<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Extinguishing_agent</id>
	<title>Extinguishing agent - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Extinguishing_agent"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;action=history"/>
	<updated>2026-11-04T12:29:59Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=2783&amp;oldid=prev</id>
		<title>Jan: Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=2783&amp;oldid=prev"/>
		<updated>2026-11-02T18:21:54Z</updated>

		<summary type="html">&lt;p&gt;Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 19:21, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l142&quot;&gt;Line 142:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 142:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== References ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== References ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, pp. 4-72–4-87&lt;/ins&gt;). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Iqbal, N., &amp;amp; Salley, M. H. (2004). &amp;#039;&amp;#039;Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program&amp;#039;&amp;#039; (NUREG-1805). U.S. Nuclear Regulatory Commission.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Iqbal, N., &amp;amp; Salley, M. H. (2004). &amp;#039;&amp;#039;Fire dynamics tools (FDTs): Quantitative fire hazard analysis methods for the U.S. Nuclear Regulatory Commission fire protection inspection program&amp;#039;&amp;#039; (NUREG-1805). U.S. Nuclear Regulatory Commission.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Mawhinney, J. R., &amp;amp; Back, G. G., III. (2002). Water mist fire suppression systems. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Mawhinney, J. R., &amp;amp; Back, G. G., III. (2002). Water mist fire suppression systems. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, pp. 4-311–4-337&lt;/ins&gt;). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno (Ed.), &#039;&#039;SFPE handbook of fire protection engineering&#039;&#039; (3rd ed.&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;, pp. 4-88–4-122&lt;/ins&gt;). National Fire Protection Association.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Van Rossum, E. (2027). &amp;#039;&amp;#039;Introduction to Fire Safety Engineering&amp;#039;&amp;#039;. Fire Safety Academy.&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;* Van Rossum, E. (2027). &amp;#039;&amp;#039;Introduction to Fire Safety Engineering&amp;#039;&amp;#039;. Fire Safety Academy.&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Category:Fire Suppression]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Category:Fire Suppression]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-2657:rev-2783:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=2657&amp;oldid=prev</id>
		<title>Jan: Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=2657&amp;oldid=prev"/>
		<updated>2026-11-02T17:39:46Z</updated>

		<summary type="html">&lt;p&gt;Improve Basic article: verified sources, clearer explanation, calculations and links (GPT-6)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;amp;diff=2657&amp;amp;oldid=1114&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=1114&amp;oldid=prev</id>
		<title>Sanne: Add diagrams fse-extinguishing-agent-v1.svg, fse-extinguishing-agent-v2.svg, fse-extinguishing-agent-v3.svg (level-1 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=1114&amp;oldid=prev"/>
		<updated>2026-11-02T07:20:29Z</updated>

		<summary type="html">&lt;p&gt;Add diagrams fse-extinguishing-agent-v1.svg, fse-extinguishing-agent-v2.svg, fse-extinguishing-agent-v3.svg (level-1 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 08:20, 2 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l8&quot;&gt;Line 8:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 8:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The [[Extinguishing mechanisms]] described in NUREG-1805 fall into four groups. Fuel can be separated from the flame, oxygen can be removed or diluted, temperatures can be reduced, or chemicals can modify combustion reactions. Real agents commonly use more than one group at the same time.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The [[Extinguishing mechanisms]] described in NUREG-1805 fall into four groups. Fuel can be separated from the flame, oxygen can be removed or diluted, temperatures can be reduced, or chemicals can modify combustion reactions. Real agents commonly use more than one group at the same time.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-extinguishing-agent-v1.svg|thumb|upright=1.5|alt=Four panels show fuel separation, oxygen reduction, cooling and chemical interference.|Four groups of extinguishing action can occur together. Based on U.S. Nuclear Regulatory Commission (2005), p. B-15.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Cooling water reduces the production of gaseous fuel from a heated solid. It also reduces flame temperature and the feedback of heat to that solid. Water turning to steam can additionally impede oxygen supply in some confined conditions, while fog can reduce radiant heat transfer.