref name=&amp;quot;F-644b6cf371&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-72.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-fire-extinguisher-rating-v2.svg|thumb|upright=1.5|alt=Explain the mechanism supporting fire extinguisher rating.|Explain the mechanism supporting fire extinguisher rating&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cote et al. (2008), chapter 17.5, pp. 17-71–17-72; Cote et al. (2008), chapter 17.5, pp. 17-81–17-82; Cote et al. (2008), chapter 17.5, pp. 17-71–17-74&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-fire-extinguisher-rating-v2.svg|thumb|upright=1.5|alt=Explain the mechanism supporting fire extinguisher rating.|Explain the mechanism supporting fire extinguisher rating.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The classification connects the fire with suitable equipment, but it does not remove the need to identify the actual fuel. Metal fires illustrate this limitation particularly clearly. An agent suitable for one metal may be unsuitable for another, and the metal&amp;#039;s form can influence the fire. A class designation therefore describes a starting point for selection, while the specific extinguishing approval describes a narrower application.&amp;lt;ref name=&amp;quot;F-168b8a6a74&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-81–17-82.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The classification connects the fire with suitable equipment, but it does not remove the need to identify the actual fuel. Metal fires illustrate this limitation particularly clearly. An agent suitable for one metal may be unsuitable for another, and the metal&amp;#039;s form can influence the fire. A class designation therefore describes a starting point for selection, while the specific extinguishing approval describes a narrower application.&amp;lt;ref name=&amp;quot;F-168b8a6a74&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-81–17-82.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l45&quot;&gt;Line 45:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 45:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Inspection, servicing and pressure-vessel condition ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Inspection, servicing and pressure-vessel condition ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An extinguisher&amp;#039;s external appearance provides only part of the evidence about its condition. Inspection can identify obstruction, damage, missing parts or an abnormal indicator. Maintenance examines the equipment more fully and addresses defects affecting continued use. The handbook distinguishes these activities from pressure testing of the container, which concerns the vessel&amp;#039;s ability to withstand the specified test rather than its extinguishing rating.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An extinguisher&amp;#039;s external appearance provides only part of the evidence about its condition. Inspection can identify obstruction, damage, missing parts or an abnormal indicator. Maintenance examines the equipment more fully and addresses defects affecting continued use. The handbook distinguishes these activities from pressure testing of the container, which concerns the vessel&amp;#039;s ability to withstand the specified test rather than its extinguishing rating.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-fire-extinguisher-rating-v3.svg|thumb|upright=1.5|alt=Distinguish complementary evidence needed to assess fire extinguisher rating.|Distinguish complementary evidence needed to assess fire extinguisher rating&lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;. Based on Cote et al. (2008), chapter 17.5, pp. 17-89–17-91; Cote et al. (2008), chapter 17.5, pp. 17-89–17-90; Cote et al. (2008), chapter 17.2, pp. 17-18–17-20&lt;/del&gt;.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-fire-extinguisher-rating-v3.svg|thumb|upright=1.5|alt=Distinguish complementary evidence needed to assess fire extinguisher rating.|Distinguish complementary evidence needed to assess fire extinguisher rating.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A pressure indication and an agent-quantity measurement are not interchangeable. A stored-pressure unit can display pressure without proving that the specified amount or condition of agent is present. Carbon dioxide extinguishers illustrate the need for a separate quantity check because stored liquid and vapour behaviour complicates interpretation from pressure alone. The handbook therefore discusses weighing and other checks appropriate to the particular extinguisher design.&amp;lt;ref name=&amp;quot;F-09d5c93557&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-90.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A pressure indication and an agent-quantity measurement are not interchangeable. A stored-pressure unit can display pressure without proving that the specified amount or condition of agent is present. Carbon dioxide extinguishers illustrate the need for a separate quantity check because stored liquid and vapour behaviour complicates interpretation from pressure alone. The handbook therefore discusses weighing and other checks appropriate to the particular extinguisher design.&amp;lt;ref name=&amp;quot;F-09d5c93557&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-90.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-6184:rev-6587:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Mark</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=6184&amp;oldid=prev</id>
