<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Dry_hydrant</id>
	<title>Dry hydrant - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://fire-safety.academy/w/index.php?action=history&amp;feed=atom&amp;title=Dry_hydrant"/>
	<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;action=history"/>
	<updated>2026-11-21T22:13:02Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.43.11</generator>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=9492&amp;oldid=prev</id>
		<title>Peter: Wiki review: corrected 8 errors: citation (8) (Claude Opus 5.5)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=9492&amp;oldid=prev"/>
		<updated>2026-11-16T00:32:08Z</updated>

		<summary type="html">&lt;p&gt;Wiki review: corrected 8 errors: citation (8) (Claude Opus 5.5)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 01:32, 16 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l1&quot;&gt;Line 1:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 1:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&#039;&#039;&#039;Dry hydrant&#039;&#039;&#039; is a normally unpressurised permanent suction connection between a static water source and fire-service pumping equipment. &amp;lt;ref name=&quot;H_13_4_13-43_13-45&quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-43–13-45.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;T_4-68&quot;&amp;gt;Titus (2002), ch. 4-2, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 4-68.&amp;lt;/ref&amp;gt; It makes water accessible without establishing a pressurised distribution supply. Performance depends on the source level, submerged intake, airtight piping, apparatus access and pump suction conditions. Its name must be distinguished from a dry-barrel hydrant connected to a pressurised main. &amp;lt;ref name=&quot;H_13_4_13-43_13-45&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&#039;&#039;&#039;Dry hydrant&#039;&#039;&#039; is a normally unpressurised permanent suction connection between a static water source and fire-service pumping equipment. &amp;lt;ref name=&quot;H_13_4_13-43_13-45&quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-43–13-45.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;T_4-68&quot;&amp;gt;Titus (2002), ch. 4-2, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 4-68.&amp;lt;/ref&amp;gt; It makes water accessible without establishing a pressurised distribution supply. Performance depends on the source level, submerged intake, airtight piping, apparatus access and pump suction conditions. Its name must be distinguished from a dry-barrel hydrant connected to a pressurised main. &amp;lt;ref name=&quot;H_13_4_13-43_13-45&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The supply assessment follows the complete route from the source to useful water at the incident. Seasonal minimum conditions, withdrawal limits, transport and initial availability can each govern the result. Total water volume is therefore different from sustained delivered flow. The mobilisation and handling involved also distinguish these arrangements from an immediately available automatic supply for a fixed sprinkler installation. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-49.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-65.&amp;lt;/ref&amp;gt; Availability can change with both season and weather. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-44.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The supply assessment follows the complete route from the source to useful water at the incident. Seasonal minimum conditions, withdrawal limits, transport and initial availability can each govern the result. Total water volume is therefore different from sustained delivered flow. The mobilisation and handling involved also distinguish these arrangements from an immediately available automatic supply for a fixed sprinkler installation. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-49.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-65.&amp;lt;/ref&amp;gt; Availability can change with both season and weather. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-44.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== A permanent suction connection ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== A permanent suction connection ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The installation provides an [[Alternative water supply|alternative water supply]] connection where an ordinary pressurised [[Fire hydrant|fire hydrant]] is unavailable or unsuitable; [[Drafting|drafting]] equipment draws through the permanent pipe. The [[Fire water supply|fire water supply]] therefore depends on the pump and extraction arrangement as well as the source volume. A well-placed connection reduces setup difficulties but cannot remove the physical limits of suction. &amp;lt;ref name=&quot;H_13_4_13-37_13-43_13-45&quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37,13-43–13-45.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The installation provides an [[Alternative water supply|alternative water supply]] connection where an ordinary pressurised [[Fire hydrant|fire hydrant]] is unavailable or unsuitable; [[Drafting|drafting]] equipment draws through the permanent pipe. The [[Fire water supply|fire water supply]] therefore depends on the pump and extraction arrangement as well as the source volume. A well-placed connection reduces setup difficulties but cannot remove the physical limits of suction. &amp;lt;ref name=&quot;H_13_4_13-37_13-43_13-45&quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37, 13-43–13-45.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-dry-hydrant-v1.svg|thumb|upright=1.5|alt=Dry hydrant: functional relationships. Measurement and water paths are distinct.|Dry hydrant: functional relationships. Schematic explanation; dimensions are not installation instructions.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-dry-hydrant-v1.svg|thumb|upright=1.5|alt=Dry hydrant: functional relationships. Measurement and water paths are distinct.|Dry hydrant: functional relationships. Schematic explanation; dimensions are not installation instructions.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l23&quot;&gt;Line 23:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 23:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The same distinction applies when assessing a static source against a fire-flow demand; a pond may contain sufficient total water while its access or intake supports too little continuous withdrawal. A rapid initial discharge may exhaust a small available reserve before replenishment becomes effective. Both rate and duration are therefore assessed through the actual extraction and transport chain. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-49&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-24.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The same distinction applies when assessing a static source against a fire-flow demand; a pond may contain sufficient total water while its access or intake supports too little continuous withdrawal. A rapid initial discharge may exhaust a small available reserve before replenishment becomes effective. Both rate and duration are therefore assessed through the actual extraction and transport chain. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-49&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-24.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These arrangements can support manual firefighting without constituting an automatic sprinkler supply; their dependence on mobilisation, priming, transport and connection must remain visible in the fire safety analysis. The handbook distinguishes automatic availability from water that requires human action before delivery. Treating the latter as immediately available would omit the delays that define its operation. &amp;lt;ref name=&quot;H_15_4_15-63_15-65&quot; /&amp;gt;&amp;lt;ref name=&quot;H_13_4_13-37_13-47_13-49&quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37,13-47–13-49.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;These arrangements can support manual firefighting without constituting an automatic sprinkler supply; their dependence on mobilisation, priming, transport and connection must remain visible in the fire safety analysis. The handbook distinguishes automatic availability from water that requires human action before delivery. Treating the latter as immediately available would omit the delays that define its operation. &amp;lt;ref name=&quot;H_15_4_15-63_15-65&quot; /&amp;gt;&amp;lt;ref name=&quot;H_13_4_13-37_13-47_13-49&quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37, 13-47–13-49.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Suction conditions and cavitation ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Suction conditions and cavitation ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&quot;H_15_6_15-91&quot;&amp;gt;Cote (2008), ch. 15.6, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;T_4-68&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&quot;H_15_6_15-91&quot;&amp;gt;Cote (2008), ch. 15.6, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;T_4-68&quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-dry-hydrant-v3.svg|thumb|upright=1.5|alt=Available suction head. Measurement and water paths are distinct.|Available suction head. Schematic explanation; dimensions are not installation instructions.]]&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[File:fse-dry-hydrant-v3.svg|thumb|upright=1.5|alt=Available suction head. Measurement and water paths are distinct.|Available suction head. Schematic explanation; dimensions are not installation instructions.]]&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l95&quot;&gt;Line 95:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 95:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;|}&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;|}&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Using the handbook&#039;s rounded SI inputs gives a vehicle volume of 5,678 L and a delivery factor of 0.9. Filling takes 3 minutes, discharge takes 4 minutes, and the two travel legs take 4.22 and 4.25 minutes. The full cycle is therefore 15.47 minutes. Recalculation gives approximately 330 L/min as the cycle-average contribution. &amp;lt;ref name=&quot;H_13_4_13-49&quot;&amp;gt;Cote (2008), ch. 13.4, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 13-49.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Using the handbook&#039;s rounded SI inputs gives a vehicle volume of 5,678 L and a delivery factor of 0.9. Filling takes 3 minutes, discharge takes 4 minutes, and the two travel legs take 4.22 and 4.25 minutes. The full cycle is therefore 15.47 minutes. Recalculation gives approximately 330 L/min as the cycle-average contribution. &amp;lt;ref name=&quot;H_13_4_13-49&quot;&amp;gt;Cote (2008), ch. 13.4, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 13-49.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A fleet calculation cannot assume that every additional vehicle contributes that rate under unchanged conditions; queues at a common fill point or discharge point increase the cycle time. Limited access can also prevent simultaneous manoeuvres. The result must therefore represent the planned operation, including the capacity of the shared equipment. &amp;lt;ref name=&amp;quot;H_13_4_13-47_13-49&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A fleet calculation cannot assume that every additional vehicle contributes that rate under unchanged conditions; queues at a common fill point or discharge point increase the cycle time. Limited access can also prevent simultaneous manoeuvres. The result must therefore represent the planned operation, including the capacity of the shared equipment. &amp;lt;ref name=&amp;quot;H_13_4_13-47_13-49&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l129&quot;&gt;Line 129:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 129:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Inspection, testing and maintenance provide different forms of evidence; visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation&amp;#039;s intended state. &amp;lt;ref name=&amp;quot;H_16_11_16-205_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-205–16-212.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Inspection, testing and maintenance provide different forms of evidence; visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation&amp;#039;s intended state. &amp;lt;ref name=&amp;quot;H_16_11_16-205_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-205–16-212.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance; a system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. &amp;lt;ref name=&quot;H_16_11_16-205&quot;&amp;gt;Cote (2008), ch. 16.11, &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 16-205.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance; a system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. &amp;lt;ref name=&quot;H_16_11_16-205&quot;&amp;gt;Cote (2008), ch. 16.11, &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 16-205.