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Cooling water reduces the production of gaseous fuel from a heated solid. It also reduces flame temperature and the feedback of heat to that solid. Water turning to steam can additionally impede oxygen supply in some confined conditions, while fog can reduce radiant heat transfer.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l26&quot;&gt;Line 26:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 27:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Flammable-liquid fires require attention to the liquid&amp;#039;s behaviour. Water is denser than many hydrocarbon fuels and does not mix with them. Such fuel can float and continue burning, so an appropriate [[Firefighting foam]] may provide a surface blanket where plain water cannot.&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-88&amp;quot;&amp;gt;Scheffey (2002), p. 4-88.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Flammable-liquid fires require attention to the liquid&amp;#039;s behaviour. Water is denser than many hydrocarbon fuels and does not mix with them. Such fuel can float and continue burning, so an appropriate [[Firefighting foam]] may provide a surface blanket where plain water cannot.&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-88&amp;quot;&amp;gt;Scheffey (2002), p. 4-88.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-extinguishing-agent-v2.svg|thumb|upright=1.5|alt=Selection moves from fuel and geometry to compatibility, delivery and post-discharge hazards.|Agent selection depends on more than a fire-class letter. Based on U.S. Nuclear Regulatory Commission (2005), pp. B-15–B-16 and Scheffey (2002), p. 4-88.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water-miscible liquids present a different problem. Sufficient water can dilute them, but that can take a long time in a deep pool. Alcohol-resistant foam is formulated to protect its blanket against breakdown by polar solvents, making formulation more specific than a generic foam label.&amp;lt;ref name=&amp;quot;NUREG-B58&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. B-57–B-58.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-89&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water-miscible liquids present a different problem. Sufficient water can dilute them, but that can take a long time in a deep pool. Alcohol-resistant foam is formulated to protect its blanket against breakdown by polar solvents, making formulation more specific than a generic foam label.&amp;lt;ref name=&amp;quot;NUREG-B58&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. B-57–B-58.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-89&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l84&quot;&gt;Line 84:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 86:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Re-ignition is a separate phase of the assessment. Hot fuel, glowing material and a damaged foam blanket can permit combustion to return after the initial agent action ends. Adequate post-discharge coverage or retention is consequently different from initial flame knockdown.&amp;lt;ref name=&amp;quot;NUREG-B44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Re-ignition is a separate phase of the assessment. Hot fuel, glowing material and a damaged foam blanket can permit combustion to return after the initial agent action ends. Adequate post-discharge coverage or retention is consequently different from initial flame knockdown.&amp;lt;ref name=&amp;quot;NUREG-B44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-extinguishing-agent-v3.svg|thumb|upright=1.5|alt=A delivery chain branches to fire control, extinction or renewed burning after agent loss.|Flame knockdown is not the whole suppression assessment. Based on U.S. Nuclear Regulatory Commission (2005), pp. B-43–B-44.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Agent delivery may also alter visibility and access. Powder clouds and space-filling foam can make it harder to locate remaining hot material. Inspection after suppression must account for those conditions rather than assuming that a clear view immediately follows discharge.&amp;lt;ref name=&amp;quot;NUREG-B57&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Agent delivery may also alter visibility and access. Powder clouds and space-filling foam can make it harder to locate remaining hot material. Inspection after suppression must account for those conditions rather than assuming that a clear view immediately follows discharge.&amp;lt;ref name=&amp;quot;NUREG-B57&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-697:rev-1114:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Sanne</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=697&amp;oldid=prev</id>
		<title>Jan: New FSE wiki article: Extinguishing agent (written by Kimi Code CLI)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Extinguishing_agent&amp;diff=697&amp;oldid=prev"/>