		<title>Peter: Add SVG figures fse-fire-extinguisher-rating-v1.svg, fse-fire-extinguisher-rating-v2.svg, fse-fire-extinguisher-rating-v3.svg (list-4 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=6184&amp;oldid=prev"/>
		<updated>2026-11-12T15:13:13Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-fire-extinguisher-rating-v1.svg, fse-fire-extinguisher-rating-v2.svg, fse-fire-extinguisher-rating-v3.svg (list-4 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 16:13, 12 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;[[Fire extinguisher|fire extinguisher]] rating&amp;#039;&amp;#039;&amp;#039; is a classification of an extinguisher&amp;#039;s fire performance under a specified test system. It differs from the amount of agent contained in the equipment. The Fire Protection Handbook presents agent capacity and rated capability as separate characteristics because the complete discharge arrangement contributes to performance.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-73–17-74.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;[[Fire extinguisher|fire extinguisher]] rating&amp;#039;&amp;#039;&amp;#039; is a classification of an extinguisher&amp;#039;s fire performance under a specified test system. It differs from the amount of agent contained in the equipment. The Fire Protection Handbook presents agent capacity and rated capability as separate characteristics because the complete discharge arrangement contributes to performance.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-73–17-74.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-fire-extinguisher-rating-v1.svg|thumb|upright=1.5|alt=Separate agent capacity from tested performance.|Separate agent capacity from tested performance. Based on Cote et al. (2008), chapter 17.5, pp. 17-73–17-74; Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84; Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-81–17-82.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the NFPA framework discussed by the handbook, [[Fire classes|fire classes]] identify the type of hazard, with numerical ratings used for particular classes. [[NFPA 10]] relates the resulting classifications to selection and distribution. The meaning of a letter or number consequently depends on the classification and edition in which it is used.&amp;lt;ref name=&amp;quot;F-fec2bf6e94&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;In the NFPA framework discussed by the handbook, [[Fire classes|fire classes]] identify the type of hazard, with numerical ratings used for particular classes. [[NFPA 10]] relates the resulting classifications to selection and distribution. The meaning of a letter or number consequently depends on the classification and edition in which it is used.&amp;lt;ref name=&amp;quot;F-fec2bf6e94&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l16&quot;&gt;Line 16:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 17:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Fire classification and agent suitability ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Fire classification and agent suitability ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The NFPA classification described in the 2008 handbook groups fires by the material or condition involved. Class A concerns ordinary combustible solids, while Class B concerns flammable and combustible liquids and related fuel hazards. Class C identifies the involvement of energised electrical equipment. Classes D and K concern combustible metals and cooking media respectively. These letters belong to the NFPA classification discussed in that source.&amp;lt;ref name=&amp;quot;F-644b6cf371&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-72.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The NFPA classification described in the 2008 handbook groups fires by the material or condition involved. Class A concerns ordinary combustible solids, while Class B concerns flammable and combustible liquids and related fuel hazards. Class C identifies the involvement of energised electrical equipment. Classes D and K concern combustible metals and cooking media respectively. These letters belong to the NFPA classification discussed in that source.&amp;lt;ref name=&amp;quot;F-644b6cf371&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-72.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-fire-extinguisher-rating-v2.svg|thumb|upright=1.5|alt=Explain the mechanism supporting fire extinguisher rating.|Explain the mechanism supporting fire extinguisher rating. Based on Cote et al. (2008), chapter 17.5, pp. 17-71–17-72; Cote et al. (2008), chapter 17.5, pp. 17-81–17-82; Cote et al. (2008), chapter 17.5, pp. 17-71–17-74.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The classification connects the fire with suitable equipment, but it does not remove the need to identify the actual fuel. Metal fires illustrate this limitation particularly clearly. An agent suitable for one metal may be unsuitable for another, and the metal&amp;#039;s form can influence the fire. A class designation therefore describes a starting point for selection, while the specific extinguishing approval describes a narrower application.