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position; neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. &amp;lt;ref name=&amp;quot;H_16_3_16-42_16-43&amp;quot;&amp;gt;Cote (2008), ch. 16.3, pp. 16-42–16-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-209_16-210&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-209–16-210.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position; neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. &amp;lt;ref name=&amp;quot;H_16_3_16-42_16-43&amp;quot;&amp;gt;Cote (2008), ch. 16.3, pp. 16-42–16-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-209_16-210&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-209–16-210.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l135&quot;&gt;Line 135:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 135:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Deposits on a sprinkler can interfere with heating or mechanical release; corrosion can affect both the operating mechanism and water passage. Inside pipes, scale or foreign material can migrate to smaller fittings and outlets. These mechanisms explain why an apparently pressurised system may still have reduced effective protection. &amp;lt;ref name=&amp;quot;H_16_11_16-207_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-207–16-212.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Deposits on a sprinkler can interfere with heating or mechanical release; corrosion can affect both the operating mechanism and water passage. Inside pipes, scale or foreign material can migrate to smaller fittings and outlets. These mechanisms explain why an apparently pressurised system may still have reduced effective protection. &amp;lt;ref name=&amp;quot;H_16_11_16-207_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-207–16-212.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The purpose of a test determines its interpretation; an alarm test can establish signalling without demonstrating the full water demand. A main-drain comparison can reveal a changed supply condition without reproducing every operating sprinkler. A pump start test exercises starting functions, while a flow test examines delivery capability over selected operating points. &amp;lt;ref name=&quot;H_14_4_14-42_14-43&quot;&amp;gt;Cote (2008), ch. 14.4, pp. 14-42–14-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;H_16_11_16-210_16-211_16-220&quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-210–16-211,16-220.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The purpose of a test determines its interpretation; an alarm test can establish signalling without demonstrating the full water demand. A main-drain comparison can reveal a changed supply condition without reproducing every operating sprinkler. A pump start test exercises starting functions, while a flow test examines delivery capability over selected operating points. &amp;lt;ref name=&quot;H_14_4_14-42_14-43&quot;&amp;gt;Cote (2008), ch. 14.4, pp. 14-42–14-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&quot;H_16_11_16-210_16-211_16-220&quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-210–16-211, 16-220.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;−&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #ffe49c; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The International Fire Engineering Guidelines (IFEG) links commissioning to the performance assumed in a fire engineering evaluation; it also links subsequent management and maintenance to keeping those assumptions valid. This provides a useful framework for reading test records: the observation must answer the performance question being claimed. Successful operation of one component is evidence about that component and the functions actually exercised. &amp;lt;ref name=&quot;I_1_7-8&quot;&amp;gt;National Research Council of Canada et al. (2005), &lt;del style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;pp&lt;/del&gt;. 1.7-8.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The International Fire Engineering Guidelines (IFEG) links commissioning to the performance assumed in a fire engineering evaluation; it also links subsequent management and maintenance to keeping those assumptions valid. This provides a useful framework for reading test records: the observation must answer the performance question being claimed. Successful operation of one component is evidence about that component and the functions actually exercised. &amp;lt;ref name=&quot;I_1_7-8&quot;&amp;gt;National Research Council of Canada et al. (2005), &lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;p&lt;/ins&gt;. 1.7-8.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== See also ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== See also ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-6332:rev-9492:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Peter</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=6332&amp;oldid=prev</id>
		<title>Mark: Add SVG figures fse-dry-hydrant-v1.svg, fse-dry-hydrant-v2.svg, fse-dry-hydrant-v3.svg (list-5 visual plan)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=6332&amp;oldid=prev"/>
		<updated>2026-11-12T18:44:09Z</updated>

		<summary type="html">&lt;p&gt;Add SVG figures fse-dry-hydrant-v1.svg, fse-dry-hydrant-v2.svg, fse-dry-hydrant-v3.svg (list-5 visual plan)&lt;/p&gt;
&lt;table style=&quot;background-color: #fff; color: #202122;&quot; data-mw=&quot;interface&quot;&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;col class=&quot;diff-marker&quot; /&gt;
				&lt;col class=&quot;diff-content&quot; /&gt;
				&lt;tr class=&quot;diff-title&quot; lang=&quot;en&quot;&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;← Older revision&lt;/td&gt;
				&lt;td colspan=&quot;2&quot; style=&quot;background-color: #fff; color: #202122; text-align: center;&quot;&gt;Revision as of 19:44, 12 November 2026&lt;/td&gt;