		<updated>2026-11-02T01:42:33Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Extinguishing agent (written by Kimi Code CLI)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;An &amp;#039;&amp;#039;&amp;#039;Extinguishing agent&amp;#039;&amp;#039;&amp;#039; is a substance used to stop combustion, limit its spread or prevent it from starting again. Water, foam, dry powders and gaseous agents work in different ways. Their performance depends on the fuel, fire form, enclosure, delivery method and compatibility with surrounding materials.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-15.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot;&amp;gt;Fleming (2002), p. 4-72.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An agent is not defined by one universal action. Water often cools both fuel and flame, while foam can separate a liquid surface from air and radiant heat. Powders can interfere with flame chemistry and coat a solid. A single discharge can combine several of these actions.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B55&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-55.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Selection therefore begins with the fire rather than with a preferred product. The agent must reach the burning region in a useful form and remain effective long enough. An agent that removes visible flame may still leave hot fuel or deep-seated combustion capable of re-ignition.&amp;lt;ref name=&amp;quot;NUREG-B44&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. B-43–B-44.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-89&amp;quot;&amp;gt;Scheffey (2002), p. 4-89.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Actions on a fire ==&lt;br /&gt;
&lt;br /&gt;
The [[Extinguishing mechanisms]] described in NUREG-1805 fall into four groups. Fuel can be separated from the flame, oxygen can be removed or diluted, temperatures can be reduced, or chemicals can modify combustion reactions. Real agents commonly use more than one group at the same time.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Cooling water reduces the production of gaseous fuel from a heated solid. It also reduces flame temperature and the feedback of heat to that solid. Water turning to steam can additionally impede oxygen supply in some confined conditions, while fog can reduce radiant heat transfer.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water has a high specific heat and latent heat of vaporisation. Fleming gives an example in which one gallon absorbs 2,586.5 kJ while rising from 21 °C to steam at 100 °C. That illustrates heat capacity, not a guaranteed extinguishing capacity for a fire of any particular size.&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Foam acts differently on a liquid pool. A blanket limits contact with air and reduces radiant heating of the liquid. Cooling can reduce vapour pressure, while water draining from foam can dilute a water-soluble fuel. These contributions vary with the liquid and the condition of the blanket.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Dry chemicals can affect active species in flame reactions. They can also absorb heat, obstruct radiation and, for some formulations, form a surface coating. Particle size and chemical composition both affect performance, so powder cannot be selected by mass alone.&amp;lt;ref name=&amp;quot;NUREG-B55&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Gaseous agents include halocarbon and inert-gas types. NUREG-1805 describes chemical flame inhibition for halogenated agents and oxygen reduction for inert gases. Their distribution and retention in an enclosure influence whether the necessary conditions persist.&amp;lt;ref name=&amp;quot;NUREG-B41&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-41.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Matching the agent to the fuel ==&lt;br /&gt;
&lt;br /&gt;
[[Fire classes]] group fires to support agent selection, but their letters and meanings differ between systems. The examples here use the US classifications reproduced in NUREG-1805. They should not be treated as identical to classifications used elsewhere.&amp;lt;ref name=&amp;quot;NUREG-B16&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-16.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Ordinary combustibles such as wood, cloth and paper can often be cooled and wetted with water. Some dry powders also form a coating over these materials. That coating can matter where glowing or deep-seated combustion remains after the flames have disappeared.&amp;lt;ref name=&amp;quot;NUREG-B16&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B56&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-56.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Flammable-liquid fires require attention to the liquid&amp;#039;s behaviour. Water is denser than many hydrocarbon fuels and does not mix with them. Such fuel can float and continue burning, so an appropriate [[Firefighting foam]] may provide a surface blanket where plain water cannot.&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-88&amp;quot;&amp;gt;Scheffey (2002), p. 4-88.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water-miscible liquids present a different problem. Sufficient water can dilute them, but that can take a long time in a deep pool. Alcohol-resistant foam is formulated to protect its blanket against breakdown by polar solvents, making formulation more specific than a generic foam label.