&amp;lt;ref name=&amp;quot;F-168b8a6a74&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-81–17-82.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The classification connects the fire with suitable equipment, but it does not remove the need to identify the actual fuel. Metal fires illustrate this limitation particularly clearly. An agent suitable for one metal may be unsuitable for another, and the metal&amp;#039;s form can influence the fire. A class designation therefore describes a starting point for selection, while the specific extinguishing approval describes a narrower application.&amp;lt;ref name=&amp;quot;F-168b8a6a74&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-81–17-82.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l43&quot;&gt;Line 43:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 45:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Inspection, servicing and pressure-vessel condition ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Inspection, servicing and pressure-vessel condition ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An extinguisher&amp;#039;s external appearance provides only part of the evidence about its condition. Inspection can identify obstruction, damage, missing parts or an abnormal indicator. Maintenance examines the equipment more fully and addresses defects affecting continued use. The handbook distinguishes these activities from pressure testing of the container, which concerns the vessel&amp;#039;s ability to withstand the specified test rather than its extinguishing rating.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An extinguisher&amp;#039;s external appearance provides only part of the evidence about its condition. Inspection can identify obstruction, damage, missing parts or an abnormal indicator. Maintenance examines the equipment more fully and addresses defects affecting continued use. The handbook distinguishes these activities from pressure testing of the container, which concerns the vessel&amp;#039;s ability to withstand the specified test rather than its extinguishing rating.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-fire-extinguisher-rating-v3.svg|thumb|upright=1.5|alt=Distinguish complementary evidence needed to assess fire extinguisher rating.|Distinguish complementary evidence needed to assess fire extinguisher rating. Based on Cote et al. (2008), chapter 17.5, pp. 17-89–17-91; Cote et al. (2008), chapter 17.5, pp. 17-89–17-90; Cote et al. (2008), chapter 17.2, pp. 17-18–17-20.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A pressure indication and an agent-quantity measurement are not interchangeable. A stored-pressure unit can display pressure without proving that the specified amount or condition of agent is present. Carbon dioxide extinguishers illustrate the need for a separate quantity check because stored liquid and vapour behaviour complicates interpretation from pressure alone. The handbook therefore discusses weighing and other checks appropriate to the particular extinguisher design.&amp;lt;ref name=&amp;quot;F-09d5c93557&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-90.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A pressure indication and an agent-quantity measurement are not interchangeable. A stored-pressure unit can display pressure without proving that the specified amount or condition of agent is present. Carbon dioxide extinguishers illustrate the need for a separate quantity check because stored liquid and vapour behaviour complicates interpretation from pressure alone. The handbook therefore discusses weighing and other checks appropriate to the particular extinguisher design.&amp;lt;ref name=&amp;quot;F-09d5c93557&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-90.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-3807:rev-6184:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=3807&amp;oldid=prev</id>
		<title>Thomas: New FSE wiki article: Fire extinguisher rating (written by GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Fire_extinguisher_rating&amp;diff=3807&amp;oldid=prev"/>
		<updated>2026-11-07T21:38:10Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Fire extinguisher rating (written by GPT-6)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;A &amp;#039;&amp;#039;&amp;#039;[[Fire extinguisher|fire extinguisher]] rating&amp;#039;&amp;#039;&amp;#039; is a classification of an extinguisher&amp;#039;s fire performance under a specified test system. It differs from the amount of agent contained in the equipment. The Fire Protection Handbook presents agent capacity and rated capability as separate characteristics because the complete discharge arrangement contributes to performance.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-73–17-74.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the NFPA framework discussed by the handbook, [[Fire classes|fire classes]] identify the type of hazard, with numerical ratings used for particular classes. [[NFPA 10]] relates the resulting classifications to selection and distribution. The meaning of a letter or number consequently depends on the classification and edition in which it is used.&amp;lt;ref name=&amp;quot;F-fec2bf6e94&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-83–17-84.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The [[Extinguishing agent|extinguishing agent]], discharge behaviour and test conditions all matter. A [[Dry chemical extinguishing agent|dry chemical extinguishing agent]] can produce different capabilities in different equipment. Test and listing work associated with organisations such as [[Underwriters Laboratories]] supplies performance evidence, while practical use remains affected by access, the actual fire and the operator.&amp;lt;ref name=&amp;quot;F-3d6eec771d&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74, 17-81–17-82.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Equipment function and interpretation ==&lt;br /&gt;