				&lt;/tr&gt;&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l5&quot;&gt;Line 5:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 5:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== A permanent suction connection ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== A permanent suction connection ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The installation provides an [[Alternative water supply|alternative water supply]] connection where an ordinary pressurised [[Fire hydrant|fire hydrant]] is unavailable or unsuitable; [[Drafting|drafting]] equipment draws through the permanent pipe. The [[Fire water supply|fire water supply]] therefore depends on the pump and extraction arrangement as well as the source volume. A well-placed connection reduces setup difficulties but cannot remove the physical limits of suction. &amp;lt;ref name=&amp;quot;H_13_4_13-37_13-43_13-45&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37,13-43–13-45.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;The installation provides an [[Alternative water supply|alternative water supply]] connection where an ordinary pressurised [[Fire hydrant|fire hydrant]] is unavailable or unsuitable; [[Drafting|drafting]] equipment draws through the permanent pipe. The [[Fire water supply|fire water supply]] therefore depends on the pump and extraction arrangement as well as the source volume. A well-placed connection reduces setup difficulties but cannot remove the physical limits of suction. &amp;lt;ref name=&amp;quot;H_13_4_13-37_13-43_13-45&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37,13-43–13-45.&amp;lt;/ref&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-dry-hydrant-v1.svg|thumb|upright=1.5|alt=Dry hydrant: functional relationships. Measurement and water paths are distinct.|Dry hydrant: functional relationships. Schematic explanation; dimensions are not installation instructions.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Net positive suction head]] connects the source level and intake losses to the pump&amp;#039;s available operating margin; a screened intake addresses debris while suitable submergence limits air entry. Pipe joints must remain airtight, and low points or exposed portions need consideration under freezing conditions. A visible connection head alone does not demonstrate the condition of the submerged and buried route. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;[[Net positive suction head]] connects the source level and intake losses to the pump&amp;#039;s available operating margin; a screened intake addresses debris while suitable submergence limits air entry. Pipe joints must remain airtight, and low points or exposed portions need consideration under freezing conditions. A visible connection head alone does not demonstrate the condition of the submerged and buried route. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l12&quot;&gt;Line 12:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 13:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Static sources and fireground logistics ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Static sources and fireground logistics ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A natural or stored source is useful only if water can be withdrawn when the incident occurs; seasonal low level, drought, ice and sediment can reduce usable capacity or obstruct the intake. Access routes and the standing area for apparatus are part of the withdrawal arrangement. Surface area alone therefore says little about the dependable firefighting supply. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A natural or stored source is useful only if water can be withdrawn when the incident occurs; seasonal low level, drought, ice and sediment can reduce usable capacity or obstruct the intake. Access routes and the standing area for apparatus are part of the withdrawal arrangement. Surface area alone therefore says little about the dependable firefighting supply. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-dry-hydrant-v2.svg|thumb|upright=1.5|alt=From static water to effective delivery. Measurement and water paths are distinct.|From static water to effective delivery. Schematic explanation; dimensions are not installation instructions.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A dry hydrant provides a permanent suction connection to a static source; the pipe is normally unpressurised, and apparatus supplies the pumping action. The intake arrangement excludes troublesome debris while remaining suitably submerged. Connections and joints must preserve the suction path, since admitting air can prevent reliable withdrawal even without a visible outward water leak. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;A dry hydrant provides a permanent suction connection to a static source; the pipe is normally unpressurised, and apparatus supplies the pumping action. The intake arrangement excludes troublesome debris while remaining suitably submerged. Connections and joints must preserve the suction path, since admitting air can prevent reliable withdrawal even without a visible outward water leak. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot; id=&quot;mw-diff-left-l25&quot;&gt;Line 25:&lt;/td&gt;
&lt;td colspan=&quot;2&quot; class=&quot;diff-lineno&quot;&gt;Line 27:&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Suction conditions and cavitation ==&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;== Suction conditions and cavitation ==&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&amp;#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation; pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&amp;#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td colspan=&quot;2&quot; class=&quot;diff-side-deleted&quot;&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot; data-marker=&quot;+&quot;&gt;&lt;/td&gt;&lt;td style=&quot;color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #a3d3ff; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;&lt;ins style=&quot;font-weight: bold; text-decoration: none;&quot;&gt;[[File:fse-dry-hydrant-v3.svg|thumb|upright=1.5|alt=Available suction head. Measurement and water paths are distinct.|Available suction head. Schematic explanation; dimensions are not installation instructions.]]&lt;/ins&gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;br&gt;&lt;/td&gt;&lt;/tr&gt;
&lt;tr&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Available net positive suction head describes the installation&amp;#039;s suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-92&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-92.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;td class=&quot;diff-marker&quot;&gt;&lt;/td&gt;&lt;td style=&quot;background-color: #f8f9fa; color: #202122; font-size: 88%; border-style: solid; border-width: 1px 1px 1px 4px; border-radius: 0.33em; border-color: #eaecf0; vertical-align: top; white-space: pre-wrap;&quot;&gt;&lt;div&gt;Available net positive suction head describes the installation&amp;#039;s suction energy above vapour-pressure head; required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-92&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-92.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;/div&gt;&lt;/td&gt;&lt;/tr&gt;