&amp;lt;ref name=&amp;quot;NUREG-B58&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. B-57–B-58.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-89&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Energised electrical equipment changes the selection because an electrically conductive stream can create a shock hazard. NUREG-1805 identifies particular nonconductive agents for its US Class C examples. The classification concerns the electrical condition, not a new fuel that disappears when power is isolated.&amp;lt;ref name=&amp;quot;NUREG-B16&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Combustible metals need agents tested for the particular metal and situation. NUREG-1805 warns against water-based agents in its Class D table because an agent must not react harmfully with the metal. A general-purpose label is not evidence of suitability for every metal fire.&amp;lt;ref name=&amp;quot;NUREG-B16&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Cooking oils and fats also require suitable application. Water introduced beneath very hot oil can vaporise and eject burning material. Wet chemical and other agents listed for the applicable fire classification must be distinguished from an arbitrary water discharge.&amp;lt;ref name=&amp;quot;NUREG-B16&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B58&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Forms and delivery ==&lt;br /&gt;
&lt;br /&gt;
A [[Fire extinguisher]] stores a limited quantity for manual use. Its contents, nozzle and operating arrangement are designed as one unit. The label and tested application are therefore more informative than the appearance of the cylinder or the broad agent family.&amp;lt;ref name=&amp;quot;NUREG-B56&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-60.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fixed systems can deliver an agent through a pipe network and nozzles. Water-based sprinkler systems release water where heat opens individual heads in common arrangements. Deluge systems instead use open outlets and a separate detection system, so the area receiving water is determined differently.&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot;&amp;gt;Fleming (2002), p. 4-73.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A [[Water mist system]] divides water into much finer sprays than conventional sprinklers. The cited fire-protection definition includes no drops larger than 1 mm. Smaller droplets offer more surface for heat transfer and evaporation, but nozzle performance remains specific to the tested design.&amp;lt;ref name=&amp;quot;Mawhinney-4-311&amp;quot;&amp;gt;Mawhinney and Back (2002), p. 4-311.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A [[Gaseous extinguishing system]] can distribute agent through an enclosure without the residue associated with powders. Enclosure leakage, openings and ventilation can reduce concentration. Deep-seated material can also remain hot after surface flames disappear, leading to renewed burning when air returns.&amp;lt;ref name=&amp;quot;NUREG-B44&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Foam delivery involves proportioning concentrate into water, generating bubbles and distributing the foam. Each stage affects the final blanket. A correct concentrate stored beside an incompatible proportioner or application device does not establish a functioning suppression system.&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Agent quantity and application rate must be considered together. Foam exposed to flame breaks down and loses water, so application must replace losses while preserving a residual layer. For powders and gases, losses through openings can likewise reduce the amount remaining at the fire.&amp;lt;ref name=&amp;quot;NUREG-B59&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-59.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B56&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Compatibility and secondary effects ==&lt;br /&gt;
&lt;br /&gt;
No agent is universally harmless. Water can react with particular materials to produce heat, flammable or toxic gases, or explosions. Fleming notes that sufficient water can sometimes overcome a reaction involving minor quantities, but that does not make water a default choice for reactive substances.&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water and water-based foam can also create electrical hazards. Their use near energised equipment must follow the tested system and applicable safety arrangements. Extinguishing the original fire does not remove hazards introduced by the extinguishing medium.&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Dry powder discharge can reduce visibility and cause temporary breathing difficulty. Residue requires cleaning and can damage delicate electrical equipment. Monoammonium phosphate is described in NUREG-1805 as more corrosive than several alternative powders because of its acidic products.&amp;lt;ref name=&amp;quot;NUREG-B56&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B57&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-57.