The rating belongs to the tested extinguisher, not to a generic name for its contents. Agent formulation, stored quantity and discharge characteristics work together. The handbook&amp;#039;s tables show why capacity cannot be treated as a direct numerical substitute for rating. Adding more of an unspecified agent does not establish a proportionate increase in tested fire performance.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The NFPA class symbols also contain different kinds of information. Numerical Class A and Class B ratings do not imply an equivalent numerical scale for Class C, D or K. Metal protection is especially dependent on the particular metal and approved agent. A reader therefore needs the complete designation and its classification system before comparing two pieces of equipment.&amp;lt;ref name=&amp;quot;F-3d6eec771d&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Laboratory or classification performance is not a prediction of every possible incident. Fuel distribution, obstruction and continuing fuel input can change the practical task. The handbook relates selection to the expected hazard and user capability, rather than treating the rating as a guarantee of success. It also distinguishes ordinary solid, liquid, electrical and metal-fire considerations.&amp;lt;ref name=&amp;quot;F-3d6eec771d&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Distribution decisions use the rating within a separate placement framework. The relevant questions include which hazards the extinguisher serves and the actual route needed to reach it. A highly rated unit cannot compensate automatically for an obstructed or unsuitable location. The rating remains one defined piece of evidence within the complete manual-protection arrangement.&amp;lt;ref name=&amp;quot;F-7a8785d1cd&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-83–17-84.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Fire classification and agent suitability ==&lt;br /&gt;
The NFPA classification described in the 2008 handbook groups fires by the material or condition involved. Class A concerns ordinary combustible solids, while Class B concerns flammable and combustible liquids and related fuel hazards. Class C identifies the involvement of energised electrical equipment. Classes D and K concern combustible metals and cooking media respectively. These letters belong to the NFPA classification discussed in that source.&amp;lt;ref name=&amp;quot;F-644b6cf371&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-72.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The classification connects the fire with suitable equipment, but it does not remove the need to identify the actual fuel. Metal fires illustrate this limitation particularly clearly. An agent suitable for one metal may be unsuitable for another, and the metal&amp;#039;s form can influence the fire. A class designation therefore describes a starting point for selection, while the specific extinguishing approval describes a narrower application.&amp;lt;ref name=&amp;quot;F-168b8a6a74&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-81–17-82.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Electrical involvement also requires careful interpretation. It identifies a conductivity concern during agent application, rather than a separate combustible substance. The burning material can still present an ordinary solid or liquid fuel problem. Removal of electrical energy changes one aspect of the hazard, but does not itself establish that the remaining fire is extinguished. Agent conductivity and the underlying fuel consequently require separate consideration.&amp;lt;ref name=&amp;quot;F-e7a8199012&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-71–17-74.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Names used in different technical traditions can conceal distinctions. In the handbook&amp;#039;s terminology, dry chemical agents include bicarbonate and phosphate formulations for their specified fire classes. Dry powders for Class D protection are separately selected for combustible metals. Treating every particulate extinguishant as interchangeable obscures differences in mechanism, application and compatibility. The label, formulation and applicable test evidence give the term its practical meaning.&amp;lt;ref name=&amp;quot;F-a895b6ce44&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.2, pp. 17-18–17-20.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-168b8a6a74&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Capacity, rating and tested performance ==&lt;br /&gt;