&lt;!-- diff cache key firesb_pjbsiy42-wiki_:diff:1.41:old-3856:rev-6332:php=table --&gt;
&lt;/table&gt;</summary>
		<author><name>Mark</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=3856&amp;oldid=prev</id>
		<title>Daan: Refine sentence flow and printed-page reference locators (written by GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=3856&amp;oldid=prev"/>
		<updated>2026-11-07T21:39:19Z</updated>

		<summary type="html">&lt;p&gt;Refine sentence flow and printed-page reference locators (written by GPT-6)&lt;/p&gt;
&lt;a href=&quot;https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;amp;diff=3856&amp;amp;oldid=3480&quot;&gt;Show changes&lt;/a&gt;</summary>
		<author><name>Daan</name></author>
	</entry>
	<entry>
		<id>https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=3480&amp;oldid=prev</id>
		<title>Daan: New FSE wiki article: Dry hydrant (written by GPT-6)</title>
		<link rel="alternate" type="text/html" href="https://fire-safety.academy/w/index.php?title=Dry_hydrant&amp;diff=3480&amp;oldid=prev"/>
		<updated>2026-11-07T21:27:49Z</updated>

		<summary type="html">&lt;p&gt;New FSE wiki article: Dry hydrant (written by GPT-6)&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&amp;#039;&amp;#039;&amp;#039;Dry hydrant&amp;#039;&amp;#039;&amp;#039; is a normally unpressurised permanent suction connection between a static water source and fire-service pumping equipment. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-43–13-45.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-68.&amp;lt;/ref&amp;gt; It makes water accessible without establishing a pressurised distribution supply. Performance depends on the source level, submerged intake, airtight piping, apparatus access and pump suction conditions. Its name must be distinguished from a dry-barrel hydrant connected to a pressurised main. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The supply assessment follows the complete route from the source to useful water at the incident. Seasonal minimum conditions, withdrawal limits, transport and initial availability can each govern the result. Total water volume is therefore different from sustained delivered flow. The mobilisation and handling involved also distinguish these arrangements from an immediately available automatic supply for a fixed sprinkler installation. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-49.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-65.&amp;lt;/ref&amp;gt; Availability can change with both season and weather. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-40–13-44.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== A permanent suction connection ==&lt;br /&gt;
The installation provides an [[Alternative water supply|alternative water supply]] connection where an ordinary pressurised [[Fire hydrant|fire hydrant]] is unavailable or unsuitable. [[Drafting]] equipment draws through the permanent pipe. The [[Fire water supply|fire water supply]] therefore depends on the pump and extraction arrangement as well as the source volume. A well-placed connection reduces setup difficulties but cannot remove the physical limits of suction. &amp;lt;ref name=&amp;quot;H_13_4_13-37_13-43_13-45&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37,13-43–13-45.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
[[Net positive suction head]] connects the source level and intake losses to the pump&amp;#039;s available operating margin. A screened intake addresses debris while suitable submergence limits air entry. Pipe joints must remain airtight, and low points or exposed portions need consideration under freezing conditions. A visible connection head alone does not demonstrate the condition of the submerged and buried route. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The same source can support a [[Water shuttle|water shuttle]] fill operation where the logistics permit. That introduces loading rate, access and vehicle-turnaround constraints. The dependable withdrawal rate and the dependable transported rate are different quantities. Both need comparison with the intended fireground demand and duration. &amp;lt;ref name=&amp;quot;H_13_4_13-47_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-47–13-49.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Static sources and fireground logistics ==&lt;br /&gt;
A natural or stored source is useful only if water can be withdrawn when the incident occurs. Seasonal low level, drought, ice and sediment can reduce usable capacity or obstruct the intake. Access routes and the standing area for apparatus are part of the withdrawal arrangement. Surface area alone therefore says little about the dependable firefighting supply. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-44&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A dry hydrant provides a permanent suction connection to a static source. The pipe is normally unpressurised, and apparatus supplies the pumping action. The intake arrangement excludes troublesome debris while remaining suitably submerged. Connections and joints must preserve the suction path, since admitting air can prevent reliable withdrawal even without a visible outward water leak. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Drafting introduces limits that differ from receiving water under positive pressure. The available atmospheric-pressure head must cover lift, suction losses and the margin above vapour pressure required by the pump. Longer piping, restrictive fittings and falling source level reduce that available margin. A nominal pump capacity quoted under other conditions does not establish drafting performance at the site. &amp;lt;ref name=&amp;quot;H_13_4_13-43_13-45&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68_4-69&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-68–4-69.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Transporting water adds time and handling constraints. A vehicle repeatedly fills, travels, discharges and returns. Fill and dump arrangements can become bottlenecks when several vehicles share them. The fireground also needs water while these cycles develop, so an initial reserve and sustained delivery rate answer different operational questions. &amp;lt;ref name=&amp;quot;H_13_4_13-47_13-49&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The same distinction applies when assessing a static source against a fire-flow demand. A pond may contain sufficient total water while its access or intake supports too little continuous withdrawal. A rapid initial discharge may exhaust a small available reserve before replenishment becomes effective. Both rate and duration are therefore assessed through the actual extraction and transport chain. &amp;lt;ref name=&amp;quot;H_13_4_13-40_13-49&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-24.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