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Gaseous agents can change the atmosphere within an enclosure. Their physiological effects depend on the agent and concentration, so they cannot all be treated as safe merely because they leave little residue. System design must address occupancy and exposure conditions for the particular agent.&amp;lt;ref name=&amp;quot;NUREG-B41&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fire effluent and agent decomposition products can remain after discharge. Historical descriptions of Halon performance in NUREG-1805 belong to their period and application. They are not evidence of current environmental acceptability or permission to install a particular substance.&amp;lt;ref name=&amp;quot;NUREG-B43&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), p. B-43.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Selection and application evidence ==&lt;br /&gt;
&lt;br /&gt;
Agent selection starts by defining the physical fire problem. A surface flame, a deep-seated solid fire and a running-liquid fire present different targets. The target determines whether cooling, surface coverage or chemical flame inhibition is most useful, and whether the agent can physically reach it.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-88&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Geometry can change the result even when the fuel remains the same. Scheffey distinguishes a two-dimensional liquid pool from a pressurised spray or running fuel. Foam that spreads across a horizontal pool may not cover the moving surfaces of the three-dimensional fire.&amp;lt;ref name=&amp;quot;Scheffey-4-88&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The agent&amp;#039;s state during storage and discharge also matters. Water can be delivered as a conventional spray or as fine droplets, while gases can be stored under pressure and dispersed through a room. Dry powder must flow without caking and be projected into the fire by a gas.&amp;lt;ref name=&amp;quot;Mawhinney-4-311&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B55&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Formulation properties need to survive the complete delivery process. Foam must be proportioned and aerated correctly, powder must retain suitable flow characteristics, and gas must disperse before excessive leakage occurs. The name of the stored material alone does not describe those operational conditions.&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B56&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Product and system test evidence should correspond to the intended fuel and discharge arrangement. Fleming&amp;#039;s discussion of sprinklers explains that special products are approved for particular goals and are not automatically interchangeable. The same distinction prevents a generic suppression claim from replacing relevant application testing.&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Water supply quality can affect more than hydraulics. Foam properties can change with contaminants, and small water-mist passages can be affected by blockage. Agent selection therefore includes the condition of the supply and the maintenance needed to preserve it.&amp;lt;ref name=&amp;quot;NUREG-B59&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Mawhinney-4-311&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A system assessment should also record what happens after discharge. Water runoff, powder residue, foam solution and altered enclosure atmospheres create different recovery problems. These consequences do not necessarily outweigh fire control, but they belong to the selection evidence rather than being discovered afterwards.&amp;lt;ref name=&amp;quot;NUREG-B57&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Control, extinction and re-ignition ==&lt;br /&gt;
&lt;br /&gt;
Control limits the fire&amp;#039;s development and protects surrounding fuels. It can be achieved while some burning continues, whereas extinction requires the combustion process to cease. These outcomes should not be exchanged when interpreting a test or describing an installed system.&amp;lt;ref name=&amp;quot;NUREG-10-1&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Suppression can begin before flames disappear. Cooling hot gases reduces their ability to heat other fuels, while surface wetting reduces further pyrolysis. A falling heat-release rate can therefore be a meaningful response even where small flames remain temporarily.&amp;lt;ref name=&amp;quot;NUREG-B15&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Mawhinney-4-314&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Re-ignition is a separate phase of the assessment. Hot fuel, glowing material and a damaged foam blanket can permit combustion to return after the initial agent action ends. Adequate post-discharge coverage or retention is consequently different from initial flame knockdown.&amp;lt;ref name=&amp;quot;NUREG-B44&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Agent delivery may also alter visibility and access. Powder clouds and space-filling foam can make it harder to locate remaining hot material. Inspection after suppression must account for those conditions rather than assuming that a clear view immediately follows discharge.&amp;lt;ref name=&amp;quot;NUREG-B57&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B60&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Performance and limits ==&lt;br /&gt;