The quantity of agent contained in an extinguisher is its capacity, expressed in an appropriate mass or volume. A fire rating instead describes performance established under a specified classification and test system. Two extinguishers with similar quantities can therefore have different ratings. The Fire Protection Handbook presents capacity and rating separately because agent properties and discharge performance both influence the result.&amp;lt;ref name=&amp;quot;F-2c2522abfc&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
In the NFPA system discussed by the handbook, numerical ratings accompany the Class A and Class B designations. The other class designations convey different information and do not provide an equivalent numerical scale for every hazard. A rating must consequently be interpreted within its own classification. Comparing unlike letters or treating a numeral as a universal measure of fire size gives a misleading result.&amp;lt;ref name=&amp;quot;F-3d6eec771d&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The classification tests do not reproduce every possible fire arrangement. Accessibility, fuel depth, obstructions and the person operating the extinguisher influence practical use. The handbook connects selection with hazard extent and the capabilities of the expected user. A tested rating is therefore evidence about equipment performance under the test conditions. It does not eliminate differences between those conditions and a real incident.&amp;lt;ref name=&amp;quot;F-e7a8199012&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Rating and distribution also answer different questions. Rating helps identify an appropriate extinguisher for the hazard, while distribution addresses whether suitable equipment can be reached. The handbook&amp;#039;s placement discussion combines hazard assessment, floor-area coverage and travel distance. A larger rated extinguisher in one location does not automatically resolve an inaccessible route elsewhere. Selection and location remain linked parts of the protection arrangement.&amp;lt;ref name=&amp;quot;F-7a8785d1cd&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Location, access and the human response ==&lt;br /&gt;
Portable extinguishers depend on someone discovering the fire, recognising the available equipment and making an appropriate response. They therefore differ from automatic systems that initiate discharge from a sensor signal. The handbook relates extinguisher selection to the people expected to use the equipment as well as to the fire. The weight, handling arrangement and operating characteristics belong within that assessment.&amp;lt;ref name=&amp;quot;F-e7a8199012&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Location affects whether the selected equipment is practically available. The relevant route follows the actual means of access around partitions, furniture and other obstacles. A distance measured directly through a wall does not represent the travel required to reach the extinguisher. The handbook consequently treats travel distance, floor-area coverage and hazard location as related placement questions, rather than relying only on geometric proximity.&amp;lt;ref name=&amp;quot;F-7a8785d1cd&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Visibility and physical access are also different from the presence of a symbol on a plan. Equipment can become obstructed as the building&amp;#039;s contents change, and the location may cease to serve the original hazard. The IFEG lifecycle approach identifies management during use and review after alterations as parts of maintaining fire safety. These responsibilities connect the documented arrangement with the conditions that occupants encounter.&amp;lt;ref name=&amp;quot;I-7b0907c015&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.6–0.3.2.8; pp. 0.3-6–0.3-7.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Human response includes interpretation as well as movement. Introduction to Fire Safety Engineering separates becoming aware of a threat, deciding what to do and carrying out the response. Those stages explain why equipment availability alone cannot determine response time. Familiarity with the building, information about the event and the person&amp;#039;s role can affect the sequence before any physical intervention begins.&amp;lt;ref name=&amp;quot;V-43c46d9927&amp;quot;&amp;gt;Van Rossum (2027), §7.1–7.3.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Inspection, servicing and pressure-vessel condition ==&lt;br /&gt;
An extinguisher&amp;#039;s external appearance provides only part of the evidence about its condition. Inspection can identify obstruction, damage, missing parts or an abnormal indicator. Maintenance examines the equipment more fully and addresses defects affecting continued use. The handbook distinguishes these activities from pressure testing of the container, which concerns the vessel&amp;#039;s ability to withstand the specified test rather than its extinguishing rating.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-91.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A pressure indication and an agent-quantity measurement are not interchangeable. A stored-pressure unit can display pressure without proving that the specified amount or condition of agent is present. Carbon dioxide extinguishers illustrate the need for a separate quantity check because stored liquid and vapour behaviour complicates interpretation from pressure alone. The handbook therefore discusses weighing and other checks appropriate to the particular extinguisher design.