These arrangements can support manual firefighting without constituting an automatic sprinkler supply. Their dependence on mobilisation, priming, transport and connection must remain visible in the fire safety analysis. The handbook distinguishes automatic availability from water that requires human action before delivery. Treating the latter as immediately available would omit the delays that define its operation. &amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_13_4_13-37_13-47_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-37,13-47–13-49.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Suction conditions and cavitation ==&lt;br /&gt;
Water approaching an impeller must retain enough absolute pressure to avoid excessive vapour formation. Pressure falls as flow accelerates through the inlet region. If local pressure reaches the water&amp;#039;s vapour pressure, bubbles can form and subsequently collapse in higher-pressure regions. This cavitation can produce noise, vibration, loss of performance and material damage. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Available net positive suction head describes the installation&amp;#039;s suction energy above vapour-pressure head. Required net positive suction head describes a pump characteristic supplied by the manufacturer for stated operating conditions. The two quantities must be compared at the relevant flow and speed. They are not two alternative names for a suction gauge reading. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-92&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-92.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For a large open reservoir, the following form separates atmospheric pressure, water level and suction losses. The reservoir surface velocity is treated as negligible. A positive elevation difference means that the water surface is above the pump reference. A lower surface contributes a negative term. &amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;NPSH_a=\frac{p_a-p_v}{\rho g}+z_s-z_p-h_s&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;NPSH_a&amp;lt;/math&amp;gt; || Available net positive suction head || m&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;p_a,p_v&amp;lt;/math&amp;gt; || Absolute atmospheric and vapour pressures || Pa&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\rho,g&amp;lt;/math&amp;gt; || Water density and gravitational acceleration || kg/m³; m/s²&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;z_s,z_p,h_s&amp;lt;/math&amp;gt; || Surface elevation, pump elevation and suction loss || m&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The lowest usable tank level can be more demanding than the initial full condition. A greater flow increases suction-pipe loss and can also increase the pump&amp;#039;s required suction head. Warmer water increases vapour pressure, while atmospheric pressure varies with elevation. These effects explain why a universal maximum suction lift cannot represent every installation. &amp;lt;ref name=&amp;quot;H_15_6_15-91_15-95&amp;quot;&amp;gt;Cote (2008), ch. 15.6, pp. 15-91–15-95.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;T_4-68&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The handbook illustrates a pump requiring approximately 3.05 m of suction head at 7,570 L/min and 5.49 m at 11,400 L/min. These are converted values from one illustrative manufacturer&amp;#039;s-style curve, not general acceptance limits. Their significance is the changing requirement as flow rises. The appropriate comparison uses the actual pump data and the available head under the corresponding supply condition. &amp;lt;ref name=&amp;quot;H_15_6_15-91&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Pressure, flow and energy ==&lt;br /&gt;
Water pressure describes only one part of the energy available in a pipe. Elevation contributes potential energy, while movement contributes velocity head. Titus describes these quantities using head, expressed as an equivalent height of water. A hydraulic calculation must therefore compare locations through a common energy balance, rather than subtracting unrelated gauge readings. &amp;lt;ref name=&amp;quot;T_4-45_4-48&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-45–4-48.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
For steady, incompressible flow, the energy balance adds pump head and subtracts irreversible losses between two sections. The following form assumes that section-average velocity adequately represents kinetic energy. It describes a defined flow path, with all elevations measured from the same datum. Sudden changes require a different, transient analysis. &amp;lt;ref name=&amp;quot;T_4-47_4-50&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-47–4-50.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;\frac{p_1}{\rho g}+\frac{v_1^2}{2g}+z_1+H_p=\frac{p_2}{\rho g}+\frac{v_2^2}{2g}+z_2+h_L&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;p&amp;lt;/math&amp;gt; || Pressure at the section || Pa&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;\rho&amp;lt;/math&amp;gt; || Water density || kg/m³&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;g&amp;lt;/math&amp;gt; || Gravitational acceleration || m/s²&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;v&amp;lt;/math&amp;gt; || Mean velocity || m/s&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;z,H_p,h_L&amp;lt;/math&amp;gt; || Elevation, added pump head and head loss || m&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