&lt;br /&gt;
Extinguishment is not the same as control. A system can reduce heat release and prevent spread while combustion continues. In other circumstances, cooling adjacent material can prevent ignition even when the initial fuel continues to burn.&amp;lt;ref name=&amp;quot;Fleming-4-72&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-10-1&amp;quot;&amp;gt;U.S. Nuclear Regulatory Commission (2005), pp. 10-1–10-2.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Visible flame extinction is also not proof that a fire is out. NUREG-1805 describes cable tests in which internal temperatures continued to rise after a gaseous agent removed surface flames. Re-ignition occurred when ventilation restored air. The fuel condition and retention period therefore matter.&amp;lt;ref name=&amp;quot;NUREG-B44&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Suppression evidence is often empirical. Fleming explains that complex water-suppression mechanisms have not supported a complete general design calculation. Sprinkler criteria consequently draw on full-scale tests and experience rather than a single universal suppression equation.&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Laboratory agent concentrations require the same caution. Water-mist experiments can use ideal mixing between spray and flame that is difficult to reproduce at enclosure scale. A measured laboratory concentration cannot by itself determine nozzle spacing or flow in an actual system.&amp;lt;ref name=&amp;quot;Mawhinney-4-313&amp;quot;&amp;gt;Mawhinney and Back (2002), pp. 4-313–4-314.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The useful description of an agent includes its chemistry, physical form, tested fuels, delivery conditions and secondary effects. Omitting any of these can turn a valid test result into an incorrect generalisation. Selection is ultimately a property of the complete application, not only of the substance in storage.&amp;lt;ref name=&amp;quot;NUREG-B59&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Scheffey-4-88&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Fine water sprays illustrate why delivery form belongs in the agent description. Mawhinney and Back identify gas-phase cooling, oxygen depletion with vapour dilution, and surface wetting as primary mechanisms. Radiation attenuation and kinetic effects are secondary in their review, with their relative importance changing between applications.&amp;lt;ref name=&amp;quot;Mawhinney-4-313&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Mawhinney-4-314&amp;quot;&amp;gt;Mawhinney and Back (2002), p. 4-314.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The powder family also contains meaningful chemical differences. NUREG-1805 lists sodium and potassium compounds and monoammonium phosphate among dry agents. Their relative test performance depends on particle size as well as chemistry, and only some formulations provide the surface coating associated with deep-seated ordinary-combustible fires.&amp;lt;ref name=&amp;quot;NUREG-B55&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;NUREG-B56&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Inert gases and halocarbon gases should not be grouped as chemically identical products. The former primarily reduce available oxygen, while the latter can also affect flame reactions. Their storage volumes, distribution and physiological consequences require agent-specific evaluation.&amp;lt;ref name=&amp;quot;NUREG-B41&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The most useful selection question is therefore not which agent is strongest in general. It is whether a specified agent, delivered under specified conditions, achieves the required fire outcome without unacceptable reactions or secondary hazards. That question preserves both the physical evidence and the limits of the application.&amp;lt;ref name=&amp;quot;NUREG-B59&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;Fleming-4-73&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
&lt;br /&gt;
* [[Aqueous film-forming foam (AFFF)]]&lt;br /&gt;
* [[Fire suppression system]]&lt;br /&gt;
* [[Fire tetrahedron]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
&lt;br /&gt;
* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Mawhinney, J. R., &amp;amp; Back, G. G., III. (2002). Water mist fire suppression systems. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* Scheffey, J. L. (2002). Foam agents and AFFF system design considerations. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed.). National Fire Protection Association.&lt;br /&gt;
* U.S. Nuclear Regulatory Commission. (2005). &amp;#039;&amp;#039;Fire dynamics tools: Quantitative fire hazard analysis methods for the U.S. nuclear regulatory commission fire protection inspection program&amp;#039;&amp;#039; (NUREG-1805). Author.&lt;br /&gt;
&lt;br /&gt;
[[Category:Fire Suppression]]&lt;/div&gt;</summary>
		<author><name>Jan</name></author>
	</entry>
</feed>