&amp;lt;ref name=&amp;quot;F-09d5c93557&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.5, pp. 17-89–17-90.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Dry chemical formulations also require attention to moisture, caking and compatibility. The agent must flow through its intended discharge path, and replacement material must suit the equipment. The handbook warns against mixing incompatible formulations because the resulting condition can impair operation. Servicing is consequently a controlled activity tied to the extinguisher and agent specifications, rather than simply restoring a nominal mass of any similar-looking powder.&amp;lt;ref name=&amp;quot;F-a895b6ce44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-09d5c93557&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Records distinguish observed condition, servicing and return to availability. After use or a defect, the protection arrangement may temporarily differ from the original plan. The IFEG framework connects maintenance responsibilities with continuing building operation and management of change. Historical service intervals in the 2008 handbook are not a substitute for identifying the edition and equipment requirements governing a particular installation.&amp;lt;ref name=&amp;quot;I-7b0907c015&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Matching the agent to the hazard ==&lt;br /&gt;
The first selection question concerns the material that is burning. Ordinary solid combustibles, flammable liquids, cooking fats and combustible metals do not respond identically to the same agent. The Fire Protection Handbook consequently relates extinguisher selection to fire classification and to the specific hazard within that classification. A familiar agent name is not sufficient evidence of suitability for every material in a broad group.&amp;lt;ref name=&amp;quot;F-3d6eec771d&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Electrical equipment adds another selection question. Conductivity concerns the possibility of an electrical path through the applied agent, while residue concerns contamination after discharge. These characteristics are distinct from extinguishing effectiveness. An agent can be electrically non-conductive yet leave deposits that are undesirable around sensitive equipment. Conversely, a water-based formulation does not become electrically non-conductive merely because an additive improves its wetting or foaming behaviour.&amp;lt;ref name=&amp;quot;F-a895b6ce44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-0052ff3c01&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.3, pp. 17-36–17-38.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The physical arrangement of the fire also matters. A surface flame, a concealed hot mass and a continuing release of burning liquid present different delivery and re-ignition problems. Rapid flame removal does not necessarily cool the underlying material sufficiently. Protection of a process can therefore include isolation of its fuel or heat source as well as application of the selected extinguishing medium.&amp;lt;ref name=&amp;quot;F-72d0b0d751&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.1, pp. 17-5–17-8.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-12dd7bc483&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.2, pp. 17-24–17-26.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Compatibility extends to the equipment carrying the agent. Concentrate, powder formulation, seals, valves and discharge devices form a specified combination. The handbook identifies both incompatible dry chemicals and foam systems requiring matched proportioning and discharge equipment. Substitution based only on a similar generic description can change flow or extinguishing performance. The applicable product information and test evidence describe the combination being assessed.&amp;lt;ref name=&amp;quot;F-a895b6ce44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F-25576ee9a2&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.4, pp. 17-50–17-52, 17-64.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Protection objectives and limits of performance ==&lt;br /&gt;
Suppression describes an intended change in a fire, but the required outcome needs further definition. Control can limit growth or reduce the rate of heat release without extinguishing every burning item. Extinguishment removes the continuing combustion under the conditions considered. Prevention of renewed burning may require cooling, continued agent retention or removal of an ignition source. These outcomes impose different demands on the protection arrangement.&amp;lt;ref name=&amp;quot;F-a7e389f0f3&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.3, pp. 17-32–17-33.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-5d55059c9a&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.6, pp. 17-119–17-121.