Pressure can decrease because water rises, because velocity increases, or because energy is dissipated. These effects have different physical meanings. An elevation change can be recovered on a descending route, whereas friction dissipates mechanical energy. A larger pipe can reduce friction but cannot remove the elevation difference between the source and the outlet. &amp;lt;ref name=&amp;quot;T_4-47_4-52&amp;quot;&amp;gt;Titus (2002), ch. 4-2, pp. 4-47–4-52.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Continuity provides the corresponding flow constraint: volume flow equals cross-sectional area multiplied by mean velocity. The same flow moves faster through a smaller internal bore. At a junction, incoming and outgoing flows balance, while losses depend on the flow assigned to each connected segment. Nominal pipe size alone does not supply the internal diameter needed for this calculation. &amp;lt;ref name=&amp;quot;T_4-47_4-50&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_16_3_16-41_16-42&amp;quot;&amp;gt;Cote (2008), ch. 16.3, pp. 16-41–16-42.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The pressure at a sprinkler is the pressure remaining after the complete upstream route has been considered. It is not the pressure indicated beside a remote pump or street hydrant. The route includes connecting mains, valves, elevation and distribution piping. Leaving out an inconvenient section creates an apparently favourable calculation without providing the corresponding water at the outlet. &amp;lt;ref name=&amp;quot;F_4-75_4-81&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-75–4-81.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;N_xxxvii_xxxviii&amp;quot;&amp;gt;Hopkins et al. (2005), pp. xxxvii–xxxviii.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Calculating transport throughput ==&lt;br /&gt;
The average delivery from a water-carrying vehicle is the usable quantity delivered during one complete cycle divided by the cycle time. The time includes filling, loaded travel, discharge and return travel. Manoeuvring and connection delays belong in the relevant operation. Omitting them overstates the continuous supply that the vehicle can maintain. &amp;lt;ref name=&amp;quot;H_13_4_13-48_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-48–13-49.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The handbook expresses this relationship with a factor allowing for less than complete delivery of the nominal load. That factor describes the assumed operation rather than changing the vehicle&amp;#039;s physical tank volume. The equation gives a cycle average; it does not imply that discharge occurs uniformly throughout the trip. &amp;lt;ref name=&amp;quot;H_13_4_13-48_13-49&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;Q_{av}=\frac{kV}{t_f+t_o+t_d+t_r}&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;Q_{av}&amp;lt;/math&amp;gt; || Average delivered flow || L/min&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;V,k&amp;lt;/math&amp;gt; || Nominal vehicle volume and delivery factor || L; dimensionless&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;t_f,t_o,t_d,t_r&amp;lt;/math&amp;gt; || Fill, outbound travel, dump and return times || min&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
Using the handbook&amp;#039;s rounded SI inputs gives a vehicle volume of 5,678 L and a delivery factor of 0.9. Filling takes 3 minutes, discharge takes 4 minutes, and the two travel legs take 4.22 and 4.25 minutes. The full cycle is therefore 15.47 minutes. Recalculation gives approximately 330 L/min as the cycle-average contribution. &amp;lt;ref name=&amp;quot;H_13_4_13-49&amp;quot;&amp;gt;Cote (2008), ch. 13.4, pp. 13-49.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A fleet calculation cannot assume that every additional vehicle contributes that rate under unchanged conditions. Queues at a common fill point or discharge point increase the cycle time. Limited access can also prevent simultaneous manoeuvres. The result must therefore represent the planned operation, including the capacity of the shared equipment. &amp;lt;ref name=&amp;quot;H_13_4_13-47_13-49&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The demand comparison is made against sustained effective delivery and the initial water reserve. A brief high discharge rate from a portable tank is not itself a replenishment rate. Likewise, a large vehicle volume does not compensate for an indefinitely long turnaround. The calculation makes these trade-offs visible without predicting fire extinguishment from delivered volume alone. &amp;lt;ref name=&amp;quot;H_13_4_13-47_13-49&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Flow, pressure and duration ==&lt;br /&gt;
A fire water supply has several necessary characteristics: adequate flow, sufficient pressure at that flow, an appropriate duration and availability when needed. These characteristics cannot replace one another. A large reservoir may have insufficient delivery capacity, while a high-pressure connection may offer too little sustained flow. The required combination depends on the fire protection demand being assessed. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-67&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-67.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Demand must identify which outlets operate together. Sprinkler calculations assemble the flows of individual operating sprinklers and include other applicable demands under the selected design basis. Municipal fire-flow planning addresses a different question and may include wider firefighting activity. Treating every quoted fire-flow value as a sprinkler demand obscures these differences. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-29&amp;quot;&amp;gt;Cote (2008), ch. 15.2, pp. 15-23–15-29.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-74_4-81&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-74–4-81.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The supply location also matters. A pressure measured in a street main is not automatically available at a building riser. Connecting pipework, backflow assemblies and changes in elevation affect the transfer. The assessment follows the supply through these elements to the same reference point used for the calculated demand. &amp;lt;ref name=&amp;quot;H_15_4_15-63_15-65&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;F_4-81_4-83&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-81–4-83.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Storage introduces a time dimension that a pressure-flow curve alone does not show. Usable water is the quantity that the outlet or pump can actually draw while meeting its operating conditions. Water below the effective intake, or reserved for another purpose, cannot simply be counted as fire reserve. Replenishment contributes only through an identified source and a delivery arrangement that remains available. &amp;lt;ref name=&amp;quot;H_15_1_15-3_15-5&amp;quot;&amp;gt;Cote (2008), ch. 15.1, pp. 15-3–15-5.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot;&amp;gt;Fleming (2002), ch. 4-3, pp. 4-83–4-84.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
A constant-flow volume calculation multiplies flow by duration. In the following form, flow is in litres per minute and usable volume is in cubic metres. The factor converts litres to cubic metres. &amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