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Agent selection follows the fuel and the objective. Water can cool a solid surface, foam can maintain a barrier over a liquid, and a gaseous agent can change the atmosphere surrounding a fire. None of these descriptions establishes universal effectiveness. The protected material, fire geometry, ventilation and available delivery arrangement determine whether the relevant mechanism can operate where it is needed.&amp;lt;ref name=&amp;quot;F-4ad60f14bc&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.3, pp. 17-32–17-33, 17-36–17-38.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F-36233581a2&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.4, pp. 17-45–17-49.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The assessment also distinguishes successful operation from unsuccessful or delayed operation. An explicit example appears in Australia&amp;#039;s Fire Safety Verification Method Standard, 2022 edition. Its structural-stability scenario considers failures of suppression, delayed fire brigade intervention and combinations of failures. That requirement belongs to the Australian method and its stated scenario. It illustrates why the mere presence of equipment is insufficient evidence of the building&amp;#039;s performance.&amp;lt;ref name=&amp;quot;B-2b63577d33&amp;quot;&amp;gt;Australian Building Codes Board (2022), §2.12.2; p. 19.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The protection claim consequently includes its conditions of use. These include the hazard, the quantity and distribution of agent, the expected activation sequence and the time for which protection is maintained. Changes to storage, ventilation or operating procedures can alter those conditions. The International Fire Engineering Guidelines connect continued building use and alterations with review of the original engineering assumptions.&amp;lt;ref name=&amp;quot;I-7b0907c015&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Commissioning, maintenance and change ==&lt;br /&gt;
An installed system needs evidence that its components perform the intended sequence together. Commissioning examines the arrangement as built, including supplies, controls and the interfaces with the protected process. A component test establishes only the behaviour observed under that test. The Australian part of the International Fire Engineering Guidelines treats commissioning as a distinct stage connecting design and subsequent occupation or use.&amp;lt;ref name=&amp;quot;I-f73f312240&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), §0.3.2.4–0.3.2.6; pp. 0.3-6–0.3-7.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Inspection and functional testing provide complementary information. Physical examination can reveal corrosion, obstruction, leakage or changes around the hazard. Functional tests can demonstrate flow, proportioning, signalling or mechanical movement under specified conditions. The Fire Protection Handbook&amp;#039;s foam-system discussion separates these checks from the more extensive task of demonstrating complete extinguishing performance. It also recognises test arrangements that avoid unnecessarily discharging agent over the protected equipment.&amp;lt;ref name=&amp;quot;F-2ef4d8b6a4&amp;quot;&amp;gt;Cote et al. (2008), chapter 17.4, pp. 17-68.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Records connect observations with the installation&amp;#039;s intended performance. An indicated pressure, for example, establishes a different fact from a measured agent quantity or a demonstrated discharge pattern. The handbook makes this distinction particularly clear for portable extinguishers. A satisfactory observation must therefore be interpreted in relation to what was measured, rather than treated as proof that every possible failure has been excluded.&amp;lt;ref name=&amp;quot;F-739a9f298d&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Continuing performance also depends on management of change. A modified appliance, altered storage arrangement or new partition may change the hazard while leaving the protection equipment apparently intact. Maintenance alone cannot restore a design assumption that no longer describes the site. The IFEG lifecycle approach consequently connects alterations, operational responsibilities and maintenance with the original fire engineering assessment and its documented conditions.&amp;lt;ref name=&amp;quot;I-7b0907c015&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Commercial vehicle fire]]&lt;br /&gt;
* [[Dry powder extinguishing agent]]&lt;br /&gt;
* [[Fire extinguisher maintenance]]&lt;br /&gt;
* [[Listing and labelling]]&lt;br /&gt;
* [[Stored-pressure fire extinguisher]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Australian Building Codes Board. (2022). &amp;#039;&amp;#039;Fire Safety Verification Method Standard 2022&amp;#039;&amp;#039;.&lt;br /&gt;
* Cote, A. E., Grant, C. C., Hall, J. R., Jr., &amp;amp; Solomon, R. E. (Eds.). (2008). &amp;#039;&amp;#039;Fire Protection Handbook&amp;#039;&amp;#039; (20th ed.). National Fire Protection Association.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International Fire Engineering Guidelines&amp;#039;&amp;#039; (2005 ed.). Australian Building Codes Board.&lt;br /&gt;
* Van Rossum, E. (2027). &amp;#039;&amp;#039;Introduction to Fire Safety Engineering&amp;#039;&amp;#039;. Fire Safety Academy.&lt;br /&gt;
&lt;br /&gt;
[[Category:Fire Suppression]]&lt;/div&gt;</summary>
		<author><name>Thomas</name></author>
	</entry>
</feed>