&amp;lt;math display=&amp;quot;block&amp;quot;&amp;gt;V_u=\frac{Qt}{1000}&amp;lt;/math&amp;gt;&lt;br /&gt;
&lt;br /&gt;
{| class=&amp;quot;wikitable&amp;quot;&lt;br /&gt;
! Symbol !! Description !! Unit&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;V_u&amp;lt;/math&amp;gt; || Usable water volume || m³&lt;br /&gt;
|-&lt;br /&gt;
| &amp;lt;math&amp;gt;Q,t&amp;lt;/math&amp;gt; || Constant discharge and duration || L/min; min&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
A worked example separates usable water from gross capacity. Using Fleming&amp;#039;s example of 530 L/min for 30 minutes gives 15,900 L, or 15.9 m³, of usable water. This arithmetic does not select a design duration or establish the gross tank volume. The example is a historical worked calculation, with tank configuration and unavailable volume assessed separately. &amp;lt;ref name=&amp;quot;F_4-83_4-84&amp;quot; /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Public supplies can change with domestic use, industrial demand, maintenance and seasonal conditions. Tank levels and pump operation can change during a fire as well. The design record therefore needs the conditions represented by the available supply, including relevant adverse conditions. A favourable isolated reading does not establish availability throughout the required incident duration. &amp;lt;ref name=&amp;quot;H_15_2_15-23_15-24&amp;quot; /&amp;gt;&amp;lt;ref name=&amp;quot;H_15_4_15-63_15-64&amp;quot;&amp;gt;Cote (2008), ch. 15.4, pp. 15-63–15-64.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== Inspection and evidence of readiness ==&lt;br /&gt;
Inspection, testing and maintenance provide different forms of evidence. Visual inspection can identify closed valves, damaged sprinklers, unsuitable storage or missing components. A functional test can demonstrate operation under a defined condition. Maintenance addresses deterioration or defects, while records connect those actions to the installation&amp;#039;s intended state. &amp;lt;ref name=&amp;quot;H_16_11_16-205_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-205–16-212.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The handbook treats changes in occupancy, materials, partitions, ceilings and heating as relevant to sprinkler performance. A system can remain mechanically intact while its design assumptions no longer match the protected hazard. An inspection limited to leaks or gauge readings would miss that change. Readiness therefore includes both equipment condition and the continued relevance of the design basis. &amp;lt;ref name=&amp;quot;H_16_11_16-205&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-205.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
An indicating control valve makes its position observable, while electrical supervision can report departure from the intended position. Neither proves that every downstream route is unobstructed. Flow testing provides different evidence by exercising a water path. Valve identification and drawings help establish which part of the protection is affected by a particular closure. &amp;lt;ref name=&amp;quot;H_16_3_16-42_16-43&amp;quot;&amp;gt;Cote (2008), ch. 16.3, pp. 16-42–16-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-209_16-210&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-209–16-210.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
Deposits on a sprinkler can interfere with heating or mechanical release. Corrosion can affect both the operating mechanism and water passage. Inside pipes, scale or foreign material can migrate to smaller fittings and outlets. These mechanisms explain why an apparently pressurised system may still have reduced effective protection. &amp;lt;ref name=&amp;quot;H_16_11_16-207_16-212&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-207–16-212.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The purpose of a test determines its interpretation. An alarm test can establish signalling without demonstrating the full water demand. A main-drain comparison can reveal a changed supply condition without reproducing every operating sprinkler. A pump start test exercises starting functions, while a flow test examines delivery capability over selected operating points. &amp;lt;ref name=&amp;quot;H_14_4_14-42_14-43&amp;quot;&amp;gt;Cote (2008), ch. 14.4, pp. 14-42–14-43.&amp;lt;/ref&amp;gt;&amp;lt;ref name=&amp;quot;H_16_11_16-210_16-211_16-220&amp;quot;&amp;gt;Cote (2008), ch. 16.11, pp. 16-210–16-211,16-220.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
The International Fire Engineering Guidelines (IFEG) links commissioning to the performance assumed in a fire engineering evaluation. It also links subsequent management and maintenance to keeping those assumptions valid. This provides a useful framework for reading test records: the observation must answer the performance question being claimed. Successful operation of one component is evidence about that component and the functions actually exercised. &amp;lt;ref name=&amp;quot;I_1_7-8&amp;quot;&amp;gt;National Research Council of Canada et al. (2005), pp. 1.7-8.&amp;lt;/ref&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== See also ==&lt;br /&gt;
* [[Fire pump]]&lt;br /&gt;
* [[Jockey pump]]&lt;br /&gt;
* [[Fire pump controller]]&lt;br /&gt;
&lt;br /&gt;
== Notes ==&lt;br /&gt;
&amp;lt;references /&amp;gt;&lt;br /&gt;
&lt;br /&gt;
== References ==&lt;br /&gt;
* Cote, A. E. (Ed.). (2008). &amp;#039;&amp;#039;Fire protection handbook&amp;#039;&amp;#039; (20th ed.). National Fire Protection Association.&lt;br /&gt;
* Fleming, R. P. (2002). Automatic sprinkler system calculations. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 4-72–4-87). National Fire Protection Association.&lt;br /&gt;
* Hopkins, M., Schoenrock, J., &amp;amp; Budnick, E. (2005). &amp;#039;&amp;#039;Fire suppression systems&amp;#039;&amp;#039; (NIST NCSTAR 1-4B). National Institute of Standards and Technology.&lt;br /&gt;
* National Research Council of Canada, International Code Council, Department of Building and Housing, &amp;amp; Australian Building Codes Board. (2005). &amp;#039;&amp;#039;International fire engineering guidelines&amp;#039;&amp;#039;. Australian Building Codes Board.&lt;br /&gt;
* Titus, J. J. (2002). Hydraulics. In P. J. DiNenno (Ed.), &amp;#039;&amp;#039;SFPE handbook of fire protection engineering&amp;#039;&amp;#039; (3rd ed., pp. 4-44–4-71). National Fire Protection Association.&lt;br /&gt;
&lt;br /&gt;
[[Category:Water Supply &amp;amp; Hydraulics]]&lt;/div&gt;</summary>
		<author><name>Daan</name></author>
	</